Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 08:10 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 08:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-26 Cont ID  
Sent By rmcphers Date 2022-01-26 Time 12:38 Rev Time 0.00
Received By rmcphers Date 2022-01-26 Time 12:38 Sent To  
Notes
2022-01-26 12:40:39FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO
 VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING
 TO PROJECTDOX ( [email protected] )
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-01-28 Cont ID  
Sent By pleduc Date 2022-01-28 Time   Rev Time 0.00
Received By pleduc Date 2022-01-28 Time 11:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-01-04 Cont ID  
Sent By pleduc Date 2022-01-04 Time   Rev Time 0.00
Received By pleduc Date 2022-01-04 Time 10:06 Sent To  
Notes
2022-01-04 10:17:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF INSTALL NEW TILE FLOOR
 TILE AREA OF FLOOR PLAN; HOWEVER, THERE IS NO FLOOR
 TILE "TYPE" PROVIDED.
  
 IS IT CERAMIC, PROCELAIN, CONCRETE, OR A LAMINATE.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE "TYPE" AND
 PRODUCT SPEC SHEET IF LAMINATE OF THE PROPOSED FINISHED
 TILE FLOORING.
  
  
 2) THERE IS AN INDICATION OF INSTALL NEW TILE FLOOR
 TILE AREA OF FLOOR PLAN; HOWEVER, THERE IS NO "FLOOR
 PLAN" SHOWING THE LOCATION OF THE PROPOSED FLOOR TILE
 INSTALL.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE "UNIT FLOOR
 PLAN" SHOWING THE LOCATION OF THE PROPOSED TILE
 FLOORING.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 08:10 Rev Time 0.00
Received By rmcphers Date 2022-01-27 Time 07:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-26 Cont ID  
Sent By rmcphers Date 2022-01-26 Time 12:40 Rev Time 0.00
Received By rmcphers Date 2022-01-03 Time 06:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-01-26 Cont ID  
Sent By rmcphers Date 2022-01-26 Time 12:40 Rev Time 0.00
Received By rmcphers Date 2022-01-26 Time 12:40 Sent To  
Notes
***NONE***