Plan Review Details - Permit 21110619
Plan Review Stops For Permit 21110619
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-12-30 Cont ID  
Sent By cpuell Date 2021-12-30 Time 14:10 Rev Time 0.00
Received By cpuell Date 2021-12-30 Time 14:09 Sent To  
Notes
2021-12-30 14:10:32SECOND PERMIT APPLIED FOR FOR THE REAR BUILIND SEE
 21111063, THIS PERMIT FOR THE EAST BUILDING ONLY.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-11-19 Cont ID  
Sent By cpuell Date 2021-11-19 Time 16:03 Rev Time 0.00
Received By cpuell Date 2021-11-19 Time 16:03 Sent To  
Notes
2021-11-19 16:08:04PERMIT IS FOR BOTH THE BUILDINGS, A SEPARATE PERMIT
 WILL NEED TO BE APPLIED FOR THE GUEST HOUSE WITH THE
 ADDRESS OF 505 29TH ST. PLEASE CONTACT THE PERMIT
 LIBRARIANS FOR PERMIT TO BE SPLIT AND APPLY FOR A
 SECOND PERMIT. ONCE A SECOND PERMIT HAS BEEN APPLIED
 FOR PLEASE LET ME KNOW, FOR ANY QUESTIONS PLEASE
 CONTACT [email protected] OR CALL 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-01-28 Cont ID  
Sent By jgomez Date 2022-01-28 Time 11:04 Rev Time 0.00
Received By jgomez Date 2022-01-28 Time 08:57 Sent To  
Notes
2022-01-28 11:07:36PROVISO:
 (SECTION 702.4 FBC-EXISTING BUILDING)
 1-SECOND FLOOR WINDOW FALL PROTECTION: WINDOW OPENING
 CONTROL DEVICE COMPLYING WITH ASTM F2090 SHALL BE
 REQUIRED IF WINDOW SILL IS LESS THAN 24 INCHES ABOVE
 FINISHED FLOOR.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-01-27 Cont ID  
Sent By jgomez Date 2022-01-27 Time 17:56 Rev Time 0.00
Received By jgomez Date 2022-01-27 Time 17:14 Sent To  
Notes
2022-01-27 18:01:05RESIDENTIAL (R3) FOURTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21110619.
  
 1- MISSING PRODUCT APPROVALS LISTED ON THE ENGINEER'S
 REVISED WINDOW/DOOR SCHEDULE FOR:
 A) OK.
  
 ORIGINAL COMMENT:
 B)WINDOW #25: ALUMINUM WINDOW WALL SYSTEM NOA
 18-0319.09 AND 20-1118.02.
  
 RESPONSE:
 NOA 20-1116.02 SUBMITTED DOESN'T MATCH NOA'S LISTED BY
 THE ENGINEER ON THE WINDOW/DOOR SCHEDULE. PROVIDE
 PRODUCT APPROVALS LISTED BY TH ENGINEER OF RECORD.
  
 REMAINDER:
 WINDOW FALL PROTECTION (SECTION 702.4 FBC-EXISTING
 BUILDING)
 1- WINDOW OPENING CONTROL DEVICE COMPLYING WITH ASTM
 F2090 SHALL BE REQUIRED IF WINDOW SILL IS LESS THAN 24?
 ABOVE FINISHED FLOOR.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-01-26 Cont ID  
Sent By jgomez Date 2022-01-26 Time 15:35 Rev Time 0.00
Received By jgomez Date 2022-01-26 Time 14:12 Sent To  
Notes
2022-01-26 15:35:42RESIDENTIAL (R3) THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21110619.
  
 1- MISSING PRODUCT APPROVALS LISTED ON THE ENGINEER'S
 REVISED WINDOW/DOOR SCHEDULE FOR:
 A)DOOR #23: SWINGING EXTERIOR DOOR FL21835-R8.
  
 B)WINDOW #25: ALUMINUM WINDOW WALL SYSTEM NOA
 18-0319.09/20-1118.02.
  
 REMAINDER:
 WINDOW FALL PROTECTION (SECTION 702.4 FBC-EXISTING
 BUILDING)
 1- WINDOW OPENING CONTROL DEVICE COMPLYING WITH ASTM
 F2090 SHALL BE REQUIRED IF WINDOW SILL IS LESS THAN 24?
 ABOVE FINISHED FLOOR.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-01-13 Cont ID  
Sent By jgomez Date 2022-01-13 Time 17:08 Rev Time 0.00
Received By jgomez Date 2022-01-13 Time 17:08 Sent To  
Notes
2022-01-13 17:09:11RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21110619.
  
 NOTE:
 THERE ARE TWO SEPARATE BUILDINGS IN THIS PARCEL. TWO
 SEPARATE PERMIT APPLICATIONS WERE GENERATED TO AVOID
 CONFLICTS/CONFUSIONS AND ALLOW PROPER INSPECTIONS. THIS
 PERMIT #21110619 IS FOR THE MAIN HOUSE. AND PERMIT
 #21111063 IS FOR THE APT/GARAGE BUILDING. PLEASE SUBMIT
 ONLY THE INFORMATION PERTINENT TO THE MAIN HOUSE.
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT BY PREVIOUS PLAN REVIEWER:
 1. FBC EB 702.5, PROVIDE A PLAN WHICH SHOWS LOCATION OF
 WINDOWS/DOORS, SIZES, ROOM DESIGNATIONS, TYPE OF WINDOW
 PROPOSED, TYPE OF WINDOWS THAT ARE EXISTING.
  
 RESPONSE:
 REPEAT COMMENT. PROVIDE FLOOR PLAN OR SKETCH CLEARLY
 IDENTIFYING THE ROOMS WHERE WINDOWS/DOORS ARE GOING TO
 BE REPLACED. FOR EXAMPLE: BEDROOM, LIVING AREA, ETC.
 THIS IS REQUIRED TO IDENTIFY THE BEDROOMS AND VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS.
 NOTE: CLEARLY SPECIFY SIZE AND TYPE OF EXISTING WINDOW
 AND SIZE AND TYPE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
 COORDINATE WINDOWS/DOORS SHOWN ON THE FLOOR PLAN WITH
 WINDOWS/DOORS SHOWN ON THE ENGINEER WINDOW/DOOR
 SCHEDULE SUBMITTED TO AVOID CONFLICTS/DELAYS.
  
 ****TO FACILITATE THE FLOOR PLANS REQUIREMENT,
 CONTRACTOR MAY COPY PLANS SUBMITTED FOR THE MAIN HOUSE
 AND GARAGE/APT BUILDING FOR REFERENCE. CLEARLY
 KEY/IDENTIFY EACH WINDOW AND DOOR WITH WINDOW/DOOR
 SCHEDULE SUBMITTED.
  
 2- ENGINEER WINDOW/DOOR SCHEDULE SUBMITTED IS
 INCOMPLETE:
 CLEARLY SPECIFY TYPE OF WINDOW AND WINDOW DIMENSIONS
 (WIDTH X HEIGHT) NOT JUST THE OPENING ROUGH AREA. SEC.
 107.2.1 CITY AMENDMENTS. COORDINATE WITH ITEM #1 ABOVE.
  
 3- SECOND FLOOR WINDOW OPENING CONTROL DEVICES: WINDOW
 OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE
 REQUIRED WHEN THE TOP SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 24 INCHES (610 MM) ABOVE THE
 FINISHED FLOOR. CLEARLY SPECIFY IF THERE ARE ANY
 WINDOWS WHERE THE WINDOW SILL IS LESS THAN 24" ABOVE
 THE FINISH FLOOR. SEE SEC. 702.4 FBC-EXISTING BUILDING
 CODE
  
 4- PROVIDE COMPLETE FLORIDA PRODUCT APPROVALS. PRODUCT
 APPROVAL SUBMITTED IS MISSING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE. THIS PAGE IS REQUIRED BECAUSE IT
 SHOWS THE CURRENT CODE VERSION AND THE PRODUCT APPROVAL
 STATUS. CHAPTER 553 F.S. AND FAC 61G20-3.001.
 NOTE: SUBMIT COMPLETE FLORIDA PRODUCT APPROVAL (COVER
 PAGE AND INSTALLATION DRAWINGS) IN ONE PDF FOR EACH
 WINDOW/DOOR TYPE. DON?T SPLIT INTO TWO OR MORE SEPARATE
 FILES.
  
 ALSO, IT LOOKS LIKE SOME PRODUCT APPROVALS WERE
 SUBMITTED TWICE. PLEASE DELETE ANY REPEATED PRODUCT
 APPROVAL TO AVOID CONFLICTS/DELAYS.
  
 5- IF WINDOW REPLACEMENT INCLUDES WINDOW MULLIONS, THEN
 PROVIDE PRODUCT APPROVAL FOR SUCH WINDOW MULLIONS.
 (NOTE: NEED TO SPECIFY MULLION SIZE TO AVOID
 DELAYS/CONFLICTS).
  
 NOTE:
 COORDINATE WITH APT/GARAGE WINDOW/DOOR PERMIT #21111063
 BUILDING REVIEW COMMENTS TO HELP EXPEDITE THE REVIEW
 PROCESS WHEN RESUBMITTING.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-04 Cont ID  
Sent By shill Date 2021-12-04 Time 15:37 Rev Time 0.00
Received By shill Date 2021-12-04 Time 15:37 Sent To  
Notes
2021-12-04 15:39:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC EB 702.5, PROVIDE A PLAN WHICH SHOWS LOCATION OF
 WINDOWS/DOORS, SIZES, ROOM DESIGNATIONS, TYPE OF WINDOW
 PROPOSED, TYPE OF WINDOWS THAT ARE EXISTING.
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2022-01-26 Cont ID  
Sent By fmittner Date 2022-01-26 Time 11:47 Rev Time 0.00
Received By fmittner Date 2022-01-26 Time 11:47 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2022-01-03 Cont ID  
Sent By fmittner Date 2022-01-03 Time 10:45 Rev Time 0.00
Received By fmittner Date 2022-01-03 Time 10:45 Sent To  
Notes
2022-01-03 10:46:33NO UPDATED FLOOR PLANS WITH OPENING NUMBERS HAVE BEEN
 SUBMITTED TO CLEARLY SHOW FRONT WINDOWS ARE NOT
 INCLUDED.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-11-19 Cont ID  
Sent By fmittner Date 2021-11-19 Time 11:31 Rev Time 0.00
Received By fmittner Date 2021-11-19 Time 11:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-01-28 Cont ID  
Sent By jgomez Date 2022-01-28 Time 11:16 Rev Time 0.00
Received By jgomez Date 2022-01-28 Time 08:57 Sent To I
Notes
2022-01-28 08:57:52NEYITA LEIVA EMAILED NOA 20-1118.02. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-01-27 Cont ID  
Sent By jgomez Date 2022-01-27 Time 18:01 Rev Time 0.00
Received By jgomez Date 2022-01-27 Time 17:12 Sent To  
Notes
2022-01-27 17:14:14NEYITA LEIVA EMAILED PRODUCT APPROVALS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-26 Cont ID  
Sent By jgomez Date 2022-01-26 Time 15:38 Rev Time 0.00
Received By jgomez Date 2022-01-24 Time 16:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-13 Cont ID  
Sent By jgomez Date 2022-01-13 Time 17:10 Rev Time 0.00
Received By jgomez Date 2021-12-27 Time 16:27 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-04 Cont ID  
Sent By shill Date 2021-12-04 Time 15:40 Rev Time 0.00
Received By shill Date 2021-12-02 Time 11:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-01-26 Cont ID  
Sent By jgomez Date 2022-01-26 Time 15:38 Rev Time 0.00
Received By jgomez Date 2022-01-26 Time 15:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-01-13 Cont ID  
Sent By jgomez Date 2022-01-13 Time 17:09 Rev Time 0.00
Received By jgomez Date 2022-01-13 Time 17:09 Sent To  
Notes
2022-01-13 17:10:47ENGINEER'S WINDOW/DOOR SCHEDULE DIGITAL SIGNATURE IS
 OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-12-04 Cont ID  
Sent By shill Date 2021-12-04 Time 15:40 Rev Time 0.00
Received By shill Date 2021-12-04 Time 15:40 Sent To  
Notes
***NONE***