Plan Review Details - Permit 21110869
Plan Review Stops For Permit 21110869
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-12-17 Cont ID  
Sent By cwalker Date 2021-12-17 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-11-22 Cont ID  
Sent By cwalker Date 2021-11-22 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2021-11-23 14:26:57SPECIFY DISTANCES FROM HVAC REGISTERS PER TABLE 8.3.2.5
 NFPA 13
 SPECIFY MAXIMUM DISTANCE BETWEEN HANGERS PER TABLE
 9.2.2.1 NFPA 13
 SPECIFY HOW HYDROSTATIC TESTING WILL BE CONDUCTED PER
 SECTION 25.2.1 NFPA 13
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-18 Cont ID  
Sent By lmarchan Date 2021-12-18 Time 08:39 Rev Time 0.00
Received By lmarchan Date 2021-12-16 Time 09:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-23 Cont ID  
Sent By mpeterso Date 2021-11-23 Time 12:39 Rev Time 0.00
Received By mpeterso Date 2021-11-23 Time 12:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-11-23 Cont ID  
Sent By mpeterso Date 2021-11-23 Time 12:39 Rev Time 0.00
Received By mpeterso Date 2021-11-23 Time 12:39 Sent To  
Notes
2021-11-23 14:27:14DISREGARD NOTES IN THIS REVIEW STOP - FIRE ENTERED IN
 ERROR. LEM
2021-11-22 13:30:34SPECIFY DISTANCES FROM HVAC REGISTERS PER TABLE 8.3.2.5
 NFPA 13
 SPECIFY MAXIMUM DISTANCE BETWEEN HANGERS PER TABLE
 9.2.2.1 NFPA 13
 SPECIFY HOW HYDROSTATIC TESTING WILL BE CONDUCTED PER
 SECTION 25.2.1 NFPA 13
  