Plan Review Details - Permit 21110615
Plan Review Stops For Permit 21110615
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-11-17 Cont ID  
Sent By   Date 2021-11-17 Time   Rev Time 0.00
Received By jcclark Date 2021-11-17 Time 13:21 Sent To  
Notes
2021-11-17 13:22:13PENDING PROVISO
 7.9.2.3* THE EMERGENCY LIGHTING SYSTEM SHALL BE
 ARRANGED TO PROVIDE THE REQUIRED ILLUMINATION
 AUTOMATICALLY IN THE EVENT OF AN INTERRUPTION OF NORMAL
 LIGHTING DUE TO AN OF THE FOLLOWING
 (1) FAILURE OF THE PUBLIC UTILITY OR OTHER OUTSIDE
 ELECTRICAL POWER
 (2) OPENING OF A CIRCUIT BREAKER OR FUSE
 (3) MANUAL ACT(S), INCLUDING ACCIDENTAL OPENING OF A
 SWITCH CONTROLLING NORMAL LIGHTING FUNCTIONS
 7.10.1.5.1 ACCESS TO EXITS MUST BE MARKED BY APPROVED,
 READILY VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR
 WAY TO REACH THE EXIT IS NOT READILY APPARENT TO THE
 OCCUPANT.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jcclark Date 2021-11-17 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-14 Cont ID  
Sent By lmarchan Date 2021-12-14 Time 11:29 Rev Time 0.00
Received By lmarchan Date 2021-12-10 Time 08:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-18 Cont ID  
Sent By lmarchan Date 2021-11-18 Time 12:20 Rev Time 0.00
Received By lmarchan Date 2021-11-16 Time 10:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-12-13 Cont ID  
Sent By medwards Date 2021-12-13 Time 07:43 Rev Time 0.00
Received By medwards Date 2021-12-13 Time 07:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-17 Cont ID  
Sent By medwards Date 2021-11-17 Time 16:07 Rev Time 0.00
Received By medwards Date 2021-11-17 Time 16:07 Sent To  
Notes
2021-11-17 16:13:11PLEASE PROVIDE DETAILS FOR THE REFRIGERATION SYSTEMS:
 PROVIDE A MECHANICAL DRAWING SHOWING THE LOCATION OF
 THE WALKIN COOLER AND THE WALKIN COOLER/FREEZER. FBC
 107.2.1
 PROVIDE A DRAWING SHOWING THE LOCATION OF THE
 CONDENSING UNITS AND THE APPLIANCE TIE DOWN
 REQUIREMENTS. FBC 107.2.1
 PLEASE PROVIDE THE DETAILS OF THE REFRIGERATION USED IN
 THESE SYSTEMS. FBC M 1102
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-11-17 Cont ID  
Sent By medwards Date 2021-11-17 Time 16:13 Rev Time 0.00
Received By medwards Date 2021-11-17 Time 16:13 Sent To  
Notes
***NONE***