Plan Review Details - Permit 21111184
Plan Review Stops For Permit 21111184
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 07:55 Rev Time 0.00
Received By rmcphers Date 2021-12-15 Time 07:55 Sent To  
Notes
2021-12-15 08:04:45FLOORING REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE TYPE OF
 FLOORING AND THE LOCATION OF THE FLOORING - ALSO SHOW
 THE SQUARE FOOTAGE FOR EACH FLOORING TYPE.
  
 2) PLEASE SHOW THE ADDITIONAL JOB VALUE ON THE PLAN
 REVIEW REQUEST FORM IN THE SPACE PROVIDED.
  
 3) ACUSTICAL TEST REPORT PROVIDED FOR "MAXXIM SIM 90
 UNDERLAYMENT" SHOWS A DROP CEILING - TEST REPORT CANNOT
 INCLUDE A DROP CEILING UNLESS THE DROP CEILING
 DESCRIPTION MATCHES YOUR CEILING.
  
 4) PLEASE PROVIDE A FLAME SPREAD TEST REPORT FOR THE
 WOOD FLOORING - FBC 603.1, ALLOWABLE MATERIALS IN NON
 COMBUSTIBLE BUILDINGS, SEE ITEM 2, EXCEPTION 2,
 ACOUSTICAL INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN
 ACCORDANCE WITH ASTM E 84 OR UL 723.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-02 Cont ID  
Sent By pleduc Date 2021-12-02 Time   Rev Time 0.00
Received By pleduc Date 2021-12-02 Time 13:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 08:05 Rev Time 0.00
Received By rmcphers Date 2021-12-01 Time 20:27 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved