Plan Review Details - Permit 21110519
Plan Review Stops For Permit 21110519
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-12-13 Cont ID  
Sent By cpuell Date 2021-12-13 Time 17:06 Rev Time 0.00
Received By cpuell Date 2021-12-13 Time 17:06 Sent To  
Notes
2021-12-13 17:06:37ADDRESS APPROPRIATE FOR PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-08-30 Cont ID  
Sent By cthroop Date 2022-08-30 Time 17:33 Rev Time 0.00
Received By cthroop Date 2022-08-30 Time 15:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-10 Cont ID  
Sent By cthroop Date 2022-08-06 Time 10:33 Rev Time 0.00
Received By cthroop Date 2022-08-06 Time 09:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-24 Cont ID  
Sent By cthroop Date 2022-05-24 Time 15:02 Rev Time 0.00
Received By cthroop Date 2022-05-13 Time 05:24 Sent To  
Notes
2022-05-24 15:43:09PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BUILDING REVIEW COMMENTS
  
 1.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVAL, APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED
 DEVICES TO BE INSTALLED.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. PROVIDE THE ICC-ES REPORT FOR THE SPRAY APPLIED
 INSULATION.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. PROVIDE FLORIDA PRODUCT APPROVALS AND ICC-ES REPORT
 FOR THE PROPOSED SMART VENTS. INDICATE MODEL OF VENT TO
 BE INSTALLED.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-03-18 Cont ID  
Sent By fgiaquin Date 2022-03-18 Time 22:24 Rev Time 0.00
Received By fgiaquin Date 2022-03-18 Time 20:52 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-07-07 Cont ID  
Sent By rwbrown Date 2022-07-07 Time 11:18 Rev Time 0.00
Received By rwbrown Date 2022-07-07 Time 11:15 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-03-04 Cont ID  
Sent By lcrespo Date 2022-03-04 Time 13:17 Rev Time 0.00
Received By lcrespo Date 2022-03-04 Time 13:17 Sent To  
Notes
2022-03-04 13:20:0803/04/22 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P-2, A SECTION OF METAL PIPE FROM THE METER
 TO THE GENERATOR SEEMS TO BE UNDERGROUND, AND ZINC
 COATING SHALL NOT BE DEEMED ADEQUATE PROTECTION FOR
 UNDERGROUND GAS PIPING PER THE 20230 FBC G2415.11.1.
  
 2. WOULD YOU PLEASE PROVIDE THE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC RES. SEC.
 G2408.1.
  
 3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC
 RES. SEC. G2413.2 AND G2404.3.
  
 4. WOULD YOU PLEASE LABEL AND SHOW ALL UNIONS IN FRONT
 OF REGULATOR 1' OF EITHER SIDE PER THE 2 2020 FBC RES.
 SEC G2421.2.
  
 5. WOULD YOU PLEASE LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC FG SEC. 409.5 OR 2020 FBC
 RES. SEC. G2420.5.
  
 6. A GRILL ON THE ISOMETRIC IS NOT SHOWN ON THE
 ARCHITECTURAL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 7. A GAS GRILL IS SHOWN ON THE ISOMETRIC BUT IS IT FOR
 OUTDOOR USE, AND IS IT UNDER A COVERED PATIO; IF SO,
 PLEASE PROVIDE MANUFACTURERS RECOMMENDATION FOR A
 VENTILATION HOOD PER THE 2020 FBC RES. SEC. G2408.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-30 Cont ID  
Sent By cthroop Date 2022-08-30 Time 17:33 Rev Time 0.00
Received By cthroop Date 2022-08-17 Time 06:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-06 Cont ID  
Sent By cthroop Date 2022-08-06 Time 10:33 Rev Time 0.00
Received By cthroop Date 2022-07-06 Time 15:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-24 Cont ID  
Sent By cthroop Date 2022-05-24 Time 15:45 Rev Time 0.00
Received By cthroop Date 2022-03-03 Time 10:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-10-24 Cont ID  
Sent By lmarchan Date 2022-10-24 Time 16:58 Rev Time 0.00
Received By lmarchan Date 2022-10-14 Time 09:26 Sent To  
Notes
2022-10-24 16:58:14RECEIPT - MU-2022-048034 - $22.46
2022-10-14 09:27:0410/14/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-05-13 Cont ID  
Sent By cthroop Date 2022-05-13 Time 16:51 Rev Time 0.00
Received By cthroop Date 2022-05-13 Time 05:24 Sent To  
Notes
2022-05-13 16:52:20IMPACT FEE QUESTIONNAIRE
  
 PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-07-11 Cont ID  
Sent By medwards Date 2022-07-11 Time 13:29 Rev Time 0.00
Received By medwards Date 2022-07-11 Time 13:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-15 Cont ID  
Sent By medwards Date 2022-03-15 Time 11:23 Rev Time 0.00
Received By medwards Date 2022-03-15 Time 11:23 Sent To  
Notes
2022-03-15 11:23:431ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21110519
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS SHOWING THE
 GARAGE MEETS CONDITIONED SPACE FROM THE EC. FBC EC
 R402.1
  
 2) SHEET M-3: PLEASE REMOVE THE RETURN AIR GRILLE FROM
 HIS WALKIN CLOSET AS RETURN AIR SHALL NOT BE FROM A
 CLOSET. FBC RES M1602.2 ? 4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2022-08-30 Cont ID  
Sent By cthroop Date 2022-08-30 Time 17:32 Rev Time 0.00
Received By cthroop Date 2022-08-30 Time 15:37 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2022-08-16 Cont ID  
Sent By cthroop Date 2022-08-16 Time 17:12 Rev Time 0.00
Received By cthroop Date 2022-08-16 Time 06:59 Sent To  
Notes
2022-08-16 13:33:06NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
 FEMA DESK REFERENCE P 758
 FBC R322 FLOOD-RESISTANT CONSTRUCTION
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CONSTRUCTION DRAWING ELEVATION CERTIFICATE SHALL
 HAVE A VALID DIGITAL SIGNTURE.
  
 2. PROVIDE COVER SHEET AND EVALUATION REPORT FOR SMART
 VENT FL5822, MODEL 1540-520.
 THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE
 VERSION, AND STATUS, FBC R 301.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2022-08-06 Cont ID  
Sent By cthroop Date 2022-08-06 Time 09:48 Rev Time 0.00
Received By cthroop Date 2022-08-06 Time 09:05 Sent To  
Notes
2022-08-06 09:52:40NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
 FEMA DESK REFERENCE P 758
 FBC R322 FLOOD-RESISTANT CONSTRUCTION
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. SEE
 BELOW.
  
 SUBMIT A CORRECTED CONSTRUCTION DRAWING ELEVATION
 CERTIFICATE FOR REVIEW.
  
  
 NFIP REVIEW COMMENTS
  
 THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). THE FLOOD ZONE DESIGNATION FOR THIS SITE IS AE
 WITH A BASE FLOOD ELEVATION (BFE) OF 6'0" NAVD AND 7'0"
 NAVD,
 THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO.
 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD.
 THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE
 9'0" NAVD.
  
  
 PLEASE REFERENCE PLAN PAGE A1.10 FOR THE FOLLOWING
 COMMENTS:
  
 4A) PROVIDE MODEL NUMBER OF VENT TO BE INSTALLED.
 4B) STATE SQ/IN OF VENT AND HOW MUCH FLOOR AREA IT WILL
 COVER.
 4C) PLACE THE SF OF GARAGE FLOOR ON PLAN (579SF)
 4D) A/C EQUIPMENT SHALL BE AT OR ABOVE THE DESIGN FLOOD
 ELEVATION OF 9'0" NAVD.
  
 5. PLAN PAGE S-1 DOES NOT SHOW THE THIRD VENT INSTALLED
 ON AN ADJACENT WALL.
  
 6. LINE B1, NFIP COMMUNITY NAME AND NUMBER IS
 INCORRECT.
  
 7. LINE C1, THIS IS A CONSTRUCTION DRAWING EC.
  
 8. ENTER CORRECT DATA FOR LINES C2A THRU C2H.
  
 9. REMOVE PHOTOS OF AN EXISTING STRUCTURE. NOT
 APPLICABLE FOR A CONSTRUCTION DRAWING EC.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-05-24 Cont ID  
Sent By cthroop Date 2022-05-24 Time 15:43 Rev Time 0.00
Received By cthroop Date 2022-05-13 Time 05:51 Sent To  
Notes
2022-05-24 15:45:25NFIP REVIEW COMMENTS
  
 THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). THE FLOOD ZONE DESIGNATION FOR THIS SITE IS AE
 WITH A BASE FLOOD ELEVATION (BFE) OF 6'0" NAVD AND 7'0"
 NAVD,
 THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO.
 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD.
 THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE
 9'0" NAVD.
  
  
 PLEASE REFERENCE PLAN PAGE A1.10 FOR THE FOLLOWING
 COMMENTS:
  
 4A) PROVIDE MODEL NUMBER OF VENT TO BE INSTALLED.
 4B) STATE SQ/IN OF VENT AND HOW MUCH FLOOR AREA IT WILL
 COVER.
 4C) PLACE THE SF OF GARAGE FLOOR ON PLAN (579SF)
 4D) A/C EQUIPMENT SHALL BE AT OR ABOVE THE DESIGN FLOOD
 ELEVATION OF 9'0" NAVD.
  
 5. PLAN PAGE S-1 DOES NOT SHOW THE THIRD VENT INSTALLED
 ON AN ADJACENT WALL.
  
 6. LINE B1, NFIP COMMUNITY NAME AND NUMBER IS
 INCORRECT.
  
 7. LINE C1, THIS IS A CONSTRUCTION DRAWING EC.
  
 8. ENTER CORRECT DATA FOR LINES C2A THRU C2H.
  
 9. REMOVE PHOTOS OF AN EXISTING STRUCTURE. NOT
 APPLICABLE FOR A CONSTRUCTION DRAWING EC.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-07-07 Cont ID  
Sent By rwbrown Date 2022-07-07 Time 10:46 Rev Time 0.00
Received By rwbrown Date 2022-07-07 Time 10:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-04 Cont ID  
Sent By lcrespo Date 2022-03-04 Time 11:15 Rev Time 0.00
Received By lcrespo Date 2022-03-04 Time 10:43 Sent To  
Notes
2022-03-04 12:06:1403/04/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P-1, IT SHOWS A P TRAP FOR A 2" DRIP, AND
 IT REQUIRES A TRAP SEAL PROTECTION PER THE 2020 FBC
 SEC. 1002.4.1 TRAP SEAL PROTECTION.
  
 2. THE DRAWING ON THE TANK-LESS ONLY SHOWS TWO TANKS
 AND THREE IN THE SCOPE OF WORK. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. GAS UNITS REQUIRE CONDENSATE, AND THEY NEED TO BE 1'
 AWAY FROM THE STRUCTURE TO A SAFE LOCATION PER THE 2020
 FBC SEC R318.5.
  
 4. WOULD YOU PLEASE SUBMIT ON THE PLAN THE LOCATION OF
 THE TANK-LESS WATER HEATER AND THE LOCATION AND
 DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION
 TO THE WATER HEATER? THE LOCATION OF THE WATER HEATER
 SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. WOULD YOU PLEASE IDENTIFY ALL GAS APPLIANCES ON
 PLANS TO REFLECT GAS ISOMETRIC WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER
 DIAGRAM FOR WATER PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING. THE HOT WATER
 LINES NEED TO BE LOOPED FOR THE RECIRCULATING SYSTEM IN
 A CONTINUOUS LOOP. THERE IS A REQUIREMENT IN THE
 FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A TABLE
 THAT LIMITS THE BETWEEN THE SOURCE AND THE OUTLET;
 PLEASE REFER TO TABLE 404.5.1 FOR THE MAXIMUM ALLOWABLE
 PIPE LENGTH METHOD AND SIZE ACCORDANTLY.
  
 7. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-05-24 Cont ID  
Sent By cthroop Date 2022-05-24 Time 07:42 Rev Time 0.00
Received By cthroop Date 2022-05-13 Time 05:24 Sent To  
Notes
2022-05-24 07:43:17PROVISO ON PLAN PAGE S-3: A SEPERATE ROOFING PERMIT IS
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-08-30 Cont ID  
Sent By cthroop Date 2022-08-30 Time 17:33 Rev Time 0.00
Received By cthroop Date 2022-08-30 Time 15:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-07 Cont ID  
Sent By rwbrown Date 2022-07-07 Time 11:28 Rev Time 0.00
Received By rwbrown Date 2022-07-07 Time 11:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-05-24 Cont ID  
Sent By cthroop Date 2022-05-24 Time 12:37 Rev Time 0.00
Received By cthroop Date 2022-05-13 Time 05:24 Sent To  
Notes
2022-03-15 11:24:33MECHANICAL DIGITAL SIGNATURES APPROVED. ME

Review Stop Z ZONING
Rev No 2 Status P Date 2022-07-12 Cont ID  
Sent By afowlkes Date 2022-07-12 Time 12:37 Rev Time 0.00
Received By afowlkes Date 2022-07-12 Time 12:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-15 Cont ID  
Sent By afowkles Date 2022-03-15 Time 15:29 Rev Time 0.00
Received By afowlkes Date 2022-03-15 Time 15:19 Sent To  
Notes
2022-03-15 15:28:5903/15/22 FAILED - SEE ANNOTATIONS ON THE ELEVATION
 PLANS
  
 ROOF OVERHANG INTO REAR SETBACK NEEDS TO BE SPECIFIED.
 THE CODE DICTATES THAT ROOF OVERHANGS CANNOT EXTEND
 MORE THAN 3 FEET INTO ANY SETBACK
  
 THE CHIMNEY WAS MEASURED INCORRECTLY. CHIMNEY HEIGHT
 NEEDS TO BE MEASURE FROM THE HIGHEST POINT, AND THE
 PLAN DOES NOT MEASURE FROM THIS POINT. PLEASE NOTE THAT
 CHIMNEYS CAN ONLY EXCEED DISCTRICT HEIGHT REQUIREMENTS
 BY 10%OF THE DISTRICT REUIREMENTS, THEREFORE THE PLAN
 MAY NEED TO BE ALTERED TO FIT CODE.
  
 BUILDING HEIGHT IS MEASURED FROM FINISHED GRADE AND THE
 DRAWING DOES NOT SPECIFY WHERE THIS IS. ADDITIONALLY,
 THE MAX OVERALL BUILDING HEIGHT WAS MEASURED FROM A
 POINT BELOW GRADE, PLEASE CONFIRM WHETHER THIS IS THE
 POINT OF FINISHED GRADE.
  
 ALEXANDER FOWLKES
 [email protected]
 5618221431


Account Summary | Usage Policy | Privacy Policy