Plan Review Details - Permit 21110737
Plan Review Stops For Permit 21110737
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-11-19 Cont ID  
Sent By cpuell Date 2021-11-19 Time 12:55 Rev Time 0.00
Received By cpuell Date 2021-11-19 Time 12:55 Sent To  
Notes
2021-11-19 12:56:35GARAGE ATTACHED TO THE MAIN HOUSE, NO NEED ADDRESSES
 NEEDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-01-18 Cont ID  
Sent By cthroop Date 2022-01-18 Time 15:21 Rev Time 0.00
Received By cthroop Date 2022-01-18 Time 14:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-12-11 Cont ID  
Sent By jleahy Date 2021-12-11 Time 11:57 Rev Time 0.00
Received By jleahy Date 2021-12-11 Time 11:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-18 Cont ID  
Sent By cthroop Date 2022-01-18 Time 15:57 Rev Time 0.00
Received By cthroop Date 2021-11-18 Time 08:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2022-01-25 Cont ID  
Sent By cthroop Date 2022-01-25 Time 10:36 Rev Time 0.00
Received By cthroop Date 2022-01-25 Time 10:36 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-01-18 Cont ID  
Sent By cthroop Date 2022-01-18 Time 15:14 Rev Time 0.00
Received By cthroop Date 2022-01-18 Time 15:14 Sent To  
Notes
2022-01-18 15:15:31IMPACT FEE QUESTIONNAIRE
  
 PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-11-19 Cont ID  
Sent By medwards Date 2021-11-19 Time 15:08 Rev Time 0.00
Received By medwards Date 2021-11-19 Time 15:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-01-18 Cont ID  
Sent By cthroop Date 2022-01-18 Time 15:54 Rev Time 0.00
Received By cthroop Date 2022-01-18 Time 14:31 Sent To  
Notes
2022-01-18 15:56:51PROVISOS ON PLAN PAGE EP:
 1. VTR PER P904.1
 2. HB VACUME BREAKER REQ. PER P608.16
 3. HW REQ. PER P607.1
 4. 2-WAY C/O REQ. PER P708.1.3
 5. A SEPERATE PERMIT IS REQUIRED FOR THE RELOCATED
 SPRINKLER SYSTEM AND WATER PURIFICATION SYSTEM.
 CT

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-01 Cont ID  
Sent By abelisle Date 2021-12-01 Time 17:47 Rev Time 0.00
Received By abelisle Date 2021-12-01 Time 16:25 Sent To  
Notes
2021-12-01 17:30:161ST REVIEW FBC-2020 PLUMBING
 PERMIT-21110737
 12/1/21
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. PLEASE CLEARLY INDICATE WHAT TYPE OF FLUIDS WILL BE
 DISCHARGED INTO THE 2 FLOOR DRAINS IN THE GARAGE FLOOR.
 IT WOULD APEAR AS THOUGH THIS GARAGE WILL BE USED TO
 WASH OFF/ DETAIL THE VEHICLES. NO OIL, SAND OR OTHER
 SUBSTANCES SHALL BE DISHARGED INTO THE CITYS SANITARY
 SEWER SYSTEM. AN OIL AND SAND TRAP WOULD BE REQUIRED TO
 SEPERATE THIS. PLEASE CLEARIFY .WPB CODE OF ORDINANCES
 SEC. 90-126. - PROHIBITIONS AND LIMITATIONS OF
 DISCHARGE. (3)POLLUTANTS WHICH CREATE A FIRE OR
 EXPLOSION HAZARD IN THE WWF. PROHIBITED MATERIALS
 INCLUDE, BUT ARE NOT LIMITED TO, PETROLEUM OIL AND
 NON-BIODEGRADABLE CUTTING OIL, GASOLINE, KEROSENE, FUEL
 OIL, MOTOR OIL, NAPHTHA, BENZENE, TOLUENE, XYLENE,
 ETHERS, ALCOHOLS, KETONES, ALDEHYDES, PEROXIDES,
 CHLORATES, PERCHLORATES, BROMATES, CARBIDES, HYDRIDES,
 AND SULFIDES OR ANY OTHER SUBSTANCE WHICH THE CITY, THE
 STATE, OR ANY FEDERAL AGENCY HAS DETERMINED IS A FIRE
 HAZARD OR A HAZARD TO THE WWF.
  
 2. FLOOR DRAINS REQUIRE TRAP PRIMMERS TO BE INSTALLED
 PER FBC P 2020 -901.2
  
 3. MINIMUM OF 1 SANITARY VENT SHALL BE RAN THROUGH THE
 ROOF PER FBC P 904.1
  
 4. PRESSURE VACUUM BREAKERS ARE REQUIRED FOR HOSE BIBBS
 AS PER FBC P608.16
  
 5. SEPERATE PERMIT REQUIRED FOR THE RELOCATION OF THE
 IRRIGATION AND THE WATER PURIFIER. WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 6. A SANITARY 2-WAY CLEAN OUT SHALL BE INSTALLED IN THE
 SEWER LINE WHERE THE SANITARY SEWER METS THE BUILDING
 MAIN DRAIN LINE ON THE EXTERIOR OF THE GARAGE.AS PER
 FBC P708.1.3
  
 7. HOW WILL HOT WATER BE SUPPLIED TO THE NEW SINK IN
 THE GARAGE? AS PER FBC P607.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-01-18 Cont ID  
Sent By cthroop Date 2022-01-18 Time 15:17 Rev Time 0.00
Received By cthroop Date 2022-01-18 Time 14:32 Sent To  
Notes
2022-01-18 15:17:49PROVISO ON PLAN PAGE A2.1: A SEPERATE ROOFING PERMIT IS
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-18 Cont ID  
Sent By cthroop Date 2022-01-18 Time 15:57 Rev Time 0.00
Received By cthroop Date 2022-01-18 Time 14:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-12-03 Cont ID  
Sent By llouie Date 2021-12-03 Time   Rev Time  
Received By llouie Date 2021-12-03 Time   Sent To  
Notes
2021-12-03 10:55:19* SEPARATE PERMIT REQUIRED FOR DRIVEWAY
 MODIFICATION/EXTENSION (MIN. 3 FT. SETBACK REQUIRED FOR
 DRIVEWAY). HOLD HAS BEEN PLACED ON C.O.