Plan Review Details - Permit 21111243
Plan Review Stops For Permit 21111243
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-09 Cont ID  
Sent By rmcdouga Date 2022-03-09 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2022-03-09 Time 08:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-27 Cont ID  
Sent By rmcdouga Date 2022-01-27 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2022-01-27 Time 16:17 Sent To  
Notes
2022-01-27 16:20:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-12 Cont ID  
Sent By jleahy Date 2022-01-12 Time 14:08 Rev Time 0.00
Received By jleahy Date 2022-01-12 Time 14:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-12-17 Cont ID  
Sent By lcrespo Date 2021-12-17 Time 11:55 Rev Time 0.00
Received By lcrespo Date 2021-12-17 Time 11:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-09 Cont ID  
Sent By rmcdouga Date 2022-03-09 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2022-02-09 Time 06:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-27 Cont ID  
Sent By rmcdouga Date 2022-01-27 Time 16:20 Rev Time 0.00
Received By rmcdouga Date 2021-12-09 Time 07:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-12-17 Cont ID  
Sent By lcrespo Date 2021-12-17 Time 11:56 Rev Time 0.00
Received By lcrespo Date 2021-12-17 Time 11:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-27 Cont ID  
Sent By rmcdouga Date 2022-01-27 Time 16:20 Rev Time 0.00
Received By rmcdouga Date 2022-01-27 Time 16:20 Sent To  
Notes
2022-01-12 14:09:14ELECTRICAL PAGES ARE OK JLEAHY

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-11 Cont ID  
Sent By vbroglia Date 2022-02-11 Time 15:00 Rev Time 0.00
Received By vbroglia Date 2022-02-11 Time 15:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-12-17 Cont ID  
Sent By vbroglia Date 2021-12-17 Time 12:37 Rev Time 0.00
Received By vbroglia Date 2021-12-17 Time 12:37 Sent To  
Notes
***NONE***