Plan Review Details - Permit 21110596
Plan Review Stops For Permit 21110596
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-12-30 Cont ID  
Sent By cthroop Date 2021-12-30 Time 14:12 Rev Time 0.00
Received By cthroop Date 2021-12-30 Time 13:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-04-13 Cont ID  
Sent By mpeterso Date 2022-04-13 Time 13:19 Rev Time 0.00
Received By mpeterso Date 2022-04-13 Time 13:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-03-17 Cont ID  
Sent By mpeterso Date 2022-03-17 Time 10:43 Rev Time 0.00
Received By mpeterso Date 2022-03-17 Time 10:43 Sent To  
Notes
2022-03-17 10:47:40ELECTRIC REVIEW FAILED
 1) PLANS NEED TO PROVIDE MORE CLARITY. PLEASE PROVIDE A
 FLOOR PLAN THAT INCLUDES ELECTRIC WORK ONLY. PLEASE
 PROVIDE AN ELECTRIC ONLY WORK SCOPE. FBC 107.2
 2 )PLEASE DETAIL ON DRAWING COMPLIANCE WITH ANY OF THE
 APPLICABLE NEC REQUIREMENTS INCLUDING BUT NOT LIMITED
 TO THE FOLLOWING:
 A) NEC 210.8 GFCI PROTECTION
 B) NEC 210.12 AND NEC 406.4 ARC-FAULT PROTECTION
 C) NEC 220.52 RECEPTACLE SPACING
 D) NEC 406.12 AND NEC 406.4(D)(5) TAMPER RESISTANT
 RECEPTACLES
 E) NEC 250.140 RANGE GROUNDING
 F) SMOKE/CARBON ALARMS AS PER FBC 553.883
 G) PLEASE PROVIDE SPECIFICATIONS OF NEW LIGHTS. THEY
 ARE STATED AS LOW VOLTAGE. WILL THIS BE LOW VOLTAGE
 WIRING? WHERE WILL THE LED DRIVER BE LOCATED? IF LOW
 VOLTAGE WIRING, PLEASE DETAIL WIRE TYPE AND INDICATE
 WHETHER CEILING IS A PLENUM
 3) PLEASE HAVE THE CONTRACTOR OR QUALIFIER WHO PREPARED
 THE DRAWING PROVIDE HIS/HER SIGNATURE ON IT- SECTION
 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) &
 471.025. SURVEYOR SEAL STATUTE 472.025
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-16 Cont ID  
Sent By mpeterso Date 2021-12-16 Time 14:00 Rev Time 0.00
Received By mpeterso Date 2021-12-16 Time 14:00 Sent To  
Notes
2021-12-16 14:00:37ELECTRICAL REVIEW FAILED
 1) PLEASE PROVIDE A SCOPE OF WORK DETAILING ALL
 ELECTRICAL WORK TO BE INSTALLED, CHANGED OR REMOVED
 2) PROVIDE DRAWINGS DETAILING LOCATIONS OF ALL
 ELECTRICAL WORK TO BE INSTALLED, CHANGED OR REMOVED
 F.B.C. 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-04-08 Cont ID  
Sent By ccole Date 2022-04-08 Time 10:49 Rev Time 0.00
Received By ccole Date 2022-04-08 Time 10:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-03-09 Cont ID  
Sent By ccole Date 2022-03-09 Time 10:32 Rev Time 0.00
Received By ccole Date 2022-03-09 Time 09:10 Sent To  
Notes
2022-03-09 10:49:342ND REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21110596
 3/9/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A WRITTEN SCOPE OF GAS WORK ON THE
 PLAN FOR CLARIFICATION- SEC. 107.2.1 WPB. CLARIFY IF
 ANY GAS PIPING, GAS APPLIANCES, SHUTOFFS, REGULATORS
 ETC. ARE BEING REPLACED OR RELOCATED. A GAS RISER MAY
 BE REQUIRED AS OUTLINED BELOW.
  
 REFER TO SECS. G2412.3 & G2412.4 FBC RES
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) 2ND REQUEST TO PROVIDE A GAS SUB- PERMIT- SEC 105.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-11-23 Cont ID  
Sent By ccole Date 2021-11-23 Time 11:37 Rev Time 0.00
Received By ccole Date 2021-11-23 Time 11:17 Sent To  
Notes
2021-11-23 11:44:361ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21110596
 11/23/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A GAS RISER DRAWING FOR THE NEW COOKTOP AND
 DRYER INSTALLATIONS- SECTION G2412.3 & G2412.4 FBC RES.
 THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) SUBMIT SPECS FOR ALL GAS-FIRED APPLIANCES TO BE
 INSTALLED- SECTIONS G2438 & G2447 FBC RES.
  
 3) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-13 Cont ID  
Sent By medwards Date 2022-04-13 Time 16:01 Rev Time 0.00
Received By medwards Date 2022-04-07 Time 08:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-17 Cont ID  
Sent By mpeterso Date 2022-03-17 Time 10:47 Rev Time 0.00
Received By mpeterso Date 2022-03-08 Time 14:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-30 Cont ID  
Sent By cthroop Date 2021-12-30 Time 14:13 Rev Time 0.00
Received By cthroop Date 2021-11-12 Time 15:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2022-04-13 Cont ID  
Sent By medwards Date 2022-04-13 Time 16:01 Rev Time 0.00
Received By medwards Date 2022-04-13 Time 16:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-03-10 Cont ID  
Sent By medwards Date 2022-03-10 Time 06:01 Rev Time 0.00
Received By medwards Date 2022-03-10 Time 05:59 Sent To  
Notes
2022-03-10 06:01:56PLEASE RESPOND TO THE 1ST CYCLE MECHANICAL REVIEW
 COMMENTS LISTED BELOW.
  
 PLEASE PROVIDE DETAILS FOR THE KITCHEN HOOD. I S THE
 HOOD DUCTED TO THE OUTDOORS? IF SO PLEASE SHOW THE DUCT
 WORK AND TERMINATION LOCATION. WHAT IS THE CFM'S FOR
 THE HOOD EXHAUST? YOU MAY NEED TO BRING IN MAKE UP AIR
 IF THE CFM'S ARE MORE THATN 800 CFM'S. IF SO, PLEASE
 SHOW THIS ON THE DRAWING. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-15 Cont ID  
Sent By medwards Date 2021-11-15 Time 07:08 Rev Time 0.00
Received By medwards Date 2021-11-15 Time 07:08 Sent To  
Notes
2021-11-15 07:11:21PLEASE PROVIDE DETAILS FOR THE KITCHEN HOOD. I S THE
 HOOD DUCTED TO THE OUTDOORS? IF SO PLEASE SHOW THE DUCT
 WORK AND TERMINATION LOCATION. WHAT IS THE CFM'S FOR
 THE HOOD EXHAUST? YOU MAY NEED TO BRING IN MAKE UP AIR
 IF THE CFM'S ARE MORE THATN 800 CFM'S. IF SO, PLEASE
 SHOW THIS ON THE DRAWING. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-04-08 Cont ID  
Sent By ccole Date 2022-04-08 Time 10:49 Rev Time 0.00
Received By ccole Date 2022-04-08 Time 10:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-03-09 Cont ID  
Sent By ccole Date 2022-03-09 Time 10:29 Rev Time 0.00
Received By ccole Date 2022-03-09 Time 09:10 Sent To  
Notes
2022-03-09 10:32:072ND REVIEW FBC-2020 RES.
 PERMIT- 21110596
 3/9/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. 2ND REQUEST FOR A WRITTEN
 SCOPE OF WORK FOR PLUMBING- SEE 1ST REVIEW COMMENT
 BELOW.
  
 1) PLEASE CLARIFY THE SCOPE OF PLUMBING WORK. ARE THE
 APPLIANCES AND SINK TO BE REPLACED IN SAME LOCATIONS,
 RELOCATED, OR NEW INSTALLATIONS? PLEASE PROVIDE A
 SANITARY RISER DRAWING FOR ALL NEW DRAIN AND VENT PIPE
 INSTALLATIONS- SECTIONS 107.2.1 & 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-11-23 Cont ID  
Sent By ccole Date 2021-11-23 Time 11:33 Rev Time 0.00
Received By ccole Date 2021-11-23 Time 10:54 Sent To  
Notes
2021-11-23 11:33:481ST REVIEW FBC-2020 RES.
 PERMIT- 21110596
 11/23/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE CLARIFY THE SCOPE OF PLUMBING WORK FOR THE
 LAUNDRY. ARE THE APPLIANCES AND SINK TO BE REPLACED IN
 SAME LOCATIONS, RELOCATED, OR NEW INSTALLATIONS? PLEASE
 PROVIDE A SANITARY RISER DRAWING FOR ALL NEW DRAIN AND
 VENT PIPE INSTALLATIONS- SECTIONS 107.2.1 & 107.3.5.3
 WPB.
  
 2) PLEASE SHOW THE LOCATIONS OF THE WASHING MACHINE
 SHUTOFF VALVES TO VERIFY THEY WILL BE IN AN ACCESSIBLE
 LOCATION- SEC. P2903.9.3 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-12-30 Cont ID  
Sent By cthroop Date 2021-12-30 Time 14:12 Rev Time 0.00
Received By cthroop Date 2021-12-30 Time 13:32 Sent To  
Notes
***NONE***