Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-03-15 Cont ID  
Sent By jwitmer Date 2022-03-15 Time 15:29 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-02-15 Cont ID  
Sent By jwitmer Date 2022-02-15 Time 13:36 Rev Time 0.00
Received By jwitmer Date 2022-02-15 Time 13:24 Sent To  
Notes
2022-02-15 13:35:33WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21110469
 ADD: 2450 PRESIDENTIAL WAY # 206
 PCN:74-43-43-18-10-000-2060
 CONT: WRIGHTS IMPACT WINDOW & DOOR LLC
 TEL: 561-588-7353
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. FEB.15TH/ 2022
 ACTION: DENIED
  
 1) COMPLIED.
 2A) COMPLIED.
  
 2B) COMPLIED. BUILD HT 240 FT.
  
 3) THE PRODUCT APPROVAL FOR THE SLIDING GLASS DOORS NOA
 21-0728.02 IS A OLDER VERSION, PLEASE UPDATE THE
 PRODUCT APPROVAL. THE SLIDING GLASS DOOR NOA 21-0728.02
 TECHNICAL SHEETS 5 OF 23 HAS NOT IDENTIFIED SILL
 HEIGHTS SOME OF THE SLIDING GLASS DOORS WILL REQUIRE
 HIGHER SILL HEIGHTS THAN OTHERS. 2020 FBC-B 1709.5.1
 EXTERIOR DOORS AND WINDOWS. EXCEPTION # 2. SILL
 LIMITING FACTOR.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-01-19 Cont ID  
Sent By jwitmer Date 2022-01-19 Time 10:32 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-24 Cont ID  
Sent By jwitmer Date 2021-11-24 Time 08:45 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-24 08:45:07WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21110469
 ADD: 2450 PRESIDENTIAL WAY # 206
 PCN:74-43-43-18-10-000-2060
 CONT: WRIGHT?S IMPACT WINDOW & DOOR LLC
 TEL: 561-588-7353
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 24TH/ 2021
 ACTION: DENIED
  
 1) THE WRIGHT'S FLOOR PLAN & OPENING SCHEDULE NEEDS TO
 SHOW WHO THE AUTHOR IS OF THE PLAN. CERTIFICATION BY
 CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  
 2A) DRAWING 1 WRIGHT?S FLOOR PLAN DOES NOT SHOW THE
 FLOOR PLAN IN THE OVER ALL CURVATURE OF THE BUILDING,
 NOR THE UNITS THAT ARE PROJECTED FURTHER OUT THAN OTHER
 PORTIONS OF THE WALL LINE CREATING A FLUTTERING OR
 GALLOPING AFFECT. ENGINEERING EXPRESS SHEET SHOWS FOR
 COMPLEX BUILDINGS USE CORNER ZONES IF AT ALL IN
 QUESTION. THIS WILL GREATLY AFFECT THE PRESSURES ON
 THESE OPENINGS AND SUBMITTED SCHEDULE.
 BUILDING END ZONES (5). THE FLOOR PLAN LAYOUT INDICATES
 THE WORK TO BE PERFORMED UNDER THIS PERMIT IS A CORNER
 UNIT OF A HIGHRISE BUILDING. THE WIND LOAD CHART UNDER
 NOTES STATES WHAT IS CONSIDERED AN END ZONE 10% OF THE
 LEAST HORIZONTAL DISTANCE OF THE BUILDING OR 40% OF THE
 MRH, BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL
 DISTANCE OR 3 FT. THE CONTRACTOR HAS NOT IDENTIFIED
 WHAT THE LEAST HORIZONTAL DISTANCE IS FOR THE BUILDING
 NOR THE LOCATION OF THE UNIT IN RELATIONSHIP TO THE
 BUILDING AND THE INTERCOASTAL WATERWAY. EXAMPLE ONLY.
 IF THE BUILDING HEIGHT IS APPROXIMATELY 180 FT. (MRH.)
 X 0.40= 72 FEET. THIS WOULD PUT ALL OPENINGS IN WIND
 ZONE 5 OR 10% OF THE LEAST HORIZONTAL DISTANCE OF THE
 BUILDING, ALSO UNKNOWN.
  
 2B) THE OTHER UNKNOWN IS THE BUILDING HEIGHT DEPENDING
 ON THE PERMIT:
 21110246/ 2450 PRESIDENTIAL WAY # 1707 240?
 21110466/ 2450 PRESIDENTIAL WAY # 807 240?
 21101014/ 2480 PRESIDENTIAL WAY # 501 220?
 21110245/ 2480 PRESIDENTIAL WAY # 1104 200?
 21110469/ 2450 PRESIDENTIAL WAY # 206 190?
  
  
 3) THE REVIEW OF THE SUBMITTED PRODUCT APPROVALS CANNOT
 OCCUR WITH ALL THE UNKNOWNS LISTED IN COMMENT 2.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2022-03-15 Time   Rev Time 0.00
Received By aoliver Date 2022-03-10 Time 07:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-15 Cont ID  
Sent By jwitmer Date 2022-02-15 Time 13:36 Rev Time 0.00
Received By jwitmer Date 2022-02-08 Time 07:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-19 Cont ID  
Sent By jwitmer Date 2022-01-19 Time 10:33 Rev Time 0.00
Received By jwitmer Date 2022-01-11 Time 15:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-11-24 Time   Rev Time 0.00
Received By cdecoeur Date 2021-11-16 Time 09:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2022-02-15 Cont ID  
Sent By jwitmer Date 2022-02-15 Time 13:36 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-01-19 Cont ID  
Sent By jwitmer Date 2022-01-19 Time 10:33 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-01-19 10:32:52SEE BUILDING REVIEW. JW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-24 Cont ID  
Sent By jwitmer Date 2021-11-24 Time 08:46 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-24 08:46:11THE WRIGHT'S FLOOR PLAN & OPENING SCHEDULE NEEDS TO
 SHOW WHO THE AUTHOR IS OF THE PLAN. CERTIFICATION BY
 CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  