Plan Review Details - Permit 21110361
Plan Review Stops For Permit 21110361
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-02-18 Cont ID  
Sent By cpuell Date 2022-02-18 Time 12:27 Rev Time 0.00
Received By cpuell Date 2022-02-18 Time 12:27 Sent To  
Notes
2022-02-18 12:28:05ADDRESS AND PARCEL UPDATED TO REFLECT THE LOCATION OF
 THE BUILDING. UPDATED PERMIT.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-02-02 Cont ID  
Sent By cpuell Date 2022-02-02 Time 10:48 Rev Time 0.00
Received By cpuell Date 2022-02-02 Time 10:48 Sent To  
Notes
2022-02-02 10:48:24PREVIOUS COMMENTS NOT ADDRESSED.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-01-14 Cont ID  
Sent By cpuell Date 2022-01-14 Time 09:57 Rev Time 0.00
Received By cpuell Date 2022-01-14 Time 09:57 Sent To  
Notes
2022-01-14 09:57:14BLDG C IS NOT AN OFFICIAL ADDRESS. CONTACT
 [email protected] OR CALL 561-805-6659 CALL TO ADDRESS
 ADDRESSING

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2021-11-10 Cont ID  
Sent By scwelter Date 2021-11-10 Time 11:48 Rev Time 0.00
Received By scwelter Date 2021-11-10 Time 11:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-06-23 Cont ID  
Sent By rmcphers Date 2022-06-23 Time 12:46 Rev Time 0.00
Received By rmcphers Date 2022-06-23 Time 12:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-05-24 Cont ID  
Sent By rmcphers Date 2022-05-24 Time 12:43 Rev Time 0.00
Received By rmcphers Date 2022-05-24 Time 12:32 Sent To  
Notes
2022-05-24 12:42:54NEW BUILDING (B)
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) PLEASE PROVIDE THE REQUIRED DOCUMENTATION PER FBC
 1612.5 FLOOD HAZARD DOCUMENTATION.
  
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
  
 1.FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES:
  
 1.2.FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD
 ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC
 ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM
 REQUIREMENTS IN SECTION 2.7.2.1 OF ASCE 24,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC
 FLOOD FORCES IN ACCORDANCE WITH SECTION 2.7.2.2 OF ASCE
 24.
  
 1.3.FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH
 ASCE 24.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-03-14 Cont ID  
Sent By rmcphers Date 2022-03-14 Time 13:36 Rev Time 0.00
Received By rmcphers Date 2022-03-14 Time 13:36 Sent To  
Notes
2022-03-14 13:39:14NEW BUILDING (B)
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) ELEVATION CERTIFICATE - A2 - ADDRESS SHOULD BE THE
 SAME AS SHOWN BY THE ADDRESS REVIEW - 8101 GEORGIA AV
  
 2) ELEVATION CERTIFICATE - C2(A) - ELEVATION SHOWN DOES
 NOT MATCH THE PROPOSED LOWEST FLOOR ELEVATION SHOWN ON
 THE DRAWINGS.(10.32 NAVD)
  
 3) PLEASE PROVIDE THE REQUIRED DOCUMENTATION PER FBC
 1612.5 FLOOD HAZARD DOCUMENTATION.
  
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
  
 1.FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES:
  
 1.2.FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD
 ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC
 ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM
 REQUIREMENTS IN SECTION 2.7.2.1 OF ASCE 24,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC
 FLOOD FORCES IN ACCORDANCE WITH SECTION 2.7.2.2 OF ASCE
 24.
  
 1.3.FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH
 ASCE 24.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-02-17 Cont ID  
Sent By rmcphers Date 2022-02-17 Time 09:09 Rev Time 0.00
Received By rmcphers Date 2022-02-11 Time 12:46 Sent To  
Notes
2022-02-11 12:54:31NEW BUILDING (B)
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) SURVEY SHOWS THE BUILDING IN A FLOOD ZONE - PLEASE
 PROVIDE AN ELEVATION CERTIFICATE FBC WPB 107.3.5.1.1
 (1)
  
 2) PLEASE PROVIDE THE REQUIRED DOCUMENTATION PER FBC
 1612.5 FLOOD HAZARD DOCUMENTATION.
  
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
  
 1.FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES:
  
 1.2.FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD
 ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC
 ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM
 REQUIREMENTS IN SECTION 2.7.2.1 OF ASCE 24,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC
 FLOOD FORCES IN ACCORDANCE WITH SECTION 2.7.2.2 OF ASCE
 24.
  
 1.3.FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH
 ASCE 24.
  
 3) PLEASE PROVIDE A FLOOD EMERGENCY PLAN PER FBC 1612.4
 ASCE 24-14 - 6.2.3 (3) WHERE REMOVABLE SHIELDS ARE TO
 BE USED, A FLOOD EMERGENCY PLAN SHALL BE APPROVED BY
 THE AUTHORITY HAVING JURISDICTION
 AND SHALL SPECIFY, AT A MINIMUM, THE FOLLOWING
 INFORMATION: STORAGE LOCATIONS OF THE SHIELDS, THE
 METHOD OF INSTALLATION, CONDITIONS ACTIVATING
 INSTALLATION, MAINTENANCE OF SHIELDS AND ATTACHMENT
 DEVICES, PERIODIC PRACTICE OF INSTALLING SHIELDS,
 TESTING SUMP PUMPS AND OTHER DRAINAGE MEASURES, AND
 INSPECTING NECESSARY MATERIAL AND EQUIPMENT TO ACTIVATE
 OR IMPLEMENT FLOODPROOFING. THE FLOOD EMERGENCY
 PLAN SHALL BE POSTED PERMANENTLY IN AT LEAST TWO
 CONSPICUOUS LOCATIONS WITHIN THE STRUCTURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By rmcphers Date 2021-12-27 Time 15:08 Rev Time 0.00
Received By rmcphers Date 2021-12-27 Time 14:43 Sent To  
Notes
2021-12-27 14:44:36METAL BUILDING "B"
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY.
  
 2) PLEASE PROVIDE A SURVEY SHOWING EASEMENTS, FLOOD
 ZONE ETC.
  
 3) PLEASE PROVIDE COPIES OF THE PRODUCT APPROVALS
 LISTED ON THE METAL BUILDING DRAWINGS FOR THE EXTERIOR
 ROOF AND WALL PANELS.
  
 4) PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR
 DOORS AND LOUVERS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD. FBC WPB
 107.3.4

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-06-07 Cont ID  
Sent By mpeterso Date 2022-06-07 Time 08:18 Rev Time 0.00
Received By mpeterso Date 2022-06-07 Time 08:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-03-29 Cont ID  
Sent By mpeterso Date 2022-03-29 Time 13:24 Rev Time 0.00
Received By mpeterso Date 2022-03-29 Time 13:24 Sent To  
Notes
2022-03-29 13:28:01ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE CLARITY FOR AREAS DETAILED AS
 UNDERCLASSIFIED AS THIS LAUGUAGE APPEARS TO BE
 CONFUSING. FBC 107
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-02-11 Cont ID  
Sent By mpeterso Date 2022-02-11 Time 14:06 Rev Time 0.00
Received By mpeterso Date 2022-02-11 Time 14:06 Sent To  
Notes
2022-02-11 14:07:38ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE DOCUMENTATION STATING THE HAZARDOUS
 CLASSIFICATION FOR THE FOLLOWING AREAS, FERTILIZER
 STORAGE ROOM,NEC 500.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-01-10 Cont ID  
Sent By jleahy Date 2022-01-10 Time 16:10 Rev Time 0.00
Received By jleahy Date 2022-01-10 Time 16:09 Sent To  
Notes
2022-01-10 16:12:14ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR
 BRANCH CIRCUIT(S).
 (A) GROUNDING ELECTRODE. BUILDING(S) OR STRUCTURE(S)
 SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING
 ELECTRODE OR GROUNDING ELECTRODE SYSTEM INSTALLED IN
 ACCORDANCE WITH PART III OF ARTICLE 250. THE GROUNDING
 ELECTRODE
 CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH
 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING
 ELECTRODE,
 THE GROUNDING ELECTRODE(S) REQUIRED IN 250.50 SHALL BE
 INSTALLED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-11-30 Cont ID  
Sent By rrossano Date 2021-11-30 Time   Rev Time  
Received By rrossano Date 2021-11-30 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-03-14 Cont ID  
Sent By   Date 2022-03-14 Time   Rev Time 0.00
Received By bdolan Date 2022-03-14 Time 12:32 Sent To  
Notes
2022-03-14 12:32:37BUILDING MAY REQUIRE EXTERIOR PLACARDING OF MATERIAL
 STORAGE.
  
 STORAGE OF FLAMMABLE OR COMBUSTIBLE LIQUIDS SHALL
 COMPLY WITH NFPA 30
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-03 Cont ID  
Sent By   Date 2022-02-03 Time   Rev Time 0.00
Received By jcclark Date 2022-02-03 Time 09:12 Sent To  
Notes
2022-02-03 09:14:05PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 FLAMMABLE AND COMBUSTIBLE LIQUIDS SHALL COMPLY WITH
 NFPA 30, 2015 EDITION
  
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-11-23 Cont ID  
Sent By   Date 2021-11-23 Time   Rev Time 0.00
Received By jcclark Date 2021-11-23 Time 08:22 Sent To  
Notes
2021-11-23 08:29:28PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 FLAMMABLE AND COMBUSTIBLE LIQUIDS SHALL COMPLY WITH
 NFPA 30, 2015 EDITION
  
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-06-23 Cont ID  
Sent By rmcphers Date 2022-06-23 Time 12:47 Rev Time 0.00
Received By rmcphers Date 2022-06-23 Time 07:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-06-07 Cont ID  
Sent By mpeterso Date 2022-06-07 Time 08:19 Rev Time 0.00
Received By mpeterso Date 2022-05-07 Time 11:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-29 Cont ID  
Sent By mpeterso Date 2022-03-29 Time 13:28 Rev Time 0.00
Received By mpeterso Date 2022-02-28 Time 12:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-18 Cont ID  
Sent By lmarchan Date 2022-02-18 Time 15:48 Rev Time 0.00
Received By lmarchan Date 2022-02-01 Time 16:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-14 Cont ID  
Sent By cpuell Date 2022-01-14 Time 09:57 Rev Time 0.00
Received By cpuell Date 2021-11-20 Time 08:23 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By rmcphers Date 2021-12-27 Time 15:02 Rev Time 0.00
Received By rmcphers Date 2021-12-27 Time 15:02 Sent To  
Notes
2021-12-27 15:03:28STORAGE BUILDING

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-03-16 Cont ID  
Sent By medwards Date 2022-03-16 Time 17:11 Rev Time 0.00
Received By medwards Date 2022-03-16 Time 17:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-02-14 Cont ID  
Sent By medwards Date 2022-02-14 Time 06:25 Rev Time 0.00
Received By medwards Date 2022-02-14 Time 06:25 Sent To  
Notes
2022-02-14 06:27:09THE ATTACHMENT FOR THE CHEMICALS MSDS MENTIONED IN THE
 RESPONSE LETTER IS NOT WITH THIS SUBMITTAL. PLEASE
 PROVIDE THE CHEMICAL MSDS DATA SHEETS FOR THE PRODUCTS
 BEING STORED IN THIS BUILDING.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-09 Cont ID  
Sent By medwards Date 2021-12-09 Time 14:27 Rev Time 0.00
Received By medwards Date 2021-12-09 Time 14:27 Sent To  
Notes
2021-12-09 14:28:231ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21110361
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A DETAIL LIST OF ALL CHEMICALS STORED
 IN BUILDING B AND SHOW HOW THIS BUILDING WILL MEET FBC
 M 510 FOR HAZARDOUS EXHAUST SYSTEMS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2022-05-24 Cont ID  
Sent By rmcphers Date 2022-05-24 Time 12:56 Rev Time 0.00
Received By rmcphers Date 2022-05-24 Time 12:56 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2022-03-14 Cont ID  
Sent By rmcphers Date 2022-03-14 Time 14:01 Rev Time 0.00
Received By rmcphers Date 2022-03-14 Time 14:01 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-02-17 Cont ID  
Sent By rmcphers Date 2022-02-17 Time 09:42 Rev Time 0.00
Received By rmcphers Date 2022-02-17 Time 09:42 Sent To  
Notes
2022-02-17 09:48:52NFIP REVIEW - SEE BUILDING PLAN REVIEW
  
 FEMA FLOOD ZONE AE 10.7
 + 2 = 12.7 NAVD
 PROPOSED LOWEST FLOOR = 10.32 (DRY FLOOD PROOFED)
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-03-02 Cont ID  
Sent By ccole Date 2022-03-02 Time 16:30 Rev Time 0.00
Received By ccole Date 2022-03-02 Time 16:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-02-11 Cont ID  
Sent By ccole Date 2022-02-11 Time 13:19 Rev Time 0.00
Received By ccole Date 2022-02-11 Time 13:05 Sent To  
Notes
2022-02-11 13:22:202ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21110361
 2/10/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #1B FROM THE 1ST
 REVIEW WAS NOT ADDRESSED- SEE BELOW.
  
 1) A-401 ROOF DRAINAGE:
 B) PLEASE SEE TABLES 1106.3 & 1106.6 FBC P AND PROVIDE
 THE GPM CAPACITIES OF THE GUTTERS AND DOWNSPOUTS IN
 ORDER TO VERIFY SIZES ARE CODE COMPLIANT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-17 Cont ID  
Sent By ccole Date 2021-12-17 Time 16:26 Rev Time 0.00
Received By ccole Date 2021-12-17 Time 16:17 Sent To  
Notes
2021-12-17 16:26:561ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21110361
 12/17/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A-401 ROOF DRAINAGE:
 A) INDICATE THE RAINFALL RATE USED AS THE BASIS OF THE
 CALCULATIONS- SEC. 1106.1 AND PROVIDE ROOF DRAINAGE
 CALCULATIONS BASED ON THE RATE- SECS. 1106.1- 1106.4
 FBC P.
 B) PLEASE SEE TABLES 1106.3 & 1106.6 FBC P AND PROVIDE
 THE GPM CAPACITIES OF THE GUTTERS AND DOWNSPOUTS IN
 ORDER TO VERIFY SIZES ARE CODE COMPLIANT.
 C) SHOW THE DOWNSPOUT DISCHARGE LOCATIONS. CLARIFY IF
 THE DOWNSPOUTS WILL CONNECT TO AN UNDERGROUND STORM
 DRAIN SYSTEM OR BE DISCHARGED TO GRADE. REFER TO
 COMMENT #1 UNDER PERMIT 21110360 FOR THE MAINTENANCE
 BUILDING AND PROVIDE CIVIL DRAWINGS SHOWING STORM
 DRAINAGE POINTS OF CONNECTIONS (IF APPLICABLE), OR
 REFER TO SEC. 1503.7 FBC B AND INDICATE THE DOWNSPOUTS
 WILL DISCHARGE AT LEAST 1 FOOT AWAY FROM THE BUILDING
 SIDE WALL TO APPROVED LOCATIONS OF DISPOSAL- SEC.
 1101.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status N Date 2022-02-14 Cont ID  
Sent By ccole Date 2022-02-14 Time 14:19 Rev Time 0.00
Received By ccole Date 2022-02-11 Time 14:19 Sent To  
Notes
2022-02-14 14:20:16IRRIGATION PLANS WERE NOT SUBMITTED. A SEPARATE PERMIT
 IS REQUIRED FOR INSTALLATION OF THE SYSTEM.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By rmcphers Date 2021-12-27 Time 15:03 Rev Time 0.00
Received By rmcphers Date 2021-12-27 Time 15:03 Sent To  
Notes
2021-12-27 15:04:16METAL BUILDING - NO ROOFING SYSTEM

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-06-23 Cont ID  
Sent By rmcphers Date 2022-06-23 Time 12:47 Rev Time 0.00
Received By rmcphers Date 2022-06-23 Time 12:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-05-24 Cont ID  
Sent By rmcphers Date 2022-05-24 Time 13:01 Rev Time 0.00
Received By rmcphers Date 2022-05-24 Time 13:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-03-14 Cont ID  
Sent By rmcphers Date 2022-03-14 Time 14:07 Rev Time 0.00
Received By rmcphers Date 2022-03-14 Time 14:07 Sent To  
Notes
2022-03-14 14:07:37SIGNATURE REVIEW
  
 CORRECTIONS NEEDED-
  
 1) ALL CIVIL DRAWINGS AND THE ELEVATION CERTIFICATE -
 DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-02-17 Cont ID  
Sent By rmcphers Date 2022-02-17 Time 09:42 Rev Time 0.00
Received By rmcphers Date 2022-02-17 Time 09:41 Sent To  
Notes
2022-02-17 09:42:33SIGNATURE REVIEW
  
 CORRECTIONS NEEDED-
  
 1) DRAWINGS SP-1, SP-4, ALL CIVIL DRAWINGS AND METAL
 BUILDING DRAWING F2 OF 2 - DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By rmcphers Date 2021-12-27 Time 15:04 Rev Time 0.00
Received By rmcphers Date 2021-12-27 Time 15:04 Sent To  
Notes
2021-12-27 15:08:27SIGNATURE REVIEW
  
 CORRECTIONS NEEDED-
  
 1) METAL BUILDING DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2022-03-08 Cont ID  
Sent By jroach Date 2022-03-08 Time 14:11 Rev Time 0.00
Received By jroach Date 2022-03-08 Time 14:11 Sent To  
Notes
2022-03-08 14:12:13THE SCOPE OF THIS PERMIT REVIEW IS LIMITED TO THE
 FERTILIZER STORAGE BUILDING ONLY.
  
 THE WPB GOLF PARK DEVELOPMENT SHALL BE SUBJECT TO ALL
 DEVELOPMENT ORDER CONDITIONS, AS OUTLINED IN FORMAL
 SITE PLAN REVIEW (FSPR) CASE NO. 21-02, AND AS MAY BE
 AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY FSPR
 CASE NO. 21-02, AS AMENDED, SHALL BE ADDRESSED WITHIN
 THE APPROPRIATE SPECIFIED TIMEFRAMES.
 _______________________________________________________
 _____________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-02-18 Cont ID  
Sent By jroach Date 2022-02-18 Time 14:55 Rev Time 0.00
Received By jroach Date 2022-02-18 Time 14:55 Sent To  
Notes
2022-02-18 15:39:29ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 02.18.2022
 PERMIT NO.: 21110361
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ SATISFIED ] - A SITE PLAN SHALL BE PROVIDED
 SHOWING THE LOCATION OF THE PROPOSED BUILDING, ETC. THE
 SITE PLAN SUBMITTED SHALL MATCH THAT WHICH HAS BEEN
 SUBMITTED AS PART OF THE FORMAL SITE PLAN REVIEW
 PROCESS. THE APPROVED FSPR PLANS SHOULD BE UTILIZED FOR
 ALL BUILDING PERMIT SUBMITTALS. MODIFICATIONS TO THE
 APPROVED PLAN CAN BE MADE THROUGH THE SITE PLAN
 AMENDMENT PROCESS.
  
 2. [ SATISFIED ] - SURVEY SHALL BE PROVIDED.
  
 3. [ NOT SATISFIED ] - PRIOR TO THE ISSUANCE OF A
 PERMIT FOR THE MAINTENANCE FACILITY, EASEMENT CONSENT
 SHALL BE OBTAINED FOR ALL IMPROVEMENTS SHOWN WITHIN THE
 SOUTH FLORIDA WATER MANAGEMENT DISTRICT ACCESS
 EASEMENT, AS RECORDED IN ORB 20087 / PG 1561 OF THE
 PUBLIC RECORDS OF PALM BEACH COUNTY.
  
 3.1 [ NEW COMMENT ] - PORTIONS OF MAINTENANCE FACILITY
 IMPROVEMENTS EXTEND INTO THE EASEMENT RECORDED IN ORB
 20087 / PG 1561 AND ORB 20087 / PG 1569 AND THEREFORE
 DO REQUIRE EASEMENT CONSENT. PLEASE REFER TO THE SITE
 PLAN.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-14 Cont ID  
Sent By jroach Date 2022-01-14 Time 09:43 Rev Time 0.00
Received By jroach Date 2022-01-14 Time 09:43 Sent To  
Notes
2022-01-14 09:43:50ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 01.14.2022
 PERMIT NO.: 21110361
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. A SITE PLAN SHALL BE PROVIDED SHOWING THE LOCATION
 OF THE PROPOSED BUILDING, ETC. THE SITE PLAN SUBMITTED
 SHALL MATCH THAT WHICH HAS BEEN SUBMITTED AS PART OF
 THE FORMAL SITE PLAN REVIEW PROCESS. THE APPROVED FSPR
 PLANS SHOULD BE UTILIZED FOR ALL BUILDING PERMIT
 SUBMITTALS. MODIFICATIONS TO THE APPROVED PLAN CAN BE
 MADE THROUGH THE SITE PLAN AMENDMENT PROCESS.
  
 2. SURVEY SHALL BE PROVIDED.
  
 3. PRIOR TO THE ISSUANCE OF A PERMIT FOR THE
 MAINTENANCE FACILITY, EASEMENT CONSENT SHALL BE
 OBTAINED FOR ALL IMPROVEMENTS SHOWN WITHIN THE SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT ACCESS EASEMENT, AS
 RECORDED IN ORB 20087 / PG 1561 OF THE PUBLIC RECORDS
 OF PALM BEACH COUNTY.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  