Plan Review Details - Permit 21110486
Plan Review Stops For Permit 21110486
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-02-18 Cont ID  
Sent By jleahy Date 2022-02-18 Time 10:51 Rev Time 0.00
Received By jleahy Date 2022-02-18 Time 10:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-02-02 Cont ID  
Sent By jleahy Date 2022-02-02 Time 10:06 Rev Time 0.00
Received By jleahy Date 2022-02-02 Time 09:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-13 Cont ID  
Sent By jleahy Date 2022-01-13 Time 15:47 Rev Time 0.00
Received By jleahy Date 2022-01-13 Time 15:47 Sent To  
Notes
2022-01-13 15:47:58SUB ELECTRICAL PERMIT REQUIRED JLEAHY

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2022-02-15 Cont ID  
Sent By ccole Date 2022-02-15 Time 12:31 Rev Time 0.00
Received By ccole Date 2022-02-15 Time 09:35 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2022-01-25 Cont ID  
Sent By ccole Date 2022-01-25 Time 11:11 Rev Time 0.00
Received By ccole Date 2022-01-25 Time 10:26 Sent To  
Notes
2022-01-25 11:12:073RD REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21110486
 1/25/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS- DENIED.
  
 1) GAS RISER CORRECTIONS- SECS. G2412.3 & G2412.4 FBC
 FG: A) THE BRANCH LINE TO THE GENERATOR IS NOT SHOWN.
 B) PLEASE SHOW THE 2 PSI DELIVERY PRESSURE AT THE
 METER. C) SHOW THE LOCATIONS OF THE LOW-PRESSURE
 REGULATORS. D) PLEASE PROVIDE THE PRINTED NAME AND
 SIGNATURE OF THE PERSON WHO PREPARED THE DRAWING- SEC.
 107.2.1 WPB.
  
 2) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR
 INSTALLATION OF THE GENERATOR- SEC. 107.2.1 WPB.
 COMPLETE PLANS AND SPECIFICATIONS SHALL BE SUBMITTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-01-13 Cont ID  
Sent By ccole Date 2022-01-13 Time 15:48 Rev Time 0.00
Received By ccole Date 2022-01-13 Time 10:15 Sent To  
Notes
2022-01-13 15:50:122ND REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21110486
 1/13/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW. THE REQUESTED RISER
 DRAWING WAS NOT SUBMITTED. PLEASE NOTE A RISER DRAWING
 IS ALSO REFERRED TO AS AN ISOMETRIC DRAWING.
  
 1) FAILED. WPB AMENDMENTS TO FBC- SECTION 107.3.5.3:
 PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES ALL
 NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE
 RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO
 FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 3) FAILED. PLACE NOTES OR MEASUREMENTS ON THE PLAN TO
 INDICATE THE WATER HEATER WILL BE INSTALLED WITH
 REQUIRED CLEARANCES AS SPECIFIED BY THE MANUFACTURER
 AND IN ACCORDANCE WITH SECTION G2427.8 FBC RES. NOT
 PROVIDED.
  
 4) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED-
 SECTION- G2407.1 FBC RES. NOT PROVIDED.
  
 5) FAILED. SHOW THE LOCATION OF THE DRYER AND PROVIDE
 VENTING AND MAKEUP AIR DETAILS- SECTION G2439.1,
 G2439.3, & G2439.5 FBC RES. PLEASE SEE PAGE 16 OF THE
 SUBMITTED DRYER INSTALLATION INSTRUCTIONS. PROVIDE
 EITHER A LOUVERED DOOR OR MAKEUP AIR OPENING IN THE
 DOOR WITH A MINIMUM OF 100 SQ. INCHES.
 NEW COMMENT.
  
 1) THE SUBMITTED GAS PIPING TABLES ARE OUTDATED. IF
 SUBMITTING PIPE SIZING TABLES PLEASE SUBMIT THE CURRENT
 TABLES FOUND IN THE FBC-2020 RES. OR THE FBC-2020 FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-12-02 Cont ID  
Sent By ccole Date 2021-12-02 Time 08:39 Rev Time 0.00
Received By ccole Date 2021-12-02 Time 08:28 Sent To  
Notes
2021-12-02 08:41:221ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21110486
 12/2/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WPB AMENDMENTS TO FBC- SECTION 107.3.5.3: PROVIDE A
 COMPLETE GAS RISER DRAWING THAT INCLUDES ALL NEW AND
 EXISTING GAS PIPING AND APPLIANCES AT THE RESIDENCE-
 SECTION G2412.3 & G2412.4 FBC RES. REFER TO FBC RES.
 CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALL
 MANUALS FOR THE WATER HEATER, BBQ GRILL, RANGE, AND
 DRYER- SECTIONS G2448.1, G2447.1, G2439.1 FBC RES.
  
 3) PLACE NOTES OR MEASURMENTS ON THE PLAN TO INDICATE
 THE WATER HEATER WILL BE INSTALLED WITH REQUIRED
 CLEARANCES AS SPECIFIED BY THE MANUFACTURER AND IN
 ACCORDANCE WITH SECTION G2427.8 FBC RES.
  
 4) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE RANGE
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION-
 G2407.1 FBC RES.
  
 5) SHOW THE LOCATION OF THE DRYER AND PROVIDE VENTING
 AND MAKEUP AIR DETAILS- SECTION G2439.1, G2439.3, &
 G2439.5 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-02-18 Cont ID  
Sent By jleahy Date 2022-02-18 Time 10:51 Rev Time 0.00
Received By jleahy Date 2022-02-11 Time 12:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-02 Cont ID  
Sent By jleahy Date 2022-02-02 Time 10:06 Rev Time 0.00
Received By jleahy Date 2022-01-24 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-01-13 Time   Rev Time 0.00
Received By aoliver Date 2022-01-12 Time 08:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-12-02 Time   Rev Time 0.00
Received By ccarvaja Date 2021-11-19 Time 10:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-02-15 Cont ID  
Sent By ccole Date 2022-02-15 Time 09:35 Rev Time 0.00
Received By ccole Date 2022-02-15 Time 09:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-02-15 Cont ID  
Sent By ccole Date 2022-01-25 Time 11:12 Rev Time 0.00
Received By ccole Date 2022-01-25 Time 10:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-02-15 Cont ID  
Sent By ccole Date 2022-01-13 Time 15:53 Rev Time 0.00
Received By ccole Date 2022-01-13 Time 10:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-02 Cont ID  
Sent By ccole Date 2021-12-02 Time 08:42 Rev Time 0.00
Received By ccole Date 2021-12-02 Time 08:28 Sent To  
Notes
2021-12-02 08:46:221ST REVIEW FBC-2020 RES. PLUMBING.
 PERMIT- 21110486
 12/2/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED PERMIT APPLICATION HAS BEEN CONVERTED
 TO A PRIMARY GAS PERMIT AS REQUIRED BY THE WPB BUILDING
 DEPT. PLEASE SUBMIT A PLUMBING SUB-PERMIT APPLICATION
 FOR INSTALLATION OF THE WATER HEATER AND PLUMBING
 PIPING- SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-12-02 Time   Rev Time 0.00
Received By ccole Date 2021-12-02 Time 08:28 Sent To  
Notes
***NONE***