Plan Review Details - Permit 21110616
Plan Review Stops For Permit 21110616
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-12-03 Cont ID  
Sent By   Date 2021-12-03 Time   Rev Time 0.00
Received By jcclark Date 2021-12-03 Time 10:15 Sent To  
Notes
2021-12-03 10:15:25ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-11-17 Cont ID  
Sent By   Date 2021-11-17 Time   Rev Time 0.00
Received By jcclark Date 2021-11-17 Time 12:40 Sent To  
Notes
2021-11-17 12:45:42ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-04 Cont ID  
Sent By lmarchan Date 2021-12-04 Time 07:57 Rev Time 0.00
Received By lmarchan Date 2021-12-02 Time 11:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-23 Cont ID  
Sent By medwards Date 2021-11-23 Time 10:29 Rev Time 0.00
Received By medwards Date 2021-11-16 Time 10:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-12-03 Cont ID  
Sent By medwards Date 2021-12-03 Time 08:47 Rev Time 0.00
Received By medwards Date 2021-12-03 Time 08:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-23 Cont ID  
Sent By medwards Date 2021-11-23 Time 10:26 Rev Time 0.00
Received By medwards Date 2021-11-23 Time 10:26 Sent To  
Notes
2021-11-23 10:26:581ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21110616
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ADDRESS ON THE APPLICATION IS 1249 PALM BEACH
 LAKES BLVD. BUT THE ADDRESS ON THE HOOD DRAWINGS IS
 1225 PALM BEACH LAKES BLVD. PLEASE CORRECT.
  
 2) SHEET 5 OF 8 INDICATES A EF-5 AT 600 CFM?S OF
 EXHAUST. THE ORIGINAL PLANS DO NOT SHOW THIS EF-5 NOR
 DOES IT APPEAR ON THE AIR BALANCE REPORT. PLEASE SHOW
 THIS EF-5 AND WHAT IT IS EXHAUSTING. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-03 Cont ID  
Sent By medwards Date 2021-12-03 Time 08:47 Rev Time 0.00
Received By medwards Date 2021-12-03 Time 08:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-11-23 Cont ID  
Sent By medwards Date 2021-11-23 Time 10:28 Rev Time 0.00
Received By medwards Date 2021-11-23 Time 10:28 Sent To  
Notes
***NONE***