| 2021-11-29 17:30:37 | RESIDENTIAL (R3) REVISION BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | REVISION #: 21111061 |
| | |
| | NOTE: |
| | LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING. |
| | SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| | |
| | 1- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | CONSTRUCTION OF THE NEW BALCONY GUARDRAIL SHOWING |
| | COMPLIANCE WITH TABLE R301.5, SEC. R312.1 |
| | FBC-RESIDENTIAL. |
| | NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN SPECIFY THE |
| | DESIGN GUIDELINES REQUIRED BY TABLE R301.5 AND SEC. |
| | R312.1 AND CLEARLY SPECIFY ON PLANS THAT SHOP DRAWINGS |
| | NEED TO BE SUBMITTED FOR REVIEW PRIOR TO CONSTRUCTION. |
| | ALL SHOP DRAWINGS TO BE REVIEWED BY THE DESIGN |
| | PROFESSIONAL OF RECORD PRIOR TO SUBMITTAL TO THIS |
| | OFFICE. |
| | |
| | 2- VALUATION DECLARED IN THE REVISION FORM FOR THE |
| | ADDITIONAL WORK IS TOO LOW. $2,300 IS TOO LOW FOR ALL |
| | NEW SCOPE OF WORK: REBUILT BALCONY FLOOR AND GUARDRAIL, |
| | NEW EXTERIOR CONCRETE STAIRWAY, NEW PLUMBING LAYOUT OF |
| | CABANA BATHROOM AND FOR DESIGN PROFESSIONAL FEES. |
| | REVISE VALUE TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |