| Plan Review Stops For Permit 21110702 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-04-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-04-19 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-04-19 |
Time |
14:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-15 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-15 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2022-03-15 15:10:10 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE MANUFACTURER'S SPECIFICATIONS THAT WERE | | | SUBMITTED ARE FOR A 26 KW BRIGGS AND STRATTON GENERATOR | | | THAT WEIGHS 625 LBS. THE ENGINEERING FOR THE GENERATOR | | | PAD DOES NOT HAVE A 26 KW B&S GENERATOR LISTED. SUBMIT | | | DOCUMENTS FOR MATCHING EQUIPMENT. FBC AMENDMENTS | | | 107.2.1 | | | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE | | | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | | PARKING LOTS AND LOADING DOCKS. | | | | | | 3) SEE SIGNATURE REVIEW COMMENTS. | | | | | 2022-02-07 09:47:56 | PERMIT IS FOR A GENERATOR INSTALL JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-04-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-04-07 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-04-07 |
Time |
15:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-02-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-02-07 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-02-07 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2022-02-07 09:42:27 | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PERMIT APPLICATION STATES TRANSFER SWITCH | | | INSTALLATION, THIS NEEDS TO BE A GEN--RES PERMIT TYPE, | | | SUBMIT A NEW APPLICATION FOR A GENERATOR INSTALLATION. | | | | | | 2) VALUE OF JOB IS TO LOW PLEASE SUBMIT A COST | | | BREAKDOWN FOR THE LABOR AND MATERIALS FOR A COMPLETE | | | GENERATOR INSTALLATION. | | | | | | 3) SENDING PLANS TO MECHANICAL FOR REVIEW OF EXHAUST | | | CLEARANCES, SEE SITE PLAN | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-12-09 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-12-09 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2021-12-09 13:05:49 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | IS THIS JUST FOR THE TRANSFER SWITCH? IF SO SUBMIT A | | | SIGNED RISER DIAGRAM SHOWING WIRE SIZES AND OVER | | | CURRENT PROTECTION. 215.5 | | | | | | WHY SUBMIT A SLAB PLAN? | | | | | | IS THIS A GENERATOR JOB? $3500? |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-02-08 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-02-08 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2022-02-08 14:03:54 | GAS ON PERMIT 21110901 - NOTED THAT A GEN-RES PERMIT IS | | | REQUIRED FOR GAS ROUGH TO PASS -- RWB | | 2022-02-07 09:45:14 | PLEASE SEE SITE PLAN FOR REVIEW OF EXHAUST FROM | | | GENERATOR SEE BLOCK STAMP ON PLAN. JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-04-20 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-04-20 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-04-20 |
Time |
08:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-15 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-01-24 |
Time |
15:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-12-09 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-11-17 |
Time |
10:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-02-08 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-02-08 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2022-02-08 14:02:04 | NO PLUMBING -- RWB | | 2022-02-07 09:45:41 | PLEASE SEE SITE PLAN FOR REVIEW OF EXHAUST FROM | | | GENERATOR SEE BLOCK STAMP ON PLAN. JLEAHY |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-04-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-04-19 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-04-19 |
Time |
12:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-15 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-15 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2022-03-15 15:09:32 | THE ENGINEER'S DIGITAL SIGNATUE IS REQUIRED ON THE | | | GENERATOR PAD DRAWING. ELECTRONICALLY SUBMITTED | | | DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR | | | ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE | | | OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF | | | DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN | | | APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER | | | DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE | | | ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE | | | AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO | | | PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE | | | ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15 | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-12-09 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-12-09 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2021-12-09 13:07:02 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | RESUBMITTED PALNS WILL BE REQIRED TO BE SIGNED. | | | | | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN | | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS | | | 471.003(2)(H); 471.025; FBC 107.2.1 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-04-20 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-04-20 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-04-20 |
Time |
08:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2022-03-14 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-03-14 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-03-14 |
Time |
13:47 |
Sent To |
|
|
| Notes |
|
|