Plan Review Details - Permit 21111052
Plan Review Stops For Permit 21111052
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-03-07 Cont ID  
Sent By rmcphers Date 2022-03-07 Time 10:14 Rev Time 0.00
Received By rmcphers Date 2022-03-07 Time 10:14 Sent To  
Notes
2022-03-07 10:15:00PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-01-10 Cont ID  
Sent By rmcphers Date 2022-01-10 Time 12:37 Rev Time 0.00
Received By rmcphers Date 2022-01-10 Time 11:27 Sent To  
Notes
2022-01-10 12:38:00PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-01-10 Cont ID  
Sent By rmcphers Date 2022-01-10 Time 12:38 Rev Time 0.00
Received By rmcphers Date 2022-01-10 Time 12:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2022-03-04 Cont ID  
Sent By jleahy Date 2022-03-04 Time 11:54 Rev Time 0.00
Received By jleahy Date 2022-03-04 Time 11:20 Sent To  
Notes
2022-03-04 11:55:21NO ELECTRICAL WORK SHOWN JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-01-06 Cont ID  
Sent By jleahy Date 2022-01-06 Time 11:59 Rev Time 0.00
Received By jleahy Date 2022-01-06 Time 11:55 Sent To  
Notes
2022-01-06 13:24:25ELECTRICAL AUDIT
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL WORK SHOWN, THERE MUST BE A REQUIREMENT
 FOR EXIT LIGHTS AT THE NEW EXITS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-02-04 Cont ID  
Sent By   Date 2022-02-04 Time   Rev Time 0.00
Received By bdolan Date 2022-02-04 Time 11:42 Sent To  
Notes
2022-02-04 11:52:55THE REVIEW COMMENTS FROM THE PRIOR REVIEW HAVE NOT BEEN
 ADDRESSED. PLEASE PROVIDED DETAIL TO COMPLIANCE WITH
 CODE REQUIREMENT FOR PANIC HARDWARE TO BE INSTALLED IN
 EGRESS DOORS FROM ASSEMBLY SPACE.
  
 FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED, HOWEVER EGRESS
 DOORS FROM THE ASSEMBLY SPACE ITSELF SHALL BE EQUIPPED
 WITH PANIC HARDWARE.
  
 PLEASE INDICATE ON DOOR SCHEDULE/SPEC SHEET THE TYPE
 AND OPERATION OF PANIC HARDWARE FOR THE EGRESS DOORS TO
 BE INSTALLED.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-01-06 Cont ID  
Sent By   Date 2022-01-06 Time   Rev Time 0.00
Received By bdolan Date 2022-01-06 Time 12:57 Sent To  
Notes
2022-01-06 13:09:31FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED.
 PLEASE INDICATE ON DOOR SCHEDULE/SPEC SHEET THE TYPE
 AND OPERATION OF PANIC HARDWARE FOR THE EGRESS DOORS TO
 BE INSTALLED.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-07 Cont ID  
Sent By rmcphers Date 2022-03-07 Time 10:15 Rev Time 0.00
Received By rmcphers Date 2022-02-03 Time 16:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-27 Cont ID  
Sent By vbroglia Date 2022-01-27 Time 12:39 Rev Time 0.00
Received By vbroglia Date 2021-11-29 Time 11:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-01-10 Cont ID  
Sent By rmcphers Date 2022-01-10 Time 12:40 Rev Time 0.00
Received By rmcphers Date 2022-01-10 Time 12:40 Sent To  
Notes
2022-01-10 12:40:59ADDING EXTERIOR DOORS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-02-23 Cont ID  
Sent By medwards Date 2022-02-23 Time 14:43 Rev Time 0.00
Received By medwards Date 2022-02-23 Time 14:43 Sent To  
Notes
2022-02-23 14:44:362ND REVIEW COMMENT:
 PLEASE RESPOND TO THE ORIGINAL MECHANICAL PALN REVIEWER
 COMMENT BELOW.
  
 MECHANICAL AUDIT:
 PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL
 SYSTEM FOR THIS PROJECT. WITH THE REMOVAL OF THE ROLL
 UP DOOR HOW DOES THIS EFFECT THE VENTILATION OF THE
 AREA? IF THIS IS TO REMAIN A WAREHOUSE IT SHOULD MEET
 FBC M TABLE 403.3.1.1 FOR THE WAREHOUSE VENTILATION.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-06 Cont ID  
Sent By medwards Date 2022-01-06 Time 11:10 Rev Time 0.00
Received By medwards Date 2022-01-06 Time 11:10 Sent To  
Notes
2022-01-06 11:24:33MECHANICAL AUDIT:
 PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL
 SYSTEM FOR THIS PROJECT. WITH THE REMOVAL OF THE ROLL
 UP DOOR HOW DOES THIS EFFECT THE VENTILATION OF THE
 AREA? IF THIS IS TO REMAIN A WAREHOUSE IT SHOULD MEET
 FBC M TABLE 403.3.1.1 FOR THE WAREHOUSE VENTILATION.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-01-05 Cont ID  
Sent By abelisle Date 2022-01-05 Time 19:00 Rev Time 0.00
Received By abelisle Date 2022-01-05 Time 18:54 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-12-03 Cont ID  
Sent By shill Date 2021-12-03 Time 18:23 Rev Time 0.00
Received By shill Date 2021-12-03 Time 18:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-07 Cont ID  
Sent By rmcphers Date 2022-03-07 Time 10:14 Rev Time 0.00
Received By rmcphers Date 2022-03-07 Time 10:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-10 Cont ID  
Sent By rmcphers Date 2022-01-10 Time 12:45 Rev Time 0.00
Received By rmcphers Date 2022-01-10 Time 12:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-01-27 Cont ID  
Sent By vbroglla Date 2022-01-27 Time 12:39 Rev Time 0.00
Received By vbroglia Date 2022-01-27 Time 12:39 Sent To  
Notes
***NONE***