Plan Review Details - Permit 21110734
Plan Review Stops For Permit 21110734
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-03-02 Cont ID  
Sent By mpeterso Date 2022-03-02 Time 09:44 Rev Time 0.00
Received By mpeterso Date 2022-03-02 Time 09:44 Sent To  
Notes
2022-03-02 09:45:48VALUE ADJUSTED TO 175K AS PER S.HILL. M.P.3/2/22

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-02-10 Cont ID  
Sent By mpeterso Date 2022-02-10 Time 15:47 Rev Time 0.00
Received By mpeterso Date 2022-02-10 Time 15:47 Sent To  
Notes
2022-02-10 15:54:12ELECTRICAL PLAN REVIEW FAILED
 1) IT APPEARS A FAIR VALUE TO SUPPLY, 1,164 FIRE ALARM
 DEVICES, WOULD BE $70,000.
 PLEASE PROVIDE A FAIR VALUE OF THE FOLLOWING: CABLE,
 CABLE MOUNTS, DEVICE BOXES, AND LABOR TO WIRE AND
 INSTALL, 1,164 FIRE ALARM DEVICES, INCLUDING START UP
 AND TESTING, FOR AN 16 STORY, 371,020 SQUARE FOOT
 BUILDING. WPB F.B.C. 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-01-28 Cont ID  
Sent By mpeterso Date 2022-01-28 Time 10:49 Rev Time 0.00
Received By mpeterso Date 2022-01-28 Time 10:49 Sent To  
Notes
2022-01-28 10:50:35ELECTRIC REVIEW FAILED
 1.VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR,
 OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR OR
 PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By mpeterso Date 2021-12-27 Time 14:47 Rev Time 0.00
Received By mpeterso Date 2021-12-27 Time 14:47 Sent To  
Notes
2021-12-27 14:50:55IT APPEARS PLAN LABELED "FA-0" WITH AN ENGINEERS SEAL
 AND DIGITAL SIGNATURE CANNOT BE CERTIFIED BY DIGITAL
 SOFTWARE
 PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED
 AND SEALED BY THE ENGINEER OF RECORD
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-01-14 Cont ID  
Sent By cwalker Date 2022-01-14 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-20 Cont ID  
Sent By cwalker Date 2021-12-20 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-10 Cont ID  
Sent By mpeterso Date 2022-02-10 Time 15:55 Rev Time 0.00
Received By mpeterso Date 2022-02-10 Time 15:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-28 Cont ID  
Sent By mpeterso Date 2022-01-28 Time 10:51 Rev Time 0.00
Received By mpeterso Date 2022-01-28 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By mpeterso Date 2021-12-27 Time 14:51 Rev Time 0.00
Received By mpeterso Date 2021-12-27 Time 14:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-12-20 Cont ID  
Sent By medwards Date 2021-12-20 Time 08:40 Rev Time 0.00
Received By medwards Date 2021-12-20 Time 08:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-01-28 Cont ID  
Sent By mpeterso Date 2022-01-28 Time 10:50 Rev Time 0.00
Received By mpeterso Date 2022-01-28 Time 10:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By mpeterso Date 2021-12-27 Time 14:51 Rev Time 0.00
Received By mpeterso Date 2021-12-27 Time 14:51 Sent To  
Notes
2021-12-27 14:51:30IT APPEARS PLAN LABELED "FA-0" WITH AN ENGINEERS SEAL
 AND DIGITAL SIGNATURE CANNOT BE CERTIFIED BY DIGITAL
 SOFTWARE
 PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED
 AND SEALED BY THE ENGINEER OF RECORD
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  