Plan Review Details - Permit 21110994
Plan Review Stops For Permit 21110994
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-12-07 Cont ID  
Sent By cpuell Date 2021-12-07 Time 13:52 Rev Time 0.00
Received By cpuell Date 2021-12-07 Time 13:52 Sent To  
Notes
2021-12-07 13:52:40DEED PROVIDED AND UPDATED LOCATION FILE

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-11-22 Cont ID  
Sent By cpuell Date 2021-11-22 Time 12:18 Rev Time 0.00
Received By cpuell Date 2021-11-22 Time 12:18 Sent To  
Notes
2021-11-22 12:19:14PLEASE PROVIDE A WARRANTY DEED SO THAT WE CAN UPDATE
 THE OWNER INFORMATION. PLEASE EMAIL DEED TO
 [email protected]

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-01-04 Cont ID  
Sent By jwitmer Date 2022-01-04 Time 08:49 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By jwitmer Date 2021-12-27 Time 15:03 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-12-27 15:03:51TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-01-04 Cont ID  
Sent By jwitmer Date 2022-01-04 Time 08:48 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By jwitmer Date 2021-12-27 Time 15:02 Rev Time 0.00
Received By jwitmer Date 2021-12-27 Time 14:47 Sent To  
Notes
2021-12-27 14:47:36WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21110994
 ADD: 300 S AUSTRALIAN AVE. # 905
 CONT: MILLENNIUM DEVELOPMENT & DRYWALL, INC.
 TEL: 407-468-6101
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 12/27/2021
 ACTION: DENIED
  
 1) CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) MASTER BATH REMOVE TUB AND INSTALL NEW SHOWER. PLANS
 DO NOT REFLECT THE TYPE OF TILE BACKER BOARD TO BE
 INSTALLED IN ACCORDANCE WITH THE 2020 FBC-B 2509.2 BASE
 FOR TILE. MATERIALS USED AS A BASE FOR WALL TILE IN TUB
 AND SHOWER AREAS AND WALLS AND CEILING PANELS IN SHOWER
 AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND
 INSTALLED IN ACCORDANCE WITH MANUFACTURER?S
 RECOMMENDATIONS.
  
 3) NEW MASTER BATH FLOOR TILE, NO UNDERLAYMENT TESTING
 WAS SUBMITTED. FLOOR INSULATION/ UNDERLAYMENT (FBC-B
 2020) FOR TILE, STONE, MARBLE, VINYL LAMINATE FLOORING
 AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-01-03 Cont ID  
Sent By cwalker Date 2022-01-03 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-11-30 Cont ID  
Sent By cwalker Date 2021-11-30 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2021-11-30 10:23:53PROVIDE DOCUMENTATION ON THE TYPE OF NEW FLOOR TILE AND
 MEMBRANE BARRIER TO BE INSTALLED TO INCLUDE THE
 CRTITICAL RADIANT FLUX OF THE MATERIALS. NFPA 101
 10.2.7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-04 Cont ID  
Sent By lcrespo Date 2022-01-04 Time 09:17 Rev Time 0.00
Received By lcrespo Date 2021-12-30 Time 07:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-12-27 Time   Rev Time 0.00
Received By cdecoeur Date 2021-11-29 Time 06:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-01-04 Cont ID  
Sent By lcrespo Date 2022-01-04 Time 09:17 Rev Time 0.00
Received By lcrespo Date 2022-01-04 Time 09:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-12-17 Cont ID  
Sent By lcrespo Date 2021-12-14 Time 14:07 Rev Time 0.00
Received By lcrespo Date 2021-12-14 Time 13:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By jwitmer Date 2021-12-27 Time 15:04 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***