Plan Review Details - Permit 21111137
Plan Review Stops For Permit 21111137
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-02-09 Cont ID  
Sent By jwitmer Date 2022-02-09 Time 08:37 Rev Time 0.00
Received By jwitmer Date 2022-02-09 Time 08:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-02 Cont ID  
Sent By jwitmer Date 2022-03-02 Time 06:39 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-02-22 Cont ID  
Sent By jwitmer Date 2022-02-22 Time 06:47 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-02-22 06:48:27WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21111137
 ADD: 1551 FORUM PLACE PL. # 100A
 CONT: HALLMARK CONSTRUCTION LLC
 TEL: 561-586-7664
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. FEB. 22/2022
 ACTION: DENIED
  
 1-4) COMPLIED.
  
 5) 2ND REQUEST. ***** NOTICE ONLY ***** 4X FEE /
 NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH RESPECT
 TO EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 UNDER THE 2020 FBC-EXISTING BUILDING CODE SECTION
 805.3.1EVERY TORY UTILIZED FOR HUMAN OCCUPANCY ON WHICH
 THERE IS WORK AREA THAT INCLUDES EXITS OR CORRIDORS
 SHARED BY MRE THAN ONE TENANT WITHIN THE WORK AREA
 SHALL BE PROVIED WITH MINIMUM NUMBER OF EXITS BASED ON
 THE OCCUPANCY AND OCCUPANT LOAD IN ACCORDANE WITH THE
 FLORIDA BUILDING CODE, BUILDING.
 SHARED EXIT, CONSTRUCTION TYPE III-B, NOT SPRINKLERED,
 OCCUPANT LOAD OF SHARED FIRE RATED COORIDOR IS 56
 (SHEET A-1). PLEASE SEE TABLE 1020.1 CORRIDOR FIRE
 RESISTANCE RATING, BUSINESS>30 OCC. REQUIRES A 1 HOUR
 FIRE RATING!!! FIRE DAMPERS REQUIRED PER 717.5.2 NOT
 SHOWN ON SHEET M-1.
  
 1ST ROUND OF COMMENTS. SHEET A1 SHOWS AT THE REAR OF
 THE TENANT SPACE THERE IS A ONE-HOUR FIRE RATED SHARED
 CORRIDOR. SHEET M-1 SHOWS AIR CONDITIONING DUCTS AND
 RETURN DUCTS ENTERING THE ONE-HOUR FIRE RATED CORRIDOR
 WITH NO FIRE DAMPER. PLEASE SHOW COMPLIANCE WITH THE
 2020 FBC-BUILDING CODE SECTION 717.5.2.
  
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-09 Cont ID  
Sent By jwitmer Date 2022-02-09 Time 09:56 Rev Time 0.00
Received By jwitmer Date 2022-02-09 Time 08:37 Sent To  
Notes
2022-02-09 09:56:36WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21111137
 ADD: 1551 FORUM PLACE PL. # 100A
 CONT: HALLMARK CONSTRUCTION LLC
 TEL: 561-586-7664
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 09/2022
 ACTION: DENIED
  
 1) SHEET A1 FLOOR PLAN VS ROOM FINISH SCHEDULE. FINISH
 SCHEDULE, ROOMS 117 STAFF RESTROOM, 121 MENS RESTROOM &
 122 WOMENS RESTROOM ALL SHOW ALL WALLS TO HAVE A PAINT
 FINISH.
 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 1A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 1B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 1C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 2) SHEET A-2 THE REFLECTIVE CEILING PLAN SHOWS EXIT
 SIGNS AND DIRECTIONAL EXIT SIGNS, WHAT APPEARS MISSING
 IN THE END OF HALL 116 A DIRECTIONAL EXIT LIGHT TOWARDS
 THE COMMON HALL AND A DIRECTIONAL EXIT LIGHT IN THE
 COMMON CORRIDOR AND EXIT LIGHT AT THE EXIT. 2020
 FBC-BUILDING CODE 1013.1.
  
 3) SHEET A3 RESTROOM ELEVATIONS THE REAR ELEVATION OF
 THE WATER CLOSET MISSING THE ONE-FOOT MEASUREMENT FROM
 THE CENTERLINE OF THE WATER CLOSET. 2020
 FBC-ACCESSIBILITY CODE SECTION 604.5.1 THE SIDE WALL
 GRAB BAR SHALL BE 42 INCHES (1065 MM) LONG MINIMUM,
 LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES (1370 MM) MINIMUM FROM THE REAR
 WALL.
  
 4A) SHEET A4 ELEVATIONS. DETAIL 2, 3, 5, 6 & 7 ALL SHOW
 THE BASE CABINETS AND TOP OF COUNTER TOP AT 36 INCHES.
 2020 FBC-ACCESSIBILITY CODE 902.1. WORK SURFACES SHALL
 COMPLY WITH 902.3. ADVISORY 902.1 GENERAL. SAMPLES OF
 WORK SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORKSTATIONS. 902.3 HEIGHT. THE
 TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4B) SHEET A4 ELEVATIONS. DETAILS 5,6 & 7 ALL SHOW SINKS
 /COUNTER TOPS AT A ELEVATION OF 36 INCHES ABOVE THE
 FINISH FLOOR. 2020 FBC-ACCESSIBILITY CODE SECTION 606.3
 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED WITH
 THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE
 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) SHEET A1 SHOWS AT THE REAR OF THE TENANT SPACE THERE
 IS A ONE-HOUR FIRE RATED SHARED CORRIDOR. SHEET M-1
 SHOWS AIR CONDITIONING DUCTS AND RETURN DUCTS ENTERING
 THE ONE-HOUR FIRE RATED CORRIDOR WITH NO FIRE DAMPER.
 PLEASE SHOW COMPLIANCE WITH THE 2020 FBC-BUILDING CODE
 SECTION 717.5.2.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-03-04 Cont ID  
Sent By mpeterso Date 2022-03-04 Time 09:40 Rev Time 0.00
Received By mpeterso Date 2022-03-04 Time 09:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-02-22 Cont ID  
Sent By mpeterso Date 2022-02-22 Time 13:29 Rev Time 0.00
Received By mpeterso Date 2022-02-22 Time 13:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-02 Cont ID  
Sent By mpeterso Date 2022-02-02 Time 09:15 Rev Time 0.00
Received By mpeterso Date 2022-02-02 Time 08:17 Sent To  
Notes
2022-02-02 09:17:34ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL SIZE OF SERVICE ENTRANCE CONDUCTORS IN
 GUTTER FEEDING PANELS? A,B,C?. NEC 215.5 DIAGRAMS OF
 FEEDERS
 2) NO ELECTRICAL LOADS ARE DETAILED FOR PANELS ?B AND
 C?. PLEASE DETAIL OCCUPANCY TYPE AND EXPECTED LOADS FOR
 THESE PANELS. NEC 215.5 DIAGRAMS OF FEEDERS
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-02-28 Cont ID  
Sent By cwalker Date 2022-02-28 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-11 Cont ID  
Sent By cwalker Date 2022-02-11 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-01-18 Cont ID  
Sent By cwalker Date 2022-01-18 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-07 Cont ID  
Sent By medwards Date 2022-03-07 Time 10:54 Rev Time 0.00
Received By medwards Date 2022-02-27 Time 08:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-22 Cont ID  
Sent By mpeterso Date 2022-02-22 Time 13:30 Rev Time 0.00
Received By mpeterso Date 2022-02-10 Time 13:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-02-09 Time   Rev Time 0.00
Received By cdecoeur Date 2022-01-14 Time 07:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-03-07 Cont ID  
Sent By medwards Date 2022-03-07 Time 10:53 Rev Time 0.00
Received By medwards Date 2022-03-07 Time 10:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-02-22 Cont ID  
Sent By medwards Date 2022-02-22 Time 10:09 Rev Time 0.00
Received By medwards Date 2022-02-22 Time 09:56 Sent To  
Notes
2022-02-22 10:09:552ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21111137
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET LS-1 INDICATES THE COMMON HALL HAS 1 HOUR
 RATED WALLS AND 2 WALLS AT THE MEN?S AND WOMEN?S ADA
 TOILETS ALSO HAVE A 1 HOUR RATING. SHEET M-1 INDICATES
 A SUPPLY DUCT AND 2 RETURN DUCTS ARE BEING SUPPLIED
 FROM RTU-6. PLEASE SHOW HOW THIS WILL MEET FBC M
 601.3-3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-27 Cont ID  
Sent By medwards Date 2022-01-27 Time 08:48 Rev Time 0.00
Received By medwards Date 2022-01-27 Time 08:48 Sent To  
Notes
2022-01-27 08:48:591ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21111137
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COMMON HALL IS A 1-HOUR RATED EXIT ENCLOSURE,
 PLEASE SHOW THAT THE MECHANICAL SYSTEM FOR THIS COMMON
 HALL WILL MEET THE REQUIREMENTS OF FBC M 601.3-3
  
 2) THE EF-1 EXHAUST DUCT IS PENETRATING A RATED WALL AT
 THE WOMEN?S ADA TOILET. PLEASE SHOW HOW THE PENETRATION
 IN THE RATED WALL SHALL BE PROTECTED. FBC M 607
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 EACH USE OF SPACE. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-02-14 Cont ID  
Sent By lcrespo Date 2022-02-14 Time 15:27 Rev Time 0.00
Received By lcrespo Date 2022-02-14 Time 15:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-27 Cont ID  
Sent By lcrespo Date 2022-01-27 Time 15:59 Rev Time 0.00
Received By lcrespo Date 2022-01-27 Time 15:09 Sent To  
Notes
2022-01-27 16:03:3901/27/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A0.02 AND A1.11, A1.12, A1.14, AND A4.21;
  
 A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 URINAL PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR FLOOR
 SPACE.
  
 B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 DRINKING FOUNTAIN PER THE 2020 FBC ACC SEC. 606.2. 2
 CLEAR FLOOR SPACE.
  
 C. WOULD YOU PLEASE LABEL THE WOMEN?S AND MEN?S
 RESTROOMS PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. ON SHEET A0.04;
  
 A. THE TOILET GRAB BAR SAYS 6 INCHES FROM THE WALL,
 WHICH IS NOT AN ACTUAL NUMBER AS THE TOILET IS 16
 INCHES TO 18 INCHES TO THE CENTER, AND THAT NUMBER MAY
 CONFUSE THE INSTALLER. WOULD YOU PLEASE CORRECT PER THE
 2020 FBC ACC SEC. 604.2 LOCATION AND WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 B. WOULD YOU PLEASE PROVIDE DETAIL FOR THE PARTITIONS
 PRIVACY SHALL EXTEND NOT LESS THAN 60 INCHES ABOVE THE
 FINISHED FLOOR SURFACE PER THE 2020 FBC SEC. P 405.3.5
 URINAL PARTITIONS.
  
 C. WOULD YOU PLEASE PROVIDE DETAIL FOR THE HIGH AND LOW
 DRINKING FOUNTAINS THAT SHALL BE ACCESSIBLE IN
 ACCORDANCE WITH 2020 FBC ACC SEC. 211.2 & 602.1- 602.6.
 PROVIDE DRAWINGS AND DETAILS SHOWING; THE 30 X 48 IN.
 CLEAR FLOOR SPACE FOR A FORWARD APPROACH TO THE
 WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN 2020 FBC ACC
 SEC. 602.2 CLEAR FLOOR SPACE AND PLEASE SHOW KNEE AND
 TOE CLEARANCES, SPOUT HEIGHTS, SPOUT LOCATIONS PER THE
 2020 FBC ACC SEC. 306, 307, & 602.2, COMPLIANCE WITH
 2020 FBC ACC SEC. 307.2 PROTRUSION LIMITS.
  
 3. ON SHEET P0.1;
  
 A. THE DRINKING FOUNTAIN AND THE MOP SINK ARE NOT SHOWN
 ISOMETRICS. WOULD YOU PLEASE CORRECT AND IF THEY ARE
 PREEXISTING WOULD NOT THAT PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-03-07 Cont ID  
Sent By medwards Date 2022-03-07 Time 10:53 Rev Time 0.00
Received By medwards Date 2022-03-07 Time 10:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-22 Cont ID  
Sent By mpeterso Date 2022-02-22 Time 13:30 Rev Time 0.00
Received By mpeterso Date 2022-02-22 Time 13:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-09 Cont ID  
Sent By jwitmer Date 2022-02-09 Time 09:58 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***