| 2022-01-13 15:50:12 | 2ND REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 21110486 |
| | 1/13/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW. THE REQUESTED RISER |
| | DRAWING WAS NOT SUBMITTED. PLEASE NOTE A RISER DRAWING |
| | IS ALSO REFERRED TO AS AN ISOMETRIC DRAWING. |
| | |
| | 1) FAILED. WPB AMENDMENTS TO FBC- SECTION 107.3.5.3: |
| | PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES ALL |
| | NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE |
| | RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO |
| | FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE: |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| | UNIONS. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | K) PIPE SIZING TABLES. |
| | |
| | 3) FAILED. PLACE NOTES OR MEASUREMENTS ON THE PLAN TO |
| | INDICATE THE WATER HEATER WILL BE INSTALLED WITH |
| | REQUIRED CLEARANCES AS SPECIFIED BY THE MANUFACTURER |
| | AND IN ACCORDANCE WITH SECTION G2427.8 FBC RES. NOT |
| | PROVIDED. |
| | |
| | 4) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED- |
| | SECTION- G2407.1 FBC RES. NOT PROVIDED. |
| | |
| | 5) FAILED. SHOW THE LOCATION OF THE DRYER AND PROVIDE |
| | VENTING AND MAKEUP AIR DETAILS- SECTION G2439.1, |
| | G2439.3, & G2439.5 FBC RES. PLEASE SEE PAGE 16 OF THE |
| | SUBMITTED DRYER INSTALLATION INSTRUCTIONS. PROVIDE |
| | EITHER A LOUVERED DOOR OR MAKEUP AIR OPENING IN THE |
| | DOOR WITH A MINIMUM OF 100 SQ. INCHES. |
| | NEW COMMENT. |
| | |
| | 1) THE SUBMITTED GAS PIPING TABLES ARE OUTDATED. IF |
| | SUBMITTING PIPE SIZING TABLES PLEASE SUBMIT THE CURRENT |
| | TABLES FOUND IN THE FBC-2020 RES. OR THE FBC-2020 FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |