Plan Review Details - Permit 21111063
Plan Review Stops For Permit 21111063
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-01-10 Cont ID  
Sent By cpuell Date 2022-01-10 Time 16:30 Rev Time 0.00
Received By cpuell Date 2022-01-10 Time 16:30 Sent To  
Notes
2022-01-10 16:30:55WORK ON REAR BUILDING WITH THE ADDRESS OF 505 29TH ST

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-01-26 Cont ID  
Sent By jgomez Date 2022-01-26 Time 14:06 Rev Time 0.00
Received By jgomez Date 2022-01-26 Time 10:14 Sent To  
Notes
2022-01-26 14:07:25PROVISO:
 (SECTION 702.4 FBC-EXISTING BUILDING)
 1- SECOND FLOOR WINDOW FALL PROTECTION: WINDOW OPENING
 CONTROL DEVICE COMPLYING WITH ASTM F2090 SHALL BE
 REQUIRED IF WINDOW SILL IS LESS THAN 24" ABOVE FINISHED
 FLOOR.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-13 Cont ID  
Sent By jgomez Date 2022-01-13 Time 17:14 Rev Time 0.00
Received By jgomez Date 2022-01-13 Time 17:13 Sent To  
Notes
2022-01-13 17:15:04RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21111063
  
 NOTE:
 THERE ARE TWO SEPARATE BUILDINGS IN THIS PARCEL. TWO
 SEPARATE PERMIT APPLICATIONS WERE GENERATED TO AVOID
 CONFLICTS/CONFUSIONS AND ALLOW PROPER INSPECTIONS. THIS
 PERMIT #21111063 IS FOR THE APT/GARAGE. AND PERMIT
 #21110619 IS FOR THE MAIN HOUSE. PLEASE SUBMIT ONLY THE
 INFORMATION PERTINENT TO THE APT/GARAGE .
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- PROVIDE FLOOR PLAN OR SKETCH CLEARLY IDENTIFYING THE
 ROOMS WHERE WINDOWS/DOORS ARE GOING TO BE REPLACED. FOR
 EXAMPLE: BEDROOM, LIVING AREA, ETC. THIS IS REQUIRED TO
 IDENTIFY THE BEDROOMS AND VERIFY COMPLIANCE WITH THE
 EGRESS REQUIREMENTS.
 NOTE: CLEARLY SPECIFY SIZE AND TYPE OF EXISTING WINDOW
 AND SIZE AND TYPE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
 COORDINATE WINDOWS/DOORS SHOWN ON THE FLOOR PLAN WITH
 WINDOWS/DOORS SHOWN ON THE ENGINEER WINDOW/DOOR
 SCHEDULE SUBMITTED TO AVOID CONFLICTS/DELAYS.
  
 ****TO FACILITATE THE FLOOR PLANS REQUIREMENT,
 CONTRACTOR MAY COPY PLANS SUBMITTED FOR THE MAIN HOUSE
 AND GARAGE/APT BUILDING FOR REFERENCE. CLEARLY
 KEY/IDENTIFY EACH WINDOW AND DOOR WITH WINDOW/DOOR
 SCHEDULE SUBMITTED.
  
 2- SECOND FLOOR WINDOW OPENING CONTROL DEVICES: WINDOW
 OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE
 REQUIRED WHEN THE TOP SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 24 INCHES (610 MM) ABOVE THE
 FINISHED FLOOR. CLEARLY SPECIFY IF THERE ARE ANY
 WINDOWS WHERE THE WINDOW SILL IS LESS THAN 24" ABOVE
 THE FINISH FLOOR. SEE SEC. 702.4 FBC-EXISTING BUILDING
 CODE
  
 3- ENGINEER WINDOW/DOOR SCHEDULE SUBMITTED IS
 INCOMPLETE:
 CLEARLY SPECIFY TYPE OF WINDOW AND WINDOW DIMENSIONS
 (WIDTH X HEIGHT) NOT JUST THE OPENING ROUGH AREA. SEC.
 107.2.1 CITY AMENDMENTS. COORDINATE WITH ITEM #1 ABOVE.
  
 4- PROVIDE COMPLETE FLORIDA PRODUCT APPROVALS. PRODUCT
 APPROVAL SUBMITTED IS MISSING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE. THIS PAGE IS REQUIRED BECAUSE IT
 SHOWS THE CURRENT CODE VERSION AND THE PRODUCT APPROVAL
 STATUS. CHAPTER 553 F.S. AND FAC 61G20-3.001.
 NOTE: SUBMIT COMPLETE FLORIDA PRODUCT APPROVAL (COVER
 PAGE AND INSTALLATION DRAWINGS) IN ONE PDF FOR EACH
 WINDOW/DOOR TYPE. DON?T SPLIT INTO TWO OR MORE SEPARATE
 FILES.
  
 ALSO, IT LOOKS LIKE SOME PRODUCT APPROVALS WERE
 SUBMITTED TWICE. PLEASE DELETE ANY REPEATED PRODUCT
 APPROVAL TO AVOID CONFLICTS/DELAYS.
  
 5- IF WINDOW REPLACEMENT INCLUDES WINDOW MULLIONS, THEN
 PROVIDE PRODUCT APPROVAL FOR SUCH WINDOW MULLIONS.
 (NOTE: NEED TO SPECIFY MULLION SIZE TO AVOID
 DELAYS/CONFLICTS).
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-01-27 Cont ID  
Sent By fmittner Date 2022-01-27 Time 10:55 Rev Time 0.00
Received By fmittner Date 2022-01-27 Time 10:55 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-01-14 Cont ID  
Sent By fmittner Date 2022-01-14 Time 15:24 Rev Time 0.00
Received By fmittner Date 2022-01-14 Time 15:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-27 Cont ID  
Sent By jgomez Date 2022-01-27 Time 12:51 Rev Time 0.00
Received By jgomez Date 2022-01-25 Time 14:55 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-18 Cont ID  
Sent By lmarchan Date 2022-01-18 Time 12:18 Rev Time 0.00
Received By lmarchan Date 2022-01-12 Time 08:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-01-26 Cont ID  
Sent By jgomez Date 2022-01-26 Time 14:11 Rev Time 0.00
Received By jgomez Date 2022-01-26 Time 13:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-13 Cont ID  
Sent By jgomez Date 2022-01-13 Time 17:24 Rev Time 0.00
Received By jgomez Date 2022-01-13 Time 17:24 Sent To  
Notes
2022-01-13 17:45:41ENGINEER'S WINDOW/DOOR SCHEDULE WITH VALID DIGITAL
 SIGNATURE. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2022-01-27 Cont ID  
Sent By fmittner Date 2022-01-27 Time 10:55 Rev Time 0.00
Received By fmittner Date 2022-01-27 Time 10:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-14 Cont ID  
Sent By fmittner Date 2022-01-14 Time 15:24 Rev Time 0.00
Received By fmittner Date 2022-01-14 Time 15:24 Sent To  
Notes
2022-01-14 15:25:41PLEASE REVISE PLANS TO ONLY REFERENCE SINGLE FAMILY
 HOME WITH DETACHED APARTMENT/ACCESSORY....ONLY 2 UNITS
 TOTAL PERMITTED ON SITE. CHARITY EVENT VIA SPECIAL
 EVENTS PERMIT.