Plan Review Details - Permit 21110872
Plan Review Stops For Permit 21110872
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-04-04 Cont ID  
Sent By cthroop Date 2022-04-04 Time 16:20 Rev Time 0.00
Received By cthroop Date 2022-04-04 Time 16:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-28 Cont ID  
Sent By cthroop Date 2022-02-28 Time 15:41 Rev Time 0.00
Received By cthroop Date 2022-02-28 Time 09:05 Sent To  
Notes
2022-02-28 15:46:17BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. NOTE ON PLAN PAGE A-002 REFERS TO STRUCTURAL PLANS
 AND DETAILS FOR THE EXTERIOR WALL INFILL. NO STRUCTURAL
 PLANS OR DETAILS PROVIDED FOR REVIEW.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVAL OR MIAMI-DADE NOA, APPROVED UNDER THE 2020
 FBC, FOR THE PROPOSED EXT. WINDOWS AND MULLIONS TO BE
 INSTALLED.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
  
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-03-16 Cont ID  
Sent By jleahy Date 2022-03-16 Time 16:27 Rev Time 0.00
Received By jleahy Date 2022-03-16 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-31 Cont ID  
Sent By mpeterso Date 2022-01-31 Time 15:41 Rev Time 0.00
Received By mpeterso Date 2022-01-31 Time 15:41 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2022-04-05 Cont ID  
Sent By lcrespo Date 2022-04-05 Time 14:41 Rev Time 0.00
Received By lcrespo Date 2022-03-04 Time 14:41 Sent To  
Notes
2022-04-05 09:27:38GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE, AND A GAS PLAN REVIEW HAS NOT
 BEEN PERFORMED AT THIS TIME. PROVIDE COMPLETE PLANS AND
 GAS RISER THAT REFLECTS THE ENTIRE SCOPE OF GAS WORK TO
 BE DONE PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS ON FILE BUT NO GAS INFORMATION HAS
 BEEN SUBMITTED.
  
 A ISOMETRIC IS REQUIRED FOR GAS ISOMETRIC, ALL
 APPLIANCES, IF OTHER APPLIANCES ARE IN THE SYSTEM SHOW
 THEM, MANUFACTURE SPECIFICATION FOR EQUIPMENT AND
 REGULATOR, TYPE OF GAS, TOTAL BTU'S, LONGEST RUN,
 TABLES USED, PRESSURE OF GAS, SHOW AND LABEL SHUT OFF
 VALVE, UNIONS, REGULATORS AND DRIP LEGS IF USED.
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2022-04-05 Cont ID  
Sent By lcrespo Date 2022-02-22 Time 08:28 Rev Time 0.00
Received By lcrespo Date 2022-01-25 Time 09:05 Sent To  
Notes
2022-01-25 09:24:56GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE, AND A GAS PLAN REVIEW HAS NOT
 BEEN PERFORMED AT THIS TIME. PROVIDE COMPLETE PLANS AND
 GAS RISER THAT REFLECTS THE ENTIRE SCOPE OF GAS WORK TO
 BE DONE PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS ON FILE BUT NO GAS INFORMATION HAS
 BEEN SUBMITTED.
  
 NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS
 TIME. THIS WILL HAVE THE GAS APPROVE FOR A SUB PERMIT,
 OR IF YOU DECIDED NOT TO, PLEASE PUT A NOTE ON THE GAS
 HEATER (A SEPARATE PERMIT BY A LICENSED CONTRACTOR FOR
 THE GAS SYSTEM). AN N WILL BE PUT ON THIS REVIEW, WHICH
 STANDS FOR NOT REQUIRED, BUT A SUB PERMIT WON'T BE
 ISSUED ONCE A REVIEW IS DONE FOR THAT SUB PERMIT, SO
 PLEASE BE ADVISED ON THIS PROCEDURE.
  
 A ISOMETRIC IS REQUIRED FOR GAS ISOMETRIC, ALL
 APPLIANCES, IF OTHER APPLIANCES ARE IN THE SYSTEM SHOW
 THEM, MANUFACTURE SPECIFICATION FOR EQUIPMENT AND
 REGULATOR, TYPE OF GAS, TOTAL BTU'S, LONGEST RUN,
 TABLES USED, PRESSURE OF GAS, SHOW AND LABEL SHUT OFF
 VALVE, UNIONS, REGULATORS AND DRIP LEGS IF USED.
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-01-24 Cont ID  
Sent By amhamilt Date 2022-01-24 Time 16:22 Rev Time 0.00
Received By amhamilt Date 2022-01-24 Time 16:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-04 Cont ID  
Sent By cthroop Date 2022-04-04 Time 16:20 Rev Time 0.00
Received By cthroop Date 2022-03-03 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-28 Cont ID  
Sent By cthroop Date 2022-02-28 Time 15:46 Rev Time 0.00
Received By cthroop Date 2022-01-19 Time 09:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-03-07 Cont ID  
Sent By medwards Date 2022-03-07 Time 12:35 Rev Time 0.00
Received By medwards Date 2022-03-07 Time 12:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-20 Cont ID  
Sent By medwards Date 2022-01-20 Time 09:16 Rev Time 0.00
Received By medwards Date 2022-01-20 Time 09:16 Sent To  
Notes
2022-01-20 09:16:561ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21110872
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING ALL
 MECHANICAL WORKING BEING COMPLETED FOR THIS PROJECT. A
 MECHANICAL SUB PERMIT WILL ALSO BE NEEDED. FBC 107.2.1
  
 2) PLEASE SHOW ON THE DRAWING: THE DRYER EXHAUST AND
 THE TERMINATION LOCATION, THE RANGE HOOD WITH THE CFM?S
 OF THE MOTOR INSIDE THE HOOD ALONG WITH MAKE UP AIR IF
 REQUIRED. PLEASE ALSO SHOW ANY DUCTWORK CHANGES FOR THE
 MECHANICAL SYSTEM ALONG WITH THE CONDENSATE PIPING AND
 DRAINAGE LOCATION ON THE EXTERIOR OF THE HOME. PLEASE
 ALSO SHOW HOW THE RETURN AIR PATHWAY BACK TO THE NEW
 LOCATION OF THE AHU. PLEASE ALSO SHOW THE CFM?S OF THE
 NEW BATHROOM EXHAUST FAN AND THE TERMINATION LOCATION
 FOR THE EXHAUST DUCT. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-03-04 Cont ID  
Sent By lcrespo Date 2022-03-04 Time 14:41 Rev Time 0.00
Received By lcrespo Date 2022-03-04 Time 14:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-02-22 Cont ID  
Sent By lcrespo Date 2022-01-25 Time 09:05 Rev Time 0.00
Received By lcrespo Date 2022-01-25 Time 07:54 Sent To  
Notes
2022-01-25 09:26:3801/25/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. ON THE DEMO, THERE ARE DIFRENCECES BETWEEN THE
 PROPOSED;
  
 A. THE WASHER AND DRYER ARE IN A DIFFERENT LOCATION,
 AND ON PROPOSED, IT SAYS EXISTING. WOULD YOU PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE WASHING MACHINE SHUT-OFF VALVES SHALL BE
 ACCESSIBLE WITHOUT MOVING THE UNITS AND WITHIN REACH
 PER THE 2020 FBC SEC. R 2903.9.3.
  
 C. THERE IS A VEGETABLE SINK ON PROPOSED AND NOT SHOWN
 ON ISOMETRIC. WOULD YOU PLEASE INCORPORATE IN ISOMETRIC
 AND LABEL NEW PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. WOULD YOU PLEASE SHOW THE KITCHEN SINK ON ISOMETRIC
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL PLUMBING.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-16 Cont ID  
Sent By jleahy Date 2022-03-16 Time 16:29 Rev Time 0.00
Received By jleahy Date 2022-03-16 Time 16:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-28 Cont ID  
Sent By cthroop Date 2022-02-28 Time 15:41 Rev Time 0.00
Received By cthroop Date 2022-02-28 Time 09:05 Sent To  
Notes
***NONE***