Plan Review Details - Permit 21111124
Plan Review Stops For Permit 21111124
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-03-02 Cont ID  
Sent By jgomez Date 2022-03-02 Time 15:23 Rev Time 0.00
Received By jgomez Date 2022-03-02 Time 15:06 Sent To  
Notes
2022-03-02 15:26:24NOTE:
 SOLATUBE PRODUCT APPROVAL FL11480.1 (+/- 70 PSF)
 SUBMITTED IS APPROVED FOR ROOF ZONE #1 ONLY. IF
 SOLATUBE IS LOCATED LESS THAN 4'-0" FROM THE ROOF
 RIDGE, THEN A DIFFERENT PRODUCT APPROVAL IS REQUIRED TO
 BE SUBMITTED FOR REVIEW. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-02-22 Cont ID  
Sent By jgomez Date 2022-02-22 Time 15:23 Rev Time 0.00
Received By jgomez Date 2022-02-22 Time 15:18 Sent To  
Notes
2022-02-22 15:32:13THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21111124
  
  
 ORIGINAL COMMENT:
 1- BASED ON AERIAL VIEW (SITE MAP) SUBMITTED AND FIGURE
 R301.2(7) FBC-RESIDENTIAL IT LOOKS THE SKYLIGHTS ARE
 GOING TO BE INSTALLED ON ROOF ZONE 2R. THE DESIGN
 PRESSURES ON SOLATUBE FLORIDA PRODUCT APPROVAL
 SUBMITTED ARE +/-70.0PSF. BASED ON CITY RECORDS THE
 ROOF PITCH IS 6:12 AND THE MEAN ROOF HEIGHT IS
 APPROXIMATELY 18'. THE DESIGN PRESSURES OF PRODUCT
 APPROVAL DON'T MEET THE DESIGN PRESSURES FOR ROOF ZONE
 2R AS SHOWN ON TABLE R301.2(2) FBC-RESIDENTIAL. PROVIDE
 PRODUCT APPROVAL FOR SOLATUBE SKYLIGHT THAT MEETS THE
 DESIGN PRESSURES FOR ROOF ZONE 2R OR PROVIDE SITE
 SPECIFIC CALCULATIONS (SIGNED AND SEALED) SHOWING THAT
 THE SUBMITTED PRODUCT APPROVAL IS ADEQUATE FOR THIS
 ROOF ZONE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
  
 RESPONSE:
 THERE ARE NO DIMENSIONS SHOWING THE EXACT LOCATION OF
 THE PROPOSED SKYLIGHTS. BASED ON REVISED AERIAL VIEW
 (SITE MAP) SUBMITTED IT LOOKS THE SKYLIGHTS ARE GOING
 TO BE INSTALLED ON ROOF ZONE 2R.
 NEED TO PROVIDE PRODUCT APPROVAL WITH DESIGN PRESSURES
 OF -74.3 P.S.F OR HIGHER OR PROVIDE SITE SPECIFIC
 CALCULATIONS (SIGNED AND SEALED) SHOWING THAT THE
 SUBMITTED PRODUCT APPROVAL IS ADEQUATE FOR THIS ROOF
 ZONE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-02-17 Cont ID  
Sent By jgomez Date 2022-02-17 Time 15:04 Rev Time 0.00
Received By jgomez Date 2022-02-17 Time 14:55 Sent To  
Notes
2022-02-17 15:17:30SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21111124
  
  
 ORIGINAL COMMENT:
 1- BASED ON AERIAL VIEW (SITE MAP) SUBMITTED AND FIGURE
 R301.2(7) FBC-RESIDENTIAL IT LOOKS THE SKYLIGHTS ARE
 GOING TO BE INSTALLED ON ROOF ZONE 2R. THE DESIGN
 PRESSURES ON SOLATUBE FLORIDA PRODUCT APPROVAL
 SUBMITTED ARE +/-70.0PSF. BASED ON CITY RECORDS THE
 ROOF PITCH IS 6:12 AND THE MEAN ROOF HEIGHT IS
 APPROXIMATELY 18'. THE DESIGN PRESSURES OF PRODUCT
 APPROVAL DON'T MEET THE DESIGN PRESSURES FOR ROOF ZONE
 2R AS SHOWN ON TABLE R301.2(2) FBC-RESIDENTIAL. PROVIDE
 PRODUCT APPROVAL FOR SOLATUBE SKYLIGHT THAT MEETS THE
 DESIGN PRESSURES FOR ROOF ZONE 2R OR PROVIDE SITE
 SPECIFIC CALCULATIONS (SIGNED AND SEALED) SHOWING THAT
 THE SUBMITTED PRODUCT APPROVAL IS ADEQUATE FOR THIS
 ROOF ZONE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
  
 RESPONSE:
 ONLY THE AERIAL VIEW (SITE MAP) DRAWINGS WAS
 RESUBMITTED. THIS DOESN'T ADDRESS THE COMMENT. NEED TO
 PROVIDE PRODUCT APPROVAL WITH DESIGN PRESSURES OF -74.3
 P.S.F OR HIGHER OR PROVIDE SITE SPECIFIC CALCULATIONS
 (SIGNED AND SEALED) SHOWING THAT THE SUBMITTED PRODUCT
 APPROVAL IS ADEQUATE FOR THIS ROOF ZONE. SEC. 107.2.1.2
 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-19 Cont ID  
Sent By jgomez Date 2022-01-19 Time 14:35 Rev Time 0.00
Received By jgomez Date 2022-01-19 Time 14:06 Sent To  
Notes
2022-01-19 14:42:21RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21111124
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- BASED ON AERIAL VIEW (SITE MAP) SUBMITTED AND FIGURE
 R301.2(7) FBC-RESIDENTIAL IT LOOKS THE SKYLIGHTS ARE
 GOING TO BE INSTALLED ON ROOF ZONE 2R. THE DESIGN
 PRESSURES ON SOLATUBE FLORIDA PRODUCT APPROVAL
 SUBMITTED ARE +/-70.0PSF. BASED ON CITY RECORDS THE
 ROOF PITCH IS 6:12 AND THE MEAN ROOF HEIGHT IS
 APPROXIMATELY 18'. THE DESIGN PRESSURES OF PRODUCT
 APPROVAL DON'T MEET THE DESIGN PRESSURES FOR ROOF ZONE
 2R AS SHOWN ON TABLE R301.2(2) FBC-RESIDENTIAL. PROVIDE
 PRODUCT APPROVAL FOR SOLATUBE SKYLIGHT THAT MEETS THE
 DESIGN PRESSURES FOR ROOF ZONE 2R OR PROVIDE SITE
 SPECIFIC CALCULATIONS (SIGNED AND SEALED) SHOWING THAT
 THE SUBMITTED PRODUCT APPROVAL IS ADEQUATE FOR THIS
 ROOF ZONE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-03-02 Cont ID  
Sent By jgomez Date 2022-03-02 Time 15:48 Rev Time 0.00
Received By jgomez Date 2022-02-27 Time 08:44 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-22 Cont ID  
Sent By jgomez Date 2022-02-22 Time 15:40 Rev Time 0.00
Received By jgomez Date 2022-02-22 Time 15:18 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-17 Cont ID  
Sent By jgomez Date 2022-02-17 Time 15:18 Rev Time 0.00
Received By jgomez Date 2022-02-07 Time 17:03 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-19 Cont ID  
Sent By jgomez Date 2022-01-19 Time 15:12 Rev Time 0.00
Received By jgomez Date 2021-11-29 Time 08:32 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-11 Cont ID  
Sent By ajones Date 2022-02-11 Time 09:44 Rev Time 0.00
Received By ajones Date 2022-02-11 Time 09:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-01-03 Cont ID  
Sent By awooten Date 2022-01-03 Time 11:45 Rev Time 0.00
Received By ajones Date 2022-01-03 Time 11:45 Sent To  
Notes
***NONE***