| 2021-12-06 11:08:05 | 12/06/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THIS REVISION APPEARS TO BE DIFFERENT FROM THE |
| | ORIGINAL PERMIT SUBMITTED FOR MASTER 19060556. A |
| | SEPARATE PERMIT AND REVIEW ARE REQUIRED FOR ALL TRADES |
| | AND ZONING PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1 |
| | |
| | 2. THIS APPEARS TO BE A DIFFERENT STRUCTURE AND IF THE |
| | STRUCTURE IS THE FRONT STRUCTURE IT WILL REQUIRE A SET |
| | OF PLAN, REVIEW AND A DIFFERENT PERMIT. IF SO MAY USE |
| | THIS REVISION FOR THE PERMIT AS A MASTER IN THE FRONT |
| | STRUCTURE SO PLEASE REQUEST A CHANGE TO THE PERMIT |
| | LIBRARIAN @ [email protected]. |
| | |
| | 3. THE PLUMBING NOTES REFER TO THE 2014 FBC. PLEASE |
| | CORRECT TO CURRENT EDITION PER THE WPB AMENDMENTS TO |
| | FBC 102.3 APPLICATION OF REFERENCES. |
| | |
| | 4. THESE ARE MULTI-FAMILY DWELLINGS, AND WATER USERS |
| | WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION |
| | ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW |
| | ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF |
| | HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE |
| | BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER |
| | THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND |
| | THEIR CONNECTION CONTROL PROGRAM. A SEPARATE PERMIT IS |
| | REQUIRED FOR THE BACKFLOW DEVICES PER THE WPB |
| | AMENDMENTS TO FBC SEC. 105.1. |
| | |
| | 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. EACH STRUCTURE REQUIRES A GAS |
| | PERMIT. |
| | |
| | A. HOT WATER LINES UNDER SLAB NOT IN CONDITION SPACE |
| | NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020 |
| | FBC SEC. RE 403.5.3. PLEASE PLACE A NOTE. |
| | |
| | B. IF THE TANK-LESS HAS A CONDENSATE IT NEEDS TO BE 1' |
| | AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC. R318.5. |
| | |
| | C. NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS |
| | TIME AND ADDRESS THE COMMENTS ABOVE. THIS WILL HAVE THE |
| | GAS APPROVE FOR A SUB PERMIT, OR IF YOU DECIDED NOT TO |
| | ADDRESS THESE COMMENTS, PLEASE PUT A NOTE ON THE GAS |
| | HEATER (A SEPARATE PERMIT BY A LICENSED CONTRACTOR FOR |
| | THE GAS SYSTEM). THEN PLEASE TAKE OFF ANY GAS SHOWN ON |
| | PLANS; THESE COMMENTS CAN BE FORWARD TO THE GAS |
| | CONTRACTOR FOR REFERENCE. AN N WILL BE PUT ON THIS |
| | REVIEW, WHICH STANDS FOR NOT REQUIRED, BUT A SUB PERMIT |
| | WON'T BE ISSUED ONCE A REVIEW IS DONE FOR THAT SUB |
| | PERMIT, SO PLEASE BE ADVISED ON THIS PROCEDURE. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |