Plan Review Details - Permit 21111013
Plan Review Stops For Permit 21111013
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-12-08 Cont ID  
Sent By cpuell Date 2021-12-08 Time 14:45 Rev Time 0.00
Received By cpuell Date 2021-12-08 Time 14:45 Sent To  
Notes
2021-12-08 14:45:46ADDRESS APPROVED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-12-05 Cont ID  
Sent By cpuell Date 2021-12-05 Time 13:07 Rev Time 0.00
Received By cpuell Date 2021-12-05 Time 13:07 Sent To  
Notes
2021-12-05 13:07:55SUITE 800 IS NOT A RECOGNIZED SUITE NUMBER, PLEASE
 PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR.
 PLEASE EMAIL TO [email protected] FOR FURTHER QUESTIONS
 YOU CAN ALSO CALL 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2021-12-22 Cont ID  
Sent By rmcdouga Date 2021-12-22 Time 13:13 Rev Time 0.00
Received By rmcdouga Date 2021-12-22 Time 13:13 Sent To  
Notes
2021-12-22 13:14:25THIS IS AN INTERIOR BUILD OUT IN A NEW BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-01-20 Cont ID  
Sent By rmcdouga Date 2022-01-20 Time 15:02 Rev Time 0.00
Received By rmcdouga Date 2022-01-20 Time 15:02 Sent To  
Notes
2022-01-20 16:30:09THE ARCHITECT'S RESPONCE LETTER TO THERE BEING AN OPEN
 PERMIT, #21080195, IS THAT THE BUILDING OWNER/LANDLORD,
 RELATED COMPANIES, WILL RESOLVE ANY CONFLICT BETWEEN
 THE SHELL CONVERSION CONTRACTOR AND THE INTERIOR
 BUILDOUT CONTRACTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-22 Cont ID  
Sent By rmcdouga Date 2021-12-22 Time 17:21 Rev Time 0.00
Received By rmcdouga Date 2021-12-22 Time 13:14 Sent To  
Notes
2021-12-22 17:18:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE IS STILL AN OPEN PERMIT, #21080195, TO CONVERT
 1/2 OF THE LEVEL 8 PARKING GARAGE TO ENCLOSED SPACE.
 THAT PERMIT WILL NEED TO BE FINALED BEFORE THIS
 INTERIOR BUILD-OUT PERMIT CAN BE ISSUED.
  
 2) ADDRESS THE PLUMBING REVIEW COMMENTS FOR FLORIDA
 BUILDING CODE ACCESSIBILITY. FBC 1101.1
  
 3) PROVIDE A DIMENSIONED ELEVATION DRAWING OF THE
 RECEPTION DESK THAT SHOWS COMPLIANCE WITH FBC
 ACCESSIBILITY SECTION 904.4.
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-12-13 Cont ID  
Sent By mpeterso Date 2021-12-13 Time 16:03 Rev Time 0.00
Received By mpeterso Date 2021-12-13 Time 16:03 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-06-01 Cont ID  
Sent By jleahy Date 2022-06-01 Time 16:51 Rev Time 0.00
Received By jleahy Date 2022-06-01 Time 16:51 Sent To  
Notes
2022-06-01 16:53:50LOW VOLTATE PHONE/DATA TV JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-03 Cont ID  
Sent By pleduc Date 2021-12-03 Time   Rev Time 0.00
Received By pleduc Date 2021-12-02 Time 10:29 Sent To  
Notes
2021-12-02 11:00:37 
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-20 Cont ID  
Sent By rmcdouga Date 2022-01-20 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2022-01-06 Time 12:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-22 Cont ID  
Sent By rmcdouga Date 2021-12-22 Time 17:21 Rev Time 0.00
Received By rmcdouga Date 2021-12-01 Time 16:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-01-07 Cont ID  
Sent By medwards Date 2022-01-07 Time 14:44 Rev Time 0.00
Received By medwards Date 2022-01-07 Time 14:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-02 Cont ID  
Sent By medwards Date 2021-12-02 Time 10:55 Rev Time 0.00
Received By medwards Date 2021-12-02 Time 10:34 Sent To  
Notes
2021-12-02 10:56:001ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21111013
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M4.1: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON FBC M 403.3.1.1 AND TABLE
 403.3.1.1. THE NOTE UNDER THE VENTILATION CALCULATIONS
 STATES THE SEATING PLAN WAS USED FOR THE PEOPLE COUNT.
 FBC M 403.3.1.1 DOES NOT ALLOW THIS AND STATES YOU MUST
 USE TABLE 403.3.1.1 FOR THE OCCUPANT COUNTS.
  
 2) SHEET M2.3: VAV-8-11 INDICATES A TOTAL OF 1000 CFM
 OF SUPPLY AIR. SHEET M4.1 VAV BOX SCHEDULE CHART
 INDICATES THAT VAV-8-11 SUPPLIES ONLY 900 CFM OF SUPPLY
 AIR. FBC 107.2.1
  
 3) SHEET M2.3: VAV-8-15 INDICATES A TOTAL OF 775 CFM OF
 SUPPLY AIR. SHEET M4.1 VAV BOX SCHEDULE CHART INDICATES
 THAT VAV-8-15 SUPPLIES ONLY 675 CFM OF SUPPLY AIR. FBC
 107.2.1
  
 4) SHEET M2.3: VAV-8-17 INDICATES A TOTAL OF 1350 CFM
 OF SUPPLY AIR. SHEET M4.1 VAV BOX SCHEDULE CHART
 INDICATES THAT VAV-8-17 SUPPLIES ONLY 500 CFM OF SUPPLY
 AIR. FBC 107.2.1
  
 5) SHEET M2.3: THEE ARE 2 VAV-8-20. THEY BOTH SUPPLY
 DIFFERENT CFM?S PLEASE RENAME ONE OR ADD A NOTE
 CLARIFYING THE DRAWING DOES HAVE 2 VAV-8-20. FBC
 107.2.1
  
 6) SHEETS M2.3 AND M2.2: VAV-8-26 DOES NOT HAVE THE
 CFM?S AT THE GRILLES. FBC 107.2.1
  
 7) PLEASE IDENTIFY VAV-8-25 ON THE DRAWING AS IT IS NOT
 WHERE SHEET M0.1 INDICATES. FBC 107.2.1
  
 8) PLEASE PROVIDE INFORMATION ON THE EXHAUST FAN THAT
 INDICATE THE HOUSE EXHAUST FAN ON THE ROOF HAS THE
 EXTRA CFM?S FOR THIS ADDITIONAL LOAD OF 600 CFM?S. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-01-10 Cont ID  
Sent By ccole Date 2022-01-10 Time 14:21 Rev Time 0.00
Received By ccole Date 2022-01-10 Time 11:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-09 Cont ID  
Sent By ccole Date 2021-12-09 Time 11:46 Rev Time 0.00
Received By ccole Date 2021-12-09 Time 09:57 Sent To  
Notes
2021-12-09 11:48:101ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21111013
 12/9/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A3.3- FBC ACC COMPLIANCE DETAILS REQUIRED FOR
 THE NEW BATHROOMS 844, 861, 864, & 865. PLEASE PROVIDE
 ENLARGED, DIMENSIONED DRAWINGS AND ELEVATION VIEWS
 SHOWING:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 2) A3.3- FBC ACC COMPLIANCE DETAILS FOR ROOMS 806, 846,
 857:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 SINKS AND APPLIANCES- SECTION 606.2.
 B) HEIGHTS OF THE SINK RIMS OR COUNTER SURFACES FROM
 THE FINISHED FLOORS- SECTION 606.3.
 C) HEIGHTS OF COFFEE DISPENSER CONTROLS AND OTHER
 COUNTERTOP APPLIANCE CONTROLS- SECTION 308.
 D) OPERABLE PARTS COMPLIANCE FOR APPLIANCES- 804.6.2.
 D) PLACE A NOTE TO INDICATE THE REFRIGERATOR/FREEZER
 SHALL HAVE AT LEAST 50 PERCENT OF THE FREEZER SPACE 54
 INCHES MAXIMUM ABOVE THE FINISH FLOOR- 804.6.6.
  
 3) P1.1 & P1.2: VENTS MISSING FOR THE WATER CLOSETS
 WC-2 AND THE EFD IN ROOM 863- SECTION 909, 910, 911, &
 912 FBC P.
  
 4) P2.2: SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS
 AND BACKFLOW PREVENTERS FOR SUPPLY LINES TO COFFEE
 DISPENSERS, DISHWASHER, ICE MAKERS ETC. SECTIONS 604.9
 & 608.3 FBC P. LIST THE MAKES AND MODELS OF THE
 BACKFLOW DISPENSERS- TABLE 608.3 FBC P.
  
 5) P3.1: SHOW THE HEIGHT OF THE SPOUT FOR THE STANDING
 PERSON'S DRINKING FOUNTAIN- SECTION 602.7 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-01-20 Cont ID  
Sent By rmcdouga Date 2022-01-20 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2022-01-20 Time 16:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-12-22 Cont ID  
Sent By rmcdouga Date 2021-12-22 Time 13:32 Rev Time 0.00
Received By rmcdouga Date 2021-12-22 Time 13:32 Sent To  
Notes
***NONE***