| Plan Review Stops For Permit 21110734 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2022-03-02 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-02 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-02 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2022-03-02 09:45:48 | VALUE ADJUSTED TO 175K AS PER S.HILL. M.P.3/2/22 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-10 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-10 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2022-02-10 15:54:12 | ELECTRICAL PLAN REVIEW FAILED | | | 1) IT APPEARS A FAIR VALUE TO SUPPLY, 1,164 FIRE ALARM | | | DEVICES, WOULD BE $70,000. | | | PLEASE PROVIDE A FAIR VALUE OF THE FOLLOWING: CABLE, | | | CABLE MOUNTS, DEVICE BOXES, AND LABOR TO WIRE AND | | | INSTALL, 1,164 FIRE ALARM DEVICES, INCLUDING START UP | | | AND TESTING, FOR AN 16 STORY, 371,020 SQUARE FOOT | | | BUILDING. WPB F.B.C. 109.3 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-01-28 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-28 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-01-28 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2022-01-28 10:50:35 | ELECTRIC REVIEW FAILED | | | 1.VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR, | | | OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR OR | | | PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-12-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-12-27 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-12-27 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2021-12-27 14:50:55 | IT APPEARS PLAN LABELED "FA-0" WITH AN ENGINEERS SEAL | | | AND DIGITAL SIGNATURE CANNOT BE CERTIFIED BY DIGITAL | | | SOFTWARE | | | PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED | | | AND SEALED BY THE ENGINEER OF RECORD | | | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | | SIGNED. | | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | | DOCUMENTS ARE PREFERRED. | | | | | | PLEASE EMAIL [email protected] AND CC TO | | | [email protected] | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-01-14 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-01-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-12-20 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2021-12-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-10 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-10 |
Time |
15:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-01-28 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-28 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-01-28 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-12-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-12-27 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-12-27 |
Time |
14:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2021-12-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-12-20 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-12-20 |
Time |
08:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-01-28 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-28 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-01-28 |
Time |
10:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-12-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-12-27 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-12-27 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2021-12-27 14:51:30 | IT APPEARS PLAN LABELED "FA-0" WITH AN ENGINEERS SEAL | | | AND DIGITAL SIGNATURE CANNOT BE CERTIFIED BY DIGITAL | | | SOFTWARE | | | PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED | | | AND SEALED BY THE ENGINEER OF RECORD | | | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | | SIGNED. | | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | | DOCUMENTS ARE PREFERRED. | | | | | | PLEASE EMAIL [email protected] AND CC TO | | | [email protected] | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|