| 2022-01-21 11:26:44 | RESIDENTIAL (R3) ALTERATION/ADDITION BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21111240 |
| | |
| | NOTE: |
| | ADDITION SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1 |
| | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| | |
| | 1- THERE IS NOT INFORMATION FOR THE CONSTRUCTION OF THE |
| | "OPEN LATTICE WALL" SHOWN ON TWO SIDES OF CARPORT. |
| | PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW |
| | THIS WALL WILL RESIST THE WIND LOADS. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | 2- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR THE |
| | INSTALLATION OF THE ALUMINUM GATE TO THE STRUCTURE. |
| | SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY |
| | AMENDMENTS. |
| | |
| | 3-LOW SLOPE ROOFS: PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR OVERFLOW DRAINS OR SCUPPERS AS |
| | REQUIRED BY SEC. R903.4.1 FBC-RESIDENTIAL. |
| | PROVIDE DETAILS: SPECIFY SIZE AND LOCATION ON ROOF. |
| | |
| | 4- PRESSURE ZONES DETAIL 4 ON SHEET A-1: |
| | A)THE SPECIFIED DESIGN PRESSURES ARE TOO LOW FOR |
| | COMPONENTS AND CLADDING LOADS. REVISE AS REQUIRED BY |
| | SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | B)CLARIFY ROOF DIAGRAM ROOF ZONES. SPECIFY WHAT IS THE |
| | DIMENSION FOR "A". SEE FIGURE R301.2(7) |
| | FBC-RESIDENTIAL. CLARIFY WHY DESIGN PRESSURES FOR ZONE |
| | 3' ARE LOWER THAN DESIGN PRESSURES FOR ZONE 3 IF IT |
| | LOOKS LIKE ROOF ZONE IS THE OUTER CORNER. ALSO, WHERE |
| | ARE ROOF ZONES 3' AND 3 COMING FROM?. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | 5- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR STEEL |
| | COLUMN TOP CONNECTION. ONLY BASE CONNECTION WAS |
| | PROVIDED. SEC. R301.1 FBC-RESIDENTIAL |
| | |
| | 6- REVISE ROOFING SPECIFICATIONS SHOWN ON SECTION |
| | DETAIL 5 ON SHEET A-2. DESIGN PRESSURES ARE HIGHER THAN |
| | -90PSF ON ROOF ZONE 3. COORDINATE WITH ITEM #4 ABOVE. |
| | |
| | 7- FLAT ROOF NOA 17-1003.04: SELECTED ASSEMBLY ON PAGE |
| | 33 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF |
| | ZONES. REVISE ASSEMBLY FOR ONE THAT MEETS THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES OR SELECT ANY ASSEMBLY |
| | WITH GENERAL LIMITATION #7 THAT ALLOW FOR NAIL |
| | ENHANCEMENT. SIGNED AND SEALED RAS 117 CALCULATIONS ARE |
| | REQUIRED. SEE GENERAL LIMITATIONS #9 AND #7 ON LAST |
| | PAGE OF NOA. |
| | NOTE: COORDINATE WITH ITEMS #4 AND #6 ABOVE. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE REVISED PRODUCT |
| | APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |