| 2021-12-09 11:48:10 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21111013 |
| | 12/9/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A3.3- FBC ACC COMPLIANCE DETAILS REQUIRED FOR |
| | THE NEW BATHROOMS 844, 861, 864, & 865. PLEASE PROVIDE |
| | ENLARGED, DIMENSIONED DRAWINGS AND ELEVATION VIEWS |
| | SHOWING: |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SECTION 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| | SURFACES FROM THE FINISHED FLOORS- SECTION 606.3. |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2. |
| | |
| | 2) A3.3- FBC ACC COMPLIANCE DETAILS FOR ROOMS 806, 846, |
| | 857: |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | SINKS AND APPLIANCES- SECTION 606.2. |
| | B) HEIGHTS OF THE SINK RIMS OR COUNTER SURFACES FROM |
| | THE FINISHED FLOORS- SECTION 606.3. |
| | C) HEIGHTS OF COFFEE DISPENSER CONTROLS AND OTHER |
| | COUNTERTOP APPLIANCE CONTROLS- SECTION 308. |
| | D) OPERABLE PARTS COMPLIANCE FOR APPLIANCES- 804.6.2. |
| | D) PLACE A NOTE TO INDICATE THE REFRIGERATOR/FREEZER |
| | SHALL HAVE AT LEAST 50 PERCENT OF THE FREEZER SPACE 54 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR- 804.6.6. |
| | |
| | 3) P1.1 & P1.2: VENTS MISSING FOR THE WATER CLOSETS |
| | WC-2 AND THE EFD IN ROOM 863- SECTION 909, 910, 911, & |
| | 912 FBC P. |
| | |
| | 4) P2.2: SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS |
| | AND BACKFLOW PREVENTERS FOR SUPPLY LINES TO COFFEE |
| | DISPENSERS, DISHWASHER, ICE MAKERS ETC. SECTIONS 604.9 |
| | & 608.3 FBC P. LIST THE MAKES AND MODELS OF THE |
| | BACKFLOW DISPENSERS- TABLE 608.3 FBC P. |
| | |
| | 5) P3.1: SHOW THE HEIGHT OF THE SPOUT FOR THE STANDING |
| | PERSON'S DRINKING FOUNTAIN- SECTION 602.7 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |