Plan Review Details - Permit 21111010
Plan Review Stops For Permit 21111010
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-02-18 Cont ID  
Sent By cpuell Date 2022-02-18 Time 16:39 Rev Time 0.00
Received By cpuell Date 2022-02-18 Time 16:39 Sent To  
Notes
2022-02-18 16:39:50ADDRESS HAD PREVIOUSLY BEEN APPROVED UPON.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-11-29 Cont ID  
Sent By scwelter Date 2021-11-29 Time 15:21 Rev Time 0.00
Received By scwelter Date 2021-11-29 Time 15:22 Sent To  
Notes
2021-11-29 15:22:23TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE OVER
 $500,000 IT IS SUBJECT TO THE PUBLIC ART REQUIREMENT AS
 PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 CONTACT SYBILLE WELTER, ADMINISTRATOR OF PUBLIC ART &
 CULTURE AT [email protected] TO OBTAIN AN ART ASSESSMENT
 APPLICATION AND REVIEW THE REQUIREMENTS.
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 3 Status P Date 2022-06-27 Cont ID  
Sent By scwelter Date 2022-06-27 Time 14:12 Rev Time 0.00
Received By scwelter Date 2022-06-27 Time 14:14 Sent To  
Notes
2022-06-27 14:14:12PUBLIC ART REQUIREMENT MET. HOLDS RELEASED FOR PUBLIC
 ART. 6.27.2022

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status F Date 2022-06-08 Cont ID  
Sent By scwelter Date 2022-06-08 Time 09:09 Rev Time 0.00
Received By scwelter Date 2022-06-08 Time 09:14 Sent To  
Notes
2022-06-08 09:14:33DEVELOPMENT SUBJECT TO PUBLIC ART REQUIREMENT. CONTACT
 [email protected] TO COMPLETE AN ART ASSESSMENT
 APPLICATION THAT MUST BE COMPLETED ASAP.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status F Date 2022-01-24 Cont ID  
Sent By scwelter Date 2022-01-24 Time 09:53 Rev Time 0.00
Received By scwelter Date 2022-05-18 Time 13:55 Sent To  
Notes
2022-01-24 09:55:49MAY 18TH - CONTACT [email protected] FOR ART ASSESSMENT
 APPLICATION. DEVELOPMENT SUBJECT TO PUBLIC ART
 REQUIREMENT.
  
 PROJECT IS SUBJECT TO PUBLIC ART REQUIREMENT.
 CONTACT SYBILLE WELTER, ADMINISTRATOR OF PUBLIC ART &
 CULTURE AT [email protected] TO OBTAIN AN ART ASSESSMENT
 APPLICATION AND REVIEW THE REQUIREMENTS.
  
 BY ORDINANCE:
 TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE OVER
 $500,000 IT IS SUBJECT TO THE PUBLIC ART REQUIREMENT AS
 PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-06-22 Cont ID  
Sent By rmcphers Date 2022-06-22 Time 10:36 Rev Time 0.00
Received By rmcphers Date 2022-06-22 Time 10:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-06-07 Cont ID  
Sent By rmcphers Date 2022-06-07 Time 10:26 Rev Time 0.00
Received By rmcphers Date 2022-06-07 Time 10:26 Sent To  
Notes
2022-06-07 10:38:04NEW BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) IN PROJECTDOX DRAWING A-3.02 HAS BEEN OVERLAID WITH
 REVISED DRAWING A-2.01
  
 2) IN PROJECTDOX DRAWING A-3.01 HAS BEEN OVERLAID WITH
 REVISED DRAWING A-2.00
  
 3) PLEASE CORRECT THE NAMING IN PROJECTDOX SO THAT THE
 DRAWINGS OVERLAY WITH THE PROPER REVISED DRAWINGS AND
 RESTORE THE VERSION "1" A-3.02 AND A - 3.01

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-07 Cont ID  
Sent By rmcphers Date 2022-03-07 Time 08:46 Rev Time 0.00
Received By rmcphers Date 2022-03-07 Time 08:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-29 Cont ID  
Sent By rmcphers Date 2021-12-29 Time 14:00 Rev Time 0.00
Received By rmcphers Date 2021-12-29 Time 09:51 Sent To  
Notes
2021-12-29 13:29:32NEW 2 STORY OFFICE BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A-0.30 - THE TABLE SHOWN ON THE DRAWING -
 UNDER "EGRESS AND TRAVEL" LAST COLUMN SHOWS "NO
 SPRINKLER AND 1 STORY" - PLEASE CLARIFY.
  
 2) PLEASE SHOW WALL FINISH ON THE FINISH SCHEDULE FOR
 THE RESTROOM AND MOP SINK AREA TO COMPLY WITH FBC
 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 3) PLEASE SHOW THE OCCUPANT LOAD FOR THE TRAINING ROOM
 - FBC 1004.4
  
 4) PLEASE SHOW THE DIAGONAL DISTANCE OF THE TRAINING
 ROOM AND THE DISTANCE BETWEEN THE 2 DOORS IN THE
 TRAINING ROOM - FBC 1007.1.1
  
 5) PLEASE SHOW THE USE FOR THE 2 FLOOR SPACE FBC
 CHAPTER 3
  
 6) PLEASE SHOW STAIR NUMBER 1 TO EXIT TO THE OUTSIDE OF
 THE BUILDING OR SHOW THE EGRESS TRAVEL DISTANCE FROM
 THE ROOF TOP TO THE EXIT DISCHARGE FBC TABLE 1017.2 - -
 - FBC 1023.1 GENERAL.
 INTERIOR EXIT STAIRWAYS AND RAMPS SERVING AS AN EXIT
 COMPONENT IN A MEANS OF EGRESS SYSTEM SHALL COMPLY WITH
 THE REQUIREMENTS OF THIS SECTION. INTERIOR EXIT
 STAIRWAYS AND RAMPS SHALL BE ENCLOSED AND LEAD DIRECTLY
 TO THE EXTERIOR OF THE BUILDING OR SHALL BE EXTENDED TO
 THE EXTERIOR OF THE BUILDING WITH AN EXIT PASSAGEWAY
 CONFORMING TO THE REQUIREMENTS OF SECTION 1024, EXCEPT
 AS PERMITTED IN SECTION 1028.1. AN INTERIOR EXIT
 STAIRWAY OR RAMP SHALL NOT BE USED FOR ANY PURPOSE
 OTHER THAN AS A MEANS OF EGRESS AND A CIRCULATION PATH.
  
 7) PLEASE SHOW THE FRONT DOOR TO SWING OUT - FBC
 1010.1.2
  
 8) PLEASE SHOW THE ROOF TOP MECHANICAL SCREENING
 ATTACHMENT DETAILS TO COMPLY WITH THE WIND LOADS FBC
 1609
  
 9) PLEASE SHOW THE ROOF TOP FRONT RAILING HEIGHT AND
 OPENING LIMITATIONS PER FBC SECTION 1015
  
 10) PLEASE SHOW THE STAIR HANDRAIL EXTENSIONS AT THE
 TOP AND BOTTOM (TOP HORIZONTAL AND BOTTOM SLOPE) - FBC
 1014.6 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER.
  
 11) PLEASE PROVIDE A SOIL REPORT AS SHOWN ON THE
 DRAWINGS.
  
 12) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR
 DOORS, ROOFING SYSTEMS ETC. - ALL PRODUCT APPROVALS
 NEED TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING
 DESIGNER OF RECORD. FBC WPB 107.3.4
  
 13) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR
 DIMENSIONS FROM THE FINISHED FLOOR TO THE "REFLECTIVE
 SURFACE" - FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 14) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET GRAB
 BARS MAXIMUM HEIGHT TO THE "TOP OF THE GRIPPING
 SURFACE" - FBC A 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 15) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET REAR
 GRAB BAR DIMENSIONS FROM THE CENTER OF THE TOILET PER -
 FBC A 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 16) PLEASE SHOW THE ROOF TOP RESTROOM TO COMPLY WITH
 ACCESSIBILITY REQUIREMENTS - FBC A 213.1
  
 17) SEPARATE PERMITS ARE REQUIRED FOR - PARKING LOT,
 SITE LIGHTING, SIGNS, DUMPSTER, REAR WALK CANOPY,
 FENCING. EACH WITH ITS OWN APPLICATION FILLED OUT AND
 SENT TO THE PERMIT LIBRARIAN.
  
 18 ) ITEMS SUCH AS ROOFING SYSTEMS, CANOPIES, ROOF TOP
 SCREENING, WINDOW AND DOOR PRODUCT APPROVALS MAY BE
 DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON
 THE CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-03-17 Cont ID  
Sent By jleahy Date 2022-03-17 Time 12:53 Rev Time 0.00
Received By jleahy Date 2022-03-17 Time 12:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-21 Cont ID  
Sent By jleahy Date 2022-01-21 Time 09:26 Rev Time 0.00
Received By jleahy Date 2022-01-21 Time 08:50 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2022-02-23 Cont ID  
Sent By rrossano Date 2022-02-23 Time   Rev Time 0.00
Received By rrossano Date 2022-02-23 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-12-09 Cont ID  
Sent By rrossano Date 2021-12-09 Time   Rev Time  
Received By rrossano Date 2021-12-09 Time   Sent To  
Notes
2021-12-09 11:13:26PROJECT WILL REQUIRE A FORMAL ENGINEERING SUBMITTAL.
  
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-
 STANDARDS-DETAILS
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-28 Cont ID  
Sent By   Date 2022-02-28 Time   Rev Time 0.00
Received By jcclark Date 2022-02-28 Time 08:47 Sent To  
Notes
2022-02-28 08:47:51PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-06 Cont ID  
Sent By   Date 2021-12-06 Time   Rev Time 0.00
Received By jcclark Date 2021-12-06 Time 13:39 Sent To  
Notes
2021-12-06 13:50:10PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-08 Cont ID  
Sent By lmarchan Date 2022-07-08 Time 14:34 Rev Time 0.00
Received By lmarchan Date 2022-06-16 Time 08:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-09 Cont ID  
Sent By aoliver Date 2022-06-09 Time 07:43 Rev Time 0.00
Received By aoliver Date 2022-05-22 Time 15:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-18 Cont ID  
Sent By aoliver Date 2022-03-18 Time 10:22 Rev Time 0.00
Received By aoliver Date 2022-02-18 Time 07:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-24 Cont ID  
Sent By lmarchan Date 2022-01-24 Time 10:02 Rev Time 0.00
Received By lmarchan Date 2021-12-03 Time 09:02 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-10-13 Cont ID  
Sent By lmarchan Date 2022-10-13 Time 17:10 Rev Time 0.00
Received By lmarchan Date 2022-07-13 Time 08:51 Sent To  
Notes
2022-10-13 17:10:27RECEIPT MU-2022-032322 - $80,506.87 PAID
2022-07-13 08:53:297/13/22 EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-12-29 Cont ID  
Sent By rmcphers Date 2021-12-29 Time 13:29 Rev Time 0.00
Received By rmcphers Date 2021-12-29 Time 13:29 Sent To  
Notes
2021-12-29 13:30:24PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-03-08 Cont ID  
Sent By medwards Date 2022-03-08 Time 08:04 Rev Time 0.00
Received By medwards Date 2022-03-08 Time 08:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-22 Cont ID  
Sent By medwards Date 2021-12-22 Time 13:23 Rev Time 0.00
Received By medwards Date 2021-12-22 Time 13:23 Sent To  
Notes
2021-12-22 13:23:551ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21111010
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.3: OUTSIDE AIR CALCULATIONS: ROOM 101
 RECEPTION MINIMUM OUTDOOR AIR REQUIRED IS 63 CFM. THE
 COLUMN NAMED MIN. OUTDOOR AIR PROVIDED STATES ONLY 54
 CFM?S PROVIDE FOR THIS SPACE. PLEASE CORRECT TO SHOW AT
 LEAST THE MINIMUM REQUIRED. FBC M 403.3.1.1 AND FBC M
 TABLE 403.3.1.1
  
 2) THE LECTURE CLASSROOMS MUST BE CALCULATED USING FBC
 M 403.3.1.1 AND FBC M TABLE 403.3.1.1, THE OUTDOOR AIR
 SHOWN IN THE MINIMUM OUTDOOR AIR REQUIRED IS LOW FOR
 BOTH LECTURE CLASSROOMS. PLEASE SHOW THE REQUIRED
 MINIMUM CFM?S FOR THESE LECTURE CLASSROOMS.
  
 3) SHEET M0.2: VAV-1 AND VAV-2 TOTAL CFM?S ARE REVERSED
 ACCORDING TO SHEET M1.1.
  
 4) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZE AND
 TERMINATION LOCATION. FBC M 307
  
 5) SHEET M0.2: EF1.1 IS EXHAUSTING 400 CFM, SHEET M1.1
 INDICATES IT IS EXHAUSTING 450 CFM. PLEASE BE
 CONSISTENT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-03-08 Cont ID  
Sent By lcrespo Date 2022-03-08 Time 15:48 Rev Time 0.00
Received By lcrespo Date 2022-03-08 Time 15:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-06 Cont ID  
Sent By lcrespo Date 2022-01-06 Time 07:31 Rev Time 0.00
Received By lcrespo Date 2022-01-04 Time 06:18 Sent To  
Notes
2022-01-06 07:31:2401/06/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. ON SHEET A-4.00;
  
 A. ON DETAIL #6, THE URINAL PARTITION SHALL PROVIDE
 PRIVACY PARTITIONS SHALL BEGIN AT A HEIGHT NOT GREATER
 THAN 12 INCHES FROM AND EXTEND NOT LESS THAN 60 INCHES
 ABOVE THE FINISHED FLOOR SURFACE PER THE 2020 FBC SEC.
 P 405.3.5 URINAL PARTITIONS.
  
 B. FOR THE MIRRORS, PLEASE LABEL THE REFLECTIVE PART OF
 THE MIRROR THAT NEEDS TO BE 40" TO THE REFLECTIVE SIDE
 PER THE 2020 FBC ACC SEC. 603.3. SHOW IT ON DETAIL #4
 IN THE OPEN AREA AS WELL.
  
 C. ON THE REAR WALL GRAB BAR, THE REAR NEEDS TO BE
 MEASURED TO THE CENTER OF THE WATER CLOSET TO 12 INCHES
 AND 24 INCHES TO THE OPEN SIDE PER THE 604.5.2 REAR
 WALL. THE TOILET SAYS 17 INCHES FROM THE WALL, WHICH IS
 NOT AN ACTUAL NUMBER AS THE TOILET IS 16 INCHES TO 18
 INCHES TO THE CENTER, AND THAT NUMBER MAY CONFUSE THE
 INSTALLER. WOULD YOU PLEASE CORRECT PER THE 2020 FBC
 ACC SEC. 604.2 LOCATION AND WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU PLEASE SHOW THE 42 INCHES FOR GRAB BAR PER
 THE 2020 ACC 604.5.1SIDE WALL.
  
 E. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE
 DIMENSIONS FOR THE LAVATORY, WATER CLOSET, TURNING
 CIRCLE, URINAL, AND LAV PER THE 2020 FBC ACC SEC.
 606.2. 2 CLEAR FLOOR SPACE.
  
 2. ON SHEET A-4.02, WOULD YOU PLEASE SHOW THE CLEAR
 FLOOR SPACE FOR THE BREAK SINK PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 3. ON SHEET A-6.02, THERE IS A SCUPPER. WOULD YOU
 PLEASE PROVIDE DETAIL FOR THE ALLOWABLE SIZE PER THE
 2020 FBC SEC? P 1106.5 PARAPET WALL SCUPPERS.
  
 4. ON SHEET E1.3, IT SHOWS TWO SINKS, BUT ON THE P2.3,
 THERE IS ONLY ONE SINK SHOWN. WOULD YOU PLEASE CLARIFY
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 5. ON SHEET P0.1;
  
 A. WOULD YOU PLEASE PROVIDE THE MINIMUM NUMBER OF
 FIXTURES FOR THE OCCUPANT LOAD BASED ON THE ACTUAL USE
 OF THE BUILDING OR SPACE PER TABLE 403.1 MINIMUM NUMBER
 OF FIXTURES.
  
 B. IN THE ABOVE OCCUPANT LOAD, A DRINKING FOUNTAIN MAY
 BE REQUIRED FOR THIS ESTABLISHMENT; IF SO, WOULD YOU
 PLEASE PROVIDE THE FOLLOWING;
 A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 THE 2020 ACC FBC SEC. 211.2 AND FBC P SEC. 410.3.
  
 C. IT SHALL BE ACCESSIBLE IN ACCORDANCE WITH 2020 FBC
 ACC SEC. 211.2 & 602.1- 602.6. PROVIDE DRAWINGS AND
 DETAILS SHOWING: A) THE 30 X 48 IN. CLEAR FLOOR SPACE
 FOR A FORWARD APPROACH TO THE WHEELCHAIR ACCESSIBLE
 DRINKING FOUNTAIN 2020 FBC ACC SEC. 602.2 CLEAR FLOOR
 SPACE AND PLEASE SHOW KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, SPOUT LOCATIONS PER THE 2020 FBC ACC SEC. 306,
 307, & 602.2, COMPLIANCE WITH 2020 FBC ACC SEC. 307.2
 PROTRUSION LIMITS.
  
 D. PLEASE SHOW ON ISOMETRIC SANITARY AND WATER PER THE
 2020 FBC SEC. PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 6. ON SHEET P2.3;
  
 A. IT SHOWS A GAS GRILL ON THE ROOF. WILL THIS BE A
 TANK-TYPE OR CITY SYSTEM? WOULD YOU PLEASE CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 B. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 7. WOULD YOU PLEASE SHOW THE INDIRECT DRAIN ELEVATOR
 PIT ON THE ISOMETRIC PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 8. ON SHEET P3.3, PLEASE SHOW CLEANOUT AT THE BOTTOM OF
 EACH RISER PER THE 2020 FBC SEC. P 1101.8 CLEANOUTS
 REQUIRED.
  
 9. WOULD YOU PLEASE SUBMIT LISTED FIRE-STOPPING DETAILS
 FOR THE PIPPING THROUGH RATED WALLS OR THE FLOORS WHERE
 APPLICABLE. PLEASE SUBMIT THE COMPLETE ASSEMBLY DETAILS
 FOR THE SYSTEMS PER THE WPB AMENDMENTS TO FBC SEC.
 107.2.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2022-03-07 Cont ID  
Sent By rmcphers Date 2022-03-07 Time 08:46 Rev Time 0.00
Received By rmcphers Date 2022-03-07 Time 08:46 Sent To  
Notes
2022-03-07 08:47:03ROOFING SYSTEMS TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-12-29 Cont ID  
Sent By rmcphers Date 2021-12-29 Time 13:30 Rev Time 0.00
Received By rmcphers Date 2021-12-29 Time 13:30 Sent To  
Notes
2021-12-29 13:30:52SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-06-22 Cont ID  
Sent By rmcphers Date 2022-06-22 Time 10:37 Rev Time 0.00
Received By rmcphers Date 2022-06-22 Time 10:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-07 Cont ID  
Sent By rmcphers Date 2022-06-07 Time 10:39 Rev Time 0.00
Received By rmcphers Date 2022-06-07 Time 10:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-07 Cont ID  
Sent By rmcphers Date 2022-03-07 Time 08:56 Rev Time 0.00
Received By rmcphers Date 2022-03-07 Time 08:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-12-29 Cont ID  
Sent By rmcphers Date 2021-12-29 Time 14:00 Rev Time 0.00
Received By rmcphers Date 2021-12-29 Time 14:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2022-07-08 Cont ID  
Sent By llouie Date 2022-07-08 Time   Rev Time 0.00
Received By llouie Date 2022-07-08 Time   Sent To  
Notes
2022-07-08 12:14:47ZONING APPROVED WITH THE FOLLOWING PROVISO(S):
  
 1.) SCOPE OF PERMIT IS FOR THE NEW OFFICE BUILDING
 ONLY. PROPOSED NEW 2520 SQ. FT. WAREHOUSE/SERVICE BAY
 REQUIRES SEPARATE PERMIT (AND MINOR PD AMENDMENT FOR
 THE CHANGE IN BUILDING SQUARE FOOTAGE).
  
 2.) MINOR CHANGES DETECTED FROM THE APPROVED PLAN SET.
 A MINOR PLANNED DEVELOPMENT (PD) AMENDMENT FOR THE
 AS-BUILT WILL BE REQUIRED PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY (C.O.).
  
 3.) SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PARKING
 AREA, SIGNAGE, ETC.

Review Stop Z ZONING
Rev No 3 Status P Date 2022-06-03 Cont ID  
Sent By llouie Date 2022-06-03 Time   Rev Time 0.00
Received By llouie Date 2022-06-03 Time   Sent To  
Notes
2022-06-03 09:57:40ZONING APPROVED WITH THE FOLLOWING PROVISO(S):
  
 1.) SCOPE OF PERMIT IS FOR THE NEW OFFICE BUILDING
 ONLY. PROPOSED NEW 2520 SQ. FT. WAREHOUSE/SERVICE BAY
 REQUIRES SEPARATE PERMIT (AND MINOR PD AMENDMENT FOR
 THE CHANGE IN BUILDING SQUARE FOOTAGE).
  
 2.) MINOR CHANGES DETECTED FROM THE APPROVED PLAN SET.
 A MINOR PLANNED DEVELOPMENT (PD) AMENDMENT FOR THE
 AS-BUILT WILL BE REQUIRED PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY (C.O.).
  
 3.) SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PARKING
 AREA, SIGNAGE, ETC.

Review Stop Z ZONING
Rev No 2 Status F Date 2022-03-08 Cont ID  
Sent By llouie Date 2022-03-08 Time 16:49 Rev Time 0.00
Received By llouie Date 2022-03-08 Time   Sent To  
Notes
2022-03-08 16:49:27** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE [12/15/2021 REPEAT COMMENT]:
  
 1.) APPROVED SITE PLAN, SHOWING ALL APPROVED
 SITE/PROJECT (SQUARE FOOTAGE) CALCULATIONS, BUILDING
 SETBACKS, ETC. (REFERENCE: RESOLUTION NO. 187-21) SHALL
 BE PROVIDED AS PART OF THE PERMIT. ANY CHANGES TO THE
 APPROVED SITE PLAN WILL REQUIRE A PLANNED DEVELOPMENT
 (PD) AMENDMENT THROUGH THE DEVELOPMENT SERVICES
 DEPARTMENT - PLANNING DIVISION PRIOR TO THE APPROVAL OF
 THIS PERMIT.
  
 2.) ARCHITECTURAL ELEVATIONS PROVIDED IN THE PERMIT
 PLAN DO NOT MATCH THE APPROVED PLANS ADOPTED WITH
 RESOLUTION NO. 187-21. ALL PERMIT PLANS MUST MATCH THE
 APPROVED PLANS. ANY MODIFICATIONS TO THE PLANS WILL
 REQUIRE A PD AMENDMENT THROUGH THE DEVELOPMENT SERVICES
 DEPARTMENT - PLANNING DIVISION PRIOR TO THE APPROVAL OF
 THIS PERMIT.
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, SIGNAGE,
 PARKING AREA.
  
 * ANY REVISIONS/RESUBMITTAL MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CPD (HULETT)
  
 * REFERENCE: RESOLUTION NO. 178-21
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-12-15 Cont ID  
Sent By llouie Date 2021-12-15 Time   Rev Time  
Received By llouie Date 2021-12-15 Time   Sent To  
Notes
2021-12-15 16:34:09** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) APPROVED SITE PLAN, SHOWING ALL APPROVED
 SITE/PROJECT (SQUARE FOOTAGE) CALCULATIONS, BUILDING
 SETBACKS, ETC. (REFERENCE: RESOLUTION NO. 187-21) SHALL
 BE PROVIDED AS PART OF THE PERMIT. ANY CHANGES TO THE
 APPROVED SITE PLAN WILL REQUIRE A PLANNED DEVELOPMENT
 (PD) AMENDMENT THROUGH THE DEVELOPMENT SERVICES
 DEPARTMENT - PLANNING DIVISION PRIOR TO THE APPROVAL OF
 THIS PERMIT.
  
 2.) ARCHITECTURAL ELEVATIONS PROVIDED IN THE PERMIT
 PLAN DO NOT MATCH THE APPROVED PLANS ADOPTED WITH
 RESOLUTION NO. 187-21. ALL PERMIT PLANS MUST MATCH THE
 APPROVED PLANS. ANY MODIFICATIONS TO THE PLANS WILL
 REQUIRE A PD AMENDMENT THROUGH THE DEVELOPMENT SERVICES
 DEPARTMENT - PLANNING DIVISION PRIOR TO THE APPROVAL OF
 THIS PERMIT.
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, SIGNAGE,
 PARKING AREA.
  
 * ANY REVISIONS/RESUBMITTAL MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CPD (HULETT)
  
 * REFERENCE: RESOLUTION NO. 178-21
  