| Plan Review Stops For Permit 21110714 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
P |
Date |
2022-01-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-01-20 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-01-20 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2022-01-20 15:12:31 | RECEIVED REVISED LETTER FROM JENNY ALVAREZ. | | | | | | JULIO- | | | PLEASE DISREGARD PERVIOUS EMAIL AND ACCEPT ATTACHMENT | | | WITH TODAY?S DATE. | | | THANK YOU, | | | BEST REGARDS, | | | JENNY ALVAREZ | | | ADMINISTRATION | | | THE CURY GROUP | | | 1475 CENTREPARK BLVD. SUITE 100 | | | WEST PALM BEACH, FL 33401 | | | O 561-533-8888 | EXT. 500 | | | [email protected] | | | WWW.CURYGROUP.COM | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2022-01-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-01-20 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-01-20 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2022-01-20 10:24:05 | ASBESTOS LETTER DENIED: SECOND TIME. | | | | | | ORIGINAL COMMENT: | | | 1- ASBESTOS LETTER SUBMITTED DOESN'T HAVE THE ADDRESS | | | AND PERMIT NUMBER OF THE PROJECT. THIS INFORMATION IS | | | REQUIRED. SEE BELOW FOR STANDARD REQUIREMENTS FOR | | | ASBESTOS LETTER. | | | | | | RESPONSE: | | | 1) ASBESTOS LETTER SUBMITTED HAVE ADDITIONAL LANGUAGE | | | THAT IS NO PART OF THE REQUESTED INFORMATION. | | | CONTRACTOR TO SUBMIT REVISED LETTER ONLY WITH THE | | | REQUESTED INFORMATION TO AVOID CONFLICTS/DELAYS. ANY | | | OTHER INFORMATION REGARDING CITY POLICIES NEEDS TO BE | | | ADDRESSED TO THE BUILDING OFFICIAL. | | | | | | 2) LETTER SUBMITTED HAS NEW INFORMATION ADDED TO THE | | | ORIGINAL LETTER WITH DIFFERENT LETTERING TYPE AND SIZE. | | | AT THIS TIME IT IS NOT KNOWN IF THE CONTRACTOR HAS DONE | | | THE CHANGES. TO AVOID CONFLICTS/DELAYS PLEASE SUBMIT | | | REVISED LETTER WITH CONTRACTOR'S ACKNOWLEDGMENT THAT | | | CHANGES WERE DONE BY HIM. PLEASE PROVIDE REQUIRED | | | INFORMATION OR CONTRACTOR TO CONTACT THE BUILDING | | | OFFICIAL FOR ANY ISSUES REGARDING THIS MATTER. | | | | | | | | | | | | ASBESTOS REVIEW COMMENT: | | | 1-PLEASE PROVIDE A SIGNED ACKNOWLEDGMENT FROM THE | | | CONTRACTOR, ON CONTRACTOR'S LETTERHEAD, STATING THAT | | | THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | NOTE: | | | THE INFORMATION SHOULD INCLUDE THE ADDRESS, PERMIT | | | NUMBER AND ASBESTOS IN THE SUBJECT LINE. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-12-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-12-30 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-12-30 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2021-12-30 13:28:07 | ASBESTOS LETTER DENIED: | | | | | | 1- ASBESTOS LETTER SUBMITTED DOESN'T HAVE THE ADDRESS | | | AND PERMIT NUMBER OF THE PROJECT. THIS INFORMATION IS | | | REQUIRED. SEE BELOW FOR STANDARD REQUIREMENTS FOR | | | ASBESTOS LETTER. | | | | | | | | | ASBESTOS REVIEW: | | | 1-PLEASE PROVIDE A SIGNED ACKNOWLEDGMENT FROM THE | | | CONTRACTOR, ON CONTRACTOR'S LETTERHEAD, STATING THAT | | | THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | NOTE: | | | THE INFORMATION SHOULD INCLUDE THE ADDRESS, PERMIT | | | NUMBER AND ASBESTOS IN THE SUBJECT LINE. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-01-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-01-20 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-01-20 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2022-01-20 13:41:21 | 01/20/22 TALKED TO SCOTT HUGHES (ARCH.). THERE IS A | | | PROBLEM WITH DBPR WEBSITE WHEN ENTERING HIS NAME TO | | | FIND OUT HIS LICENSE. LICENSE ISSUE CLARIFIED. JG. | | | | | | NOTE: | | | PERMIT APPLICATION SUBMITTED IS FOR INTERIOR DEMO ONLY. | | | ADDITIONAL PLANS WERE SUBMITTED FOR PROPOSED WORK ALSO. | | | NEED TO SUBMIT THESE PLANS UNDER A SEPARATE PERMIT | | | APPLICATION FOR THE PROPOSED CONSTRUCTION. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-12-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-12-30 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-12-30 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2021-12-30 15:06:00 | INTERIOR DEMOLITION, BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #21110714. | | | | | | 1- PERSON SIGNING THE PLANS IS NOT AN ARCHITECT. PLANS | | | SUBMITTED NEED TO BE SIGNED AND SEALED BY AN ARCHITECT | | | FROM THE FIRM SHOWN ON THE TITLE BLOCK. CHAPTER 481 | | | F.S., 61G1-16.003 FAC, 61G1-16.004 FAC. | | | | | | NOTE: | | | PERMIT APPLICATION SUBMITTED IS FOR INTERIOR DEMO ONLY. | | | ADDITIONAL PLANS WERE SUBMITTED FOR PROPOSED WORK ALSO. | | | NEED TO SUBMIT THESE PLANS UNDER A SEPARATE PERMIT | | | APPLICATION FOR THE PROPOSED CONSTRUCTION. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-01-20 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-20 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-01-20 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2022-01-20 13:07:01 | APPROVED FOR DEMO ONLY, |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-01-04 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-04 |
Time |
08:40 |
Rev Time |
|
| Received By |
mpeterso |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-01-04 08:41:41 | | | | | | | 1- PERSON SIGNING THE PLANS IS NOT AN ARCHITECT. PLANS | | | SUBMITTED NEED TO BE SIGNED AND SEALED BY AN ARCHITECT | | | FROM THE FIRM SHOWN ON THE TITLE BLOCK. CHAPTER 481 | | | F.S., 61G1-16.003 FAC, 61G1-16.004 FAC. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2021-12-09 |
Time |
|
Rev Time |
|
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-12-09 09:14:01 | 16.4.4 ALTERATION OF BUILDINGS. | | | 16.4.4.1 WHERE THE BUILDING IS PROTECTED BY FIRE | | | PROTECTION | | | SYSTEMS, SUCH SYSTEMS SHALL BE MAINTAINED OPERATIONAL | | | AT ALL | | | TIMES DURING ALTERATION. | | | 16.4.4.2 WHERE ALTERATION REQUIRES MODIFICATION OF A | | | PORTION OF | | | THE FIRE PROTECTION SYSTEM, THE REMAINDER OF THE SYSTEM | | | SHALL BE | | | KEPT IN SERVICE AND THE FIRE DEPARTMENT SHALL BE | | | NOTIFIED. | | | 16.4.4.3 WHEN IT IS NECESSARY TO SHUT DOWN THE SYSTEM, | | | THE AHJ | | | SHALL HAVE THE AUTHORITY TO REQUIRE ALTERNATE MEASURES | | | OF | | | PROTECTION UNTIL THE SYSTEM IS RETURNED TO SERVICE. | | | 16.4.4.4 THE FIRE DEPARTMENT SHALL BE NOTIFIED WHEN THE | | | SYSTEM | | | IS SHUT DOWN AND WHEN THE SYSTEM IS RETURNED TO | | | SERVICE. | | | 16.4.4.5 ALL REQUIRED EXIT COMPONENTS SHALL BE | | | MAINTAINED IN | | | ACCORDANCE WITH THIS CODE AS DEEMED NECESSARY BY THE | | | AHJ. | | | 16.4.4.6 FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION | | | SHALL BE | | | MAINTAINED. NFPA 1 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-01-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-01-20 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-01-20 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2022-01-20 13:44:02 | 01/20/22 TALKED TO SCOTT HUGHES (ARCH.). THERE IS A | | | PROBLEM WITH DBPR WEBSITE WHEN ENTERING HIS NAME TO | | | FIND OUT HIS LICENSE. LICENSE ISSUE CLARIFIED. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-04 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-04 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-01-04 |
Time |
08:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2022-01-25 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2022-01-25 |
Time |
17:44 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2022-01-25 |
Time |
17:44 |
Sent To |
|
|
| Notes |
| 2022-01-25 17:45:08 | PRIVATE PROVIDER INSPECTION ONLY | | | | | | APPROVED | | | | | | RICHARD GATHRIGHT | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-01-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-01-20 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-01-20 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2022-01-20 10:17:47 | 01/20/22 TALKED TO SCOTT HUGHES (ARCH.). THERE IS A | | | PROBLEM WITH DBPR WEBSITE WHEN ENTERING HIS NAME TO | | | FIND OUT HIS LICENSE. LICENSE ISSUE CLARIFIED. JG. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-12-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-12-30 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-12-30 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2021-12-30 15:06:38 | SIGNATURE REVIEW | | | | | | 1- PERSON SIGNING THE PLANS IS NOT AN ARCHITECT. PLANS | | | SUBMITTED NEED TO BE SIGNED AND SEALED BY AN ARCHITECT | | | FROM THE FIRM SHOWN ON THE TITLE BLOCK. CHAPTER 481 | | | F.S., 61G1-16.003 FAC, 61G1-16.004 FAC. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|