Plan Review Details - Permit 21110999
Plan Review Stops For Permit 21110999
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-04-07 Cont ID  
Sent By rmcdouga Date 2022-04-07 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2022-04-07 Time 08:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-14 Cont ID  
Sent By rmcdouga Date 2022-03-14 Time 13:15 Rev Time 0.00
Received By rmcdouga Date 2022-03-14 Time 13:15 Sent To  
Notes
2022-03-14 13:30:03PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT RESOLVED. [THE DIMENSIONS AND WEIGHT OF THE
 GENERATOR IN THE PAD ENGINEERING IS MORE THAN THE
 GENERATOR SHOWN PAGE 4 OF THE GENERATOR
 SPECIFICATIONS.] THE GENERATOR PAD CALCULATIONS ARE FOR
 A GENERATOR THAT WEIGHS 850 POUNDS. THE SPECIFICATIONS
 FOR THE 22KW GENERAC GENERATOR HAS THE UNIT'S WEIGHT AS
 466 POUNDS. FBC AMENDMENTS 107.2.1
  
 2) RESOLVED.
  
 3) RESOLVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-28 Cont ID  
Sent By rmcdouga Date 2022-01-28 Time 11:06 Rev Time 0.00
Received By rmcdouga Date 2022-01-28 Time 11:06 Sent To  
Notes
2022-01-28 11:06:09PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD CALCULATIONS ARE FOR A GENERATOR
 THAT WEIGHS 850 POUNDS. THE SPECIFICATIONS FOR THE 22KW
 GENERAC GENERATOR HAS THE UNIT'S WEIGHT AS 466 POUNDS.
 FBC AMENDMENTS 107.2.1
  
 2) THE VULT WIND SPEED IS 180 MPH ON THE PAD
 CALCULATIONS AND 190 MPH ON THE PAD DRAWING. FBC
 AMENDMENTS 107.2.1
  
 3) THE DESIGN NOTES ON THE DRAWING HAS THE 2021 FBC.
 THE CORRECT CODE EDITION IS THE 2020 FBC. IT APPEARS
 THAT THIS MAY HAVE BEEN ALTERED BY SOMEONE OTHER THAN
 THE ENGINEER.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-20 Cont ID  
Sent By jleahy Date 2022-01-20 Time 13:52 Rev Time 0.00
Received By jleahy Date 2022-01-20 Time 13:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-12-27 Cont ID  
Sent By lcrespo Date 2021-12-27 Time 11:42 Rev Time 0.00
Received By lcrespo Date 2021-12-27 Time 11:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-07 Cont ID  
Sent By rmcdouga Date 2022-04-07 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2022-03-22 Time 07:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-14 Cont ID  
Sent By rmcdouga Date 2022-03-14 Time 13:30 Rev Time 0.00
Received By rmcdouga Date 2022-02-17 Time 06:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-28 Cont ID  
Sent By rmcdouga Date 2022-01-28 Time 11:06 Rev Time 0.00
Received By rmcdouga Date 2021-12-17 Time 09:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By lcrespo Date 2021-12-27 Time 11:42 Rev Time 0.00
Received By lcrespo Date 2021-12-27 Time 11:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-04-07 Cont ID  
Sent By rmcdouga Date 2022-04-07 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2022-04-07 Time 08:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-14 Cont ID  
Sent By rmcdouga Date 2022-03-14 Time 13:13 Rev Time 0.00
Received By rmcdouga Date 2022-03-14 Time 13:13 Sent To  
Notes
2022-03-14 13:14:55THE GENERATOR PAD DRAWING HAS THE ENGINEER'S DIGITAL
 SIGNATURE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-01-28 Cont ID  
Sent By rmcdouga Date 2022-01-28 Time 10:28 Rev Time 0.00
Received By rmcdouga Date 2022-01-28 Time 10:28 Sent To  
Notes
2022-01-28 10:31:04THE GENERATOR PAD CALCULATIONS AND DRAWINGS DO NOT HAVE
 THE ENGINEER'S DIGITAL SIGNATURE. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & 61G1 OR FS 471 & 61G15

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-24 Cont ID  
Sent By vbroglia Date 2022-02-24 Time 16:31 Rev Time 0.00
Received By vbroglia Date 2022-02-24 Time 16:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-12-23 Cont ID  
Sent By vbroglia Date 2021-12-23 Time 13:46 Rev Time 0.00
Received By vbroglia Date 2021-12-23 Time 13:39 Sent To  
Notes
2021-12-23 13:46:2312/23/21 FAILED. PLEASE PROVIDE THE REAR AND SIDE
 SETBACKS OF THE GENARATOR
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]
  