Plan Review Details - Permit 21111118
Plan Review Stops For Permit 21111118
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-01-26 Cont ID  
Sent By jwitmer Date 2022-01-26 Time 13:26 Rev Time 0.00
Received By jwitmer Date 2022-01-26 Time 13:13 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-01-04 Cont ID  
Sent By jwitmer Date 2022-01-04 Time 15:28 Rev Time 0.00
Received By jwitmer Date 2022-01-04 Time 15:05 Sent To  
Notes
2022-01-04 15:28:36COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-01-26 Cont ID  
Sent By jwitmer Date 2022-01-26 Time 13:26 Rev Time 0.00
Received By jwitmer Date 2022-01-26 Time 13:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-04 Cont ID  
Sent By jwitmer Date 2022-01-04 Time 16:11 Rev Time 0.00
Received By jwitmer Date 2022-01-04 Time 15:05 Sent To  
Notes
2022-01-04 16:11:14WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21111118
 ADD: 525 OKEECHOBEE BLVD. # 1650
 CONT: HOLT LEE CONSTRUCTION, INC.
 TEL: 954-725-4881
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 04TH/ 2022
 ACTION: DENIED
  
 1) SHEET A1.1 THE FLOOR PLAN SHOWS THE ROOM 1662 AS A
 PRIVATE RESTROOM. THE ONLY REQUIREMENT FOR A PRIVATE
 RESTROOM IS FUTURE BACKING FOR GRAB BARS AT THE WATER
 CLOSET. BACKING IS REQUIRED SO FUTURE TENANTS DO NOT
 NEED TO TEAR INTO THE WALLS TO INSTALL BACKING FOR AN
 ACCESSIBLE TOILET. THE REQUIRED STRENGTH FOR BACKING
 NEEDS TO SHOW COMPLIANCE WITH 609.8 OF THE 2020
 FBC-ACCESSIBILITY CODE.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-13 Cont ID  
Sent By jleahy Date 2022-01-13 Time 11:31 Rev Time 0.00
Received By jleahy Date 2022-01-13 Time 11:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-01-24 Cont ID  
Sent By pleduc Date 2022-01-24 Time   Rev Time 0.00
Received By pleduc Date 2022-01-24 Time 10:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-02 Cont ID  
Sent By pleduc Date 2021-12-02 Time   Rev Time 0.00
Received By pleduc Date 2021-11-30 Time 13:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-10 Cont ID  
Sent By medwards Date 2022-02-10 Time 14:09 Rev Time 0.00
Received By medwards Date 2022-01-21 Time 07:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-13 Cont ID  
Sent By jleahy Date 2022-01-13 Time 11:38 Rev Time 0.00
Received By jleahy Date 2021-11-29 Time 08:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-02-10 Cont ID  
Sent By medwards Date 2022-02-10 Time 14:06 Rev Time 0.00
Received By medwards Date 2022-02-10 Time 14:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-20 Cont ID  
Sent By medwards Date 2021-12-20 Time 10:34 Rev Time 0.00
Received By medwards Date 2021-12-20 Time 10:28 Sent To  
Notes
2021-12-20 10:30:35PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 EACH USE OF SPACE IN THIS TENANT SPACE. FBC M 403.3.1.1
 AND TABLE 403.3.1.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-01-30 Cont ID  
Sent By abelisle Date 2022-01-30 Time 15:18 Rev Time 0.00
Received By abelisle Date 2022-01-30 Time 14:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-04 Cont ID  
Sent By ccole Date 2022-01-04 Time 10:04 Rev Time 0.00
Received By ccole Date 2021-12-30 Time 15:41 Sent To  
Notes
2022-01-04 10:05:361ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21111118
 12/30/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A0.0, A0.2 & A1.1: PROVIDE AN ENLARGED
 DRAWING OF PRIVATE RESTROOM 1662 WITH ALL APPLICABLE
 ACCESSIBILITY DETAILS IN ACCORDANCE WITH THE FLORIDA
 ACCESSIBILITY CODE- 2020. PLEASE NOTE SHEET A0.2
 REFERENCES ADA HOWEVER THE PROPOSED PROJECT IS IN
 DESIGNED IN ACCORDANCE WITH THE FBC ACC. PLEASE PROVIDE
 THE FOLLOWING DETAILS. PLEASE NOTE THAT SOME
 COMPLIANCES LISTED MAY NOT BE REQUIRED FOR A PRIVATE
 OFFICE BATHROOM. PLEASE REVIEW THE CODE SECTIONS AND
 SHOW COMPLIANCE WHERE REQUIRED.
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- 606.2.
 C) TURNING SPACE DIAMETER- 304.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 604.2.
 E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- 604.4.
 F) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- 606.3.
 G) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACE- 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROL- 604.6.
 J) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SEC. AND FIGURE
 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- 606.2.
  
 2) A1.1 & A3.1: SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS FOR THE BREAKROOM SINK AND APPLIANCES- SECS.
 606.2 & 804.6.1 FBC P. PLEASE NOTE THAT THERE ARE TWO
 PLAN SHEETS LABELED A3.1- PLEASE CORRECT- SEC. 107.2.1
 WPB.
  
 3) A3.1: SHOW THE LOCATION OF THE COFFEE MAKER IN
 DETAIL K10, AND INDICATE THE CONTROL IS IN COMPLIANCE
 WITH SEC. 308 & 309 FBC ACC - REACH RANGE AND OPERABLE
 PARTS.
  
 4) A3.1: SHOW THE COMBINATION REFRIGERATOR/FREEZER HAS
 AT LEAST 50 PERCENT OF THE FREEZER SPACE 54 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THE CLEAR
 FLOOR OR GROUND SPACE SHALL BE POSITIONED FOR A
 PARALLEL APPROACH TO THE SPACE DEDICATED TO A
 REFRIGERATOR/FREEZER WITH THE CENTERLINE OF THE CLEAR
 FLOOR OR GROUND SPACE OFFSET 24 INCHES MAXIMUM FROM THE
 CENTERLINE OF THE DEDICATED SPACE.
  
 5) P1 & P2: HOT WATER NOT TEMPERED WATER IS REQUIRED AT
 THE BREAKROOM SINK- SEC. 607.1 FBC P.
  
 6) P2: DEDICATED SHUTOFF VALVE ARE REQUIRED FOR THE
 COLD WATER LINES TO THE WATER HEATERS. THE VALVES SHALL
 NOT INTERFERE OR CAUSE A DISRUPTION OF THE COLD WATER
 SUPPLY TO THE REMAINDER OF THE COLD WATER SYSTEM- SEC.
 503.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-10 Cont ID  
Sent By medwards Date 2022-02-10 Time 14:09 Rev Time 0.00
Received By medwards Date 2022-02-10 Time 14:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-13 Cont ID  
Sent By jleahy Date 2022-01-13 Time 11:37 Rev Time 0.00
Received By jleahy Date 2022-01-13 Time 11:17 Sent To  
Notes
***NONE***