Plan Review Details - Permit 21110915
Plan Review Stops For Permit 21110915
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-04-07 Cont ID  
Sent By jgomez Date 2022-04-07 Time 17:27 Rev Time 0.00
Received By jgomez Date 2022-04-07 Time 14:47 Sent To  
Notes
2022-04-07 17:29:17BUILDING REVIEW APPROVED WITH PROVISO (NOTE: SUBMIT
 REQUIRED INFORMATION FOR REVIEW BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS):
 1- PROVIDE ENGINEERING FOR TRUSS ALTERATIONS AT FAMILY
 AREA TO ALLOW FOR NEW 8" TRAY CEILING. SEC. R802.10.4
 FBC-RESIDENTIAL.
 2- ARCHITECT TO SPECIFY ROOFING UNDERLAYMENT SHOWING
 COMPLIANCE WITH 2020 CODE SEC. R905.1.1.1
 FBC-RESIDENTIAL. NOTE: NOA SUBMITTED REQUIRES TWO
 LAYERS.
 3- DEFERRED SUBMITTAL: PROVIDE PRODUCT APPROVAL FOR:
 A)INSWING ENTRY DOOR WITH SIDELITE. B)16X8 FEET BIFOLD
 EXTERIOR DOORS AS SHOWN AT LOGGIA. C)ALL WINDOW
 TYPES/SIZES SHOWN ON PLANS. D)SLIDING GLASS DOORS.
 E)FRENCH DOORS. F)HURRICANE SHUTTERS IF DOORS AND
 WINDOWS DON'T HAVE IMPACT GLAZING. AND, PROVIDE
 COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE.
 4-DESIGNER OF RECORD TO REVIEW/APPROVE IN WRITING ALL
 PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-21 Cont ID  
Sent By jgomez Date 2022-03-21 Time 13:34 Rev Time 0.00
Received By jgomez Date 2022-03-21 Time 13:21 Sent To  
Notes
2022-03-21 13:34:37BUILDING REVIEW APPROVED WITH PROVISO (NOTE: SUBMIT
 REQUIRED INFORMATION FOR REVIEW BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS):
 1- PROVIDE ENGINEERING FOR TRUSS ALTERATIONS AT FAMILY
 AREA TO ALLOW FOR NEW 8" TRAY CEILING. SEC. R802.10.4
 FBC-RESIDENTIAL.
 2- ARCHITECT TO SPECIFY ROOFING UNDERLAYMENT SHOWING
 COMPLIANCE WITH 2020 CODE SEC. R905.1.1.1
 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH HISTORIC FOR ALLOWED ROOF TYPE.
 3- DEFERRED SUBMITTAL: PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF MATERIAL. NOTE: COORDINATE WITH HISTORIC.
 B)INSWING ENTRY DOOR WITH SIDELITE. C)ROOFING
 UNDERLAYMENT SPECIFIED ON PLANS. D)16X8 FEET BIFOLD
 EXTERIOR DOORS AS SHOWN AT LOGGIA. E)ALL WINDOW
 TYPES/SIZES SHOWN ON PLANS. F)SLIDING GLASS DOORS.
 G)FRENCH DOORS. H)HURRICANE SHUTTERS IF DOORS AND
 WINDOWS DON'T HAVE IMPACT GLAZING. AND, PROVIDE
 COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE.
 4-DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-18 Cont ID  
Sent By jgomez Date 2022-03-18 Time 14:18 Rev Time 0.00
Received By jgomez Date 2022-03-18 Time 09:38 Sent To  
Notes
2022-03-18 14:19:58RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21110915
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1- PROVIDE ENGINEERING FOR CUTTING EXISTING TRUSSES AT
 FAMILY AREA TO ALLOW FOR NEW 8" TRAY CEILING. SEC.
 R301.1 FBC-RESIDENTIAL
  
 2- ARCHITECT TO SPECIFY ROOFING UNDERLAYMENT SHOWING
 COMPLIANCE WITH 2020 CODE SEC. R905.1.1.1
 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH HISTORIC FOR ALLOWED ROOF TYPE.
  
 3- DEFERRED SUBMITTAL:
 PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF MATERIAL. NOTE: COORDINATE WITH HISTORIC.
 B)INSWING ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS.
 C)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 D)16X8 FEET BIFOLD EXTERIOR DOORS AS SHOWN AT LOGGIA.
 E)ALL WINDOW TYPES SHOWN ON PLANS.
 F)SLIDING GLASS DOORS.
 G)FRENCH DOORS.
 H)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 4-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-14 Cont ID  
Sent By jgomez Date 2022-01-14 Time 15:36 Rev Time 0.00
Received By jgomez Date 2022-01-14 Time 11:28 Sent To  
Notes
2022-01-14 15:38:57RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21110915
  
 NOTE:
 ADDITION SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- ALL ARCHITECTURAL DRAWINGS NEED ARCHITECT'S SEAL AND
 SIGNATURE AS REQUIRED BY SEC. 481 F.S. WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 PLANS WERE SUBMITTED ELECTRONICALLY. NEED PLANS WITH
 ARCHITECT'S DIGITAL SIGNATURE OR PROVIDE HARD COPY
 PLANS WITH THE ORIGINAL SEAL AND SIGNATURE.
  
 2- WINDOW "F" SPECIFIED ON THE WINDOW SCHEDULE ON SHEET
 A.07 AS AN EGRESS WINDOW DOESN'T COMPLY WITH EGRESS.
 40"X56" SINGLE HUNG WINDOW DOESN'T PROVIDE THE 24"
 CLEAR HEIGHT OPENING. REVISE AS REQUIRED OR PROVIDE
 WINDOW CUT SHEET SHOWING COMPLIANCE. SEC. R310.2.1
 FBC-RESIDENTIAL.
  
 3- CONSTRUCTION OF NEW LOGGIA STRUCTURAL COLUMNS IS NOT
 CLEAR. EXTERIOR ELEVATIONS CALL FOR WOOD COLUMNS, WHILE
 STRUCTURAL PLANS CALL FOR MASONRY COLUMNS. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. IF
 USING WOOD COLUMNS, THEN PROVIDE COMPLETE
 DETAILS/SPECIFICATIONS INCLUDING WOOD TYPE, AND TOP AND
 BOTTOM CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL
  
 4- SPECIFY ATTIC ACCESS SIZE. SEC. R807.1
 FBC-RESIDENTIAL.
  
 5- NEED COMPLETE BATHROOM WITH MAXIMUM POSSIBLE PRIVACY
 AND A DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS
 REQUIRED BY SEC. R320 FBC-RESIDENTIAL.
  
 6- REVISE/CLARIFY FRONT ENTRY WALL SECTION DETAIL
 07/S.02.
 A) THIS DETAIL SEEMS TO BE FOR AN INTERIOR BEARING WALL
 NOT FOR AN EXTERIOR WALL. REVISE AS REQUIRED TO SHOW
 INTERIOR AND EXTERIOR CONSTRUCTION MATERIALS,
 INSULATION, ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) REAR ELEVATION SPECIFIES VERTICAL SIDING ON REAR
 FACADE ONLY. PROVIDE DETAIL/SPECIFICATIONS FOR TYPE OF
 SIDING. WOOD OR CONCRETE?. CONCRETE SIDING REQUIRES
 PRODUCT APPROVAL. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- REVISE ROOF FASTENING SCHEDULE DETAIL 02/S.02.
 A)REVISE ROOF SHEATHING NAILING SPACING. ROOF SHEATHING
 NEEDS TO BE NAILED AT 4 INCHES O.C. IN THE FIELD AND
 EDGES AS REQUIRED BY SEC. R803.2.3.1 AND TABLE
 R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS ON ALL PLANS AND WALL
 SECTIONS TO AVOID CONFLICTS/DELAYS.
  
 B)REVISE ROOF FASTENING ZONES DIAGRAM TO MATCH CURRENT
 DIAGRAM SHOWN ON CURRENT 2020 CODE. SEE FIGURE
 R301.2(7) FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 8- LOGGIA SECTION DETAIL 05/S.01: THIS SECTION
 SPECIFIES 2X4 EXTERIOR FRAME WALL ABOVE NEW BIFOLDING
 GLASS DOOR. THERE IS NOT DETAIL 09/A.07. PROVIDE THIS
 DETAIL. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS SHOWING
 HOW COMPLYING WITH THE NEW 2020 CODE REQUIREMENT FOR
 ROOFING UNDERLAYMENT. SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH TYPE OF ROOFING SPECIFIED ON
 PLANS (TESLA PHOTOVOLTAIC ROOFING SYSTEM). CLEARLY
 SPECIFY WHICH METHOD OF SEC. R905.1.1.1 FBC-RESIDENTIAL
 IS GOING TO BE USED. AND PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY F.A.C. 61G20-3.001.
  
 10-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)TESLA PHOTOVOLTAIC ROOFING SYSTEM AND ANY OTHER ROOF
 SYSTEM TO BE USED.
 B)INSWING ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS.
 C)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 D)16X8 FEET BIFOLD EXTERIOR DOORS AS SHOWN AT LOGGIA.
 E)ALL WINDOW TYPES SHOWN ON PLANS.
 F)SLIDING GLASS DOORS.
 G)FRENCH DOORS.
 H)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 12-VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW
 BASED ON ALL SCOPE OF WORK SHOWN. VALUATION TO INCLUDE
 ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT
 AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3
 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS,
 INCLUDING DESIGN PROFESSIONAL FEES OR PROVIDE COST
 BREAKDOWN, INCLUDING DESIGN PROFESSIONAL FEES FOR
 BUILDING OFFICIAL APPROVAL.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-08 Cont ID  
Sent By jleahy Date 2022-04-08 Time 12:14 Rev Time 0.00
Received By jleahy Date 2022-04-08 Time 09:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-12-23 Cont ID  
Sent By jleahy Date 2021-12-23 Time 10:30 Rev Time 0.00
Received By jleahy Date 2021-12-23 Time 10:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-04-05 Cont ID  
Sent By ccole Date 2022-04-05 Time 17:22 Rev Time 0.00
Received By ccole Date 2022-04-05 Time 16:43 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-03-04 Cont ID  
Sent By ccole Date 2022-03-04 Time 14:21 Rev Time 0.00
Received By ccole Date 2022-03-04 Time 14:21 Sent To  
Notes
2022-03-04 14:37:052ND REVIEW FBC-2020 RES.
 PERMIT-21110915
 3/5/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS # 1 & 2
 FROM THE 1ST REVIEW ARE LISTED BELOW- PLEASE COMPLY.
  
 1) P1: SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALL
 MANUALS FOR THE TANKLESS WATER HEATERS, AND THE RANGE-
 SECTIONS G2448.1, G2447.1 FBC RES.
  
 2) P1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED-
 G2407.1.
  
 NEW COMMENT.
  
 1) THE DRAWINGS INDICATE THE TANKLESS WATER HEATER WILL
 BE INSTALLED LESS THAN THE MINIMUM REQUIRED CLEARANCE
 OF 4 FT. FROM THE OPERABLE WINDOWS. PLEASE RELOCATE THE
 UNIT IN ACCORDANCE WITH SECS. G2427.5 & G2427.8 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-12-02 Cont ID  
Sent By ccole Date 2021-12-02 Time 13:01 Rev Time 0.00
Received By ccole Date 2021-12-02 Time 11:16 Sent To  
Notes
2021-12-02 13:02:171ST REVIEW FBC-2020 RES.
 PERMIT-21110915
 12/2/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER?S SPECIFICATIONS AND INSTALL
 MANUALS FOR THE TANKLESS WATER HEATERS, AND THE RANGE-
 SECTIONS G2448.1, G2447.1 FBC RES.
  
 2) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE RANGE
 AND INDICATE HOW THE AIR WILL BE PROVIDED- G2407.1.
  
 3) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR
 INSTALLATION OF THE POOL HEATER. PLEASE PLACE A NOTE
 THAT THE POOL HEATER IS ?FUTURE? AND PROVIDE A
 GAS-TIGHT CAP AT THE LOCATION- G2415.15.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2022-04-12 Cont ID  
Sent By amhamilt Date 2022-04-12 Time 11:07 Rev Time 0.00
Received By amhamilt Date 2022-04-12 Time 11:07 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2022-03-18 Cont ID  
Sent By amhamilt Date 2022-03-18 Time 11:46 Rev Time 0.00
Received By amhamilt Date 2022-03-18 Time 11:46 Sent To  
Notes
2022-03-18 11:47:50THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PROPERTY IS IN A HISTORIC DISTRICT, METAL ROOF IS NOT
 ARCHITECTURALLY COMPATIBLE. PLEASE REVISE TO EITHER
 SHINGLE OR FLAT CONCRETE TILE ROOF.
 PLEASE ALSO REACH OUT FOR A COA FORM FOR ADDITION.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-11-30 Cont ID  
Sent By amhamilt Date 2021-11-30 Time 13:42 Rev Time 0.00
Received By amhamilt Date 2021-11-30 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-20 Cont ID  
Sent By jgomez Date 2022-04-20 Time 14:36 Rev Time 0.00
Received By jgomez Date 2022-03-31 Time 08:16 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-18 Cont ID  
Sent By jgomez Date 2022-03-18 Time 14:31 Rev Time 0.00
Received By jgomez Date 2022-03-03 Time 15:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-14 Cont ID  
Sent By jgomez Date 2022-01-14 Time 15:54 Rev Time 0.00
Received By jgomez Date 2021-11-20 Time 09:14 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-04-21 Cont ID  
Sent By aoliver Date 2022-04-21 Time 11:49 Rev Time 0.00
Received By aoliver Date 2022-03-18 Time 15:37 Sent To  
Notes
2022-04-21 11:54:094/21/22 NO IMPACT FEES DUE, SEE EMAIL UPLOADED AO
2022-03-18 15:37:483/18/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-01-14 Cont ID  
Sent By jgomez Date 2022-01-14 Time 15:46 Rev Time 0.00
Received By jgomez Date 2022-01-14 Time 15:46 Sent To  
Notes
2022-01-14 15:47:07IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-11-22 Cont ID  
Sent By medwards Date 2021-11-22 Time 09:50 Rev Time 0.00
Received By medwards Date 2021-11-22 Time 09:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-04-05 Cont ID  
Sent By ccole Date 2022-04-05 Time 17:21 Rev Time 0.00
Received By ccole Date 2022-04-05 Time 16:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-03-04 Cont ID  
Sent By ccole Date 2022-03-04 Time 14:18 Rev Time 0.00
Received By ccole Date 2022-03-04 Time 12:26 Sent To  
Notes
2022-03-04 14:20:382ND REVIEW FBC-2020 RES.
 PERMIT- 21110915
 3/5/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A.06 & P1: WHICH ONE OF THESE TWO PLANS SHOWS
 THE CORRECT MASTER BATH SHOWER SIZE AND LOCATION?- SEE
 SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-02 Cont ID  
Sent By ccole Date 2021-12-02 Time 11:51 Rev Time 0.00
Received By ccole Date 2021-12-02 Time 10:19 Sent To  
Notes
2021-12-02 11:52:121ST REVIEW FBC-2020 RES.
 PERMIT- 21110915
 12/2/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P1: PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE SPA TUB IN THE
 SHOWER. THE INSTRUCTIONS SHALL PROVIDE SPECIFIC
 GUIDELINES FOR INSTALLING THE TUB ON THE SLOPED SHOWER
 FLOOR INCLUDING STRUCTURAL REINFORCEMENT AND PLUMBING
 DRAIN, VENT, AND WATER SUPPLY PIPING DETAILS- SECTION
 107.2.1 WPB AND SECTION P2609.2 FBC RES.
  
 2) P1: PROVIDE A SHOWER PAN DRAWING WHICH SHOWS THE
 LINER, THE STRUCTURAL SUPPORTS, AND THE BATHTUB AND
 SHOWER DRAIN PIPING- SECTION 2709.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2022-04-07 Cont ID  
Sent By jgomez Date 2022-04-07 Time 17:31 Rev Time 0.00
Received By jgomez Date 2022-04-07 Time 17:30 Sent To  
Notes
2022-04-07 17:36:031- GAF SHINGLES NOA 21-0105.12.
  
 2- GAF SHINGLES UNDERLAYMENT VERSASHIELD NOA 21-1027.02
 .
 NOTE: SECTION R905.1.1.1(4) REQUIRES TWO LAYERS OF THIS
 UNDERLAYMENT.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-03-18 Cont ID  
Sent By jgomez Date 2022-03-18 Time 14:29 Rev Time 0.00
Received By jgomez Date 2022-03-18 Time 14:29 Sent To  
Notes
2022-03-18 14:30:04ROOFING REVIEW:
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ROOFING MATERIAL. NOTE: COORDINATE WITH HISTORIC.
 B) ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-01-14 Cont ID  
Sent By jgomez Date 2022-01-14 Time 15:47 Rev Time 0.00
Received By jgomez Date 2022-01-14 Time 15:47 Sent To  
Notes
2022-01-14 15:50:32ROOFING REVIEW:
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)TESLA PHOTOVOLTAIC ROOFING SYSTEM AND ANY OTHER ROOF
 SYSTEM TO BE USED.
 B) ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-04-07 Cont ID  
Sent By jgomez Date 2022-04-07 Time 17:56 Rev Time 0.00
Received By jgomez Date 2022-04-07 Time 17:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-04-07 Cont ID  
Sent By jgomez Date 2022-03-18 Time 14:30 Rev Time 0.00
Received By jgomez Date 2022-03-18 Time 14:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-01-14 Cont ID  
Sent By jgomez Date 2022-01-14 Time 15:53 Rev Time 0.00
Received By jgomez Date 2022-01-14 Time 15:51 Sent To  
Notes
2022-01-14 15:54:11SIGNATURE REVIEW
  
 1- ALL ARCHITECTURAL DRAWINGS NEED ARCHITECT'S SEAL AND
 SIGNATURE AS REQUIRED BY SEC. 481 F.S. WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 PLANS WERE SUBMITTED ELECTRONICALLY. NEED PLANS WITH
 ARCHITECT'S DIGITAL SIGNATURE OR PROVIDE HARD COPY
 PLANS WITH THE ORIGINAL SEAL AND SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2022-04-20 Cont ID  
Sent By amhamilt Date 2022-04-12 Time 11:08 Rev Time 0.00
Received By amhamilt Date 2022-04-12 Time 11:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-03-18 Cont ID  
Sent By amhamilt Date 2022-03-18 Time 11:54 Rev Time 0.00
Received By amhamilt Date 2022-03-18 Time 11:54 Sent To  
Notes
2022-03-18 11:55:03PLEASE UPLOAD A SITE PLAN AND SURVEY FOR THE ADDITION.

Review Stop Z ZONING
Rev No 1 Status P Date 2021-11-30 Cont ID  
Sent By amhamilt Date 2021-11-30 Time 13:49 Rev Time 0.00
Received By amhamilt Date 2021-11-30 Time 13:49 Sent To  
Notes
***NONE***