Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-25 Cont ID  
Sent By pvalenti Date 2022-03-25 Time 10:09 Rev Time 0.00
Received By pvalenti Date 2022-03-25 Time 10:02 Sent To  
Notes
2022-03-25 10:31:06PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 ALL DOOR ASSEMBLY & FIRE RATING APPROVED DOCUMENTS MUST
 BE ON-SITE AT TIME OF INSPECTIONS.
  
 NOTE: ALL FIRE REVIEW STOP COMMENTS MUST BE APPROVED BY
 FIRE PLAN REVIEWER PRIOR TO PERMIT ISSUANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-25 Cont ID  
Sent By pvalenti Date 2022-02-25 Time 14:24 Rev Time 0.00
Received By pvalenti Date 2022-02-25 Time 13:05 Sent To  
Notes
2022-02-25 14:29:45PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 WPB AMENDMENTS TO FBC B 107.2.1, EACH SHEET OF THE
 SUBMITTED DOCUMENTS NEED TO BE IDENTIFIED & SIGNED BY
 PERSON RESPONSIBLE FOR SUBMITTED INFORMATION SUCH AS
 THE CONTRACTOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-03-08 Cont ID  
Sent By pleduc Date 2022-03-08 Time   Rev Time 0.00
Received By pleduc Date 2022-03-08 Time 09:31 Sent To  
Notes
2022-03-08 09:58:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED DOOR SCHEDULE DOES NOT INDICATE IF THE
 DOORS BEING REPLACED ARE REQUIRED TO BE FIRE RATED.
  
 THOUGH THERE IS A HAND WRITTEN NOTE FOR DOORS REQURING
 REPAIR TO BE BE RE-CERTIFIED FOR FIRE DOORS, THERE IS
 NO INDICATION OF WHICH DOORS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FIRE RATING
 OF THE ORIGINAL DOORS AND ENSURE THOSE THAT ARE BEING
 REPLACED WILL MATCH.
  
  
  
 1A) THE DOOR SCHEDULE, UNDER THE COMMENT SECTION,
 INDICATES "REPLACE DOOR" AND NUMEROUS OTHER DOORS HAVE
 NO COMMENT.
  
 FIRE RATED DOOR OPENINGS ARE INSTALLED AS AN ASSEMBLY
 THAT INCLUDES THE FRAME AND HINGES.
  
 REPLACING A DOOR MAY NOT BE APPLICABLE TO MANTAINING
 THE REQUIRED FIRE RATING OF THAT DOOR ASSEMBLY.
  
 PLEASE DEFINE AND PROVIDES DETAILS OF WHY THERE IS NO
 COMMENT ON MOST DOORS AND OTHER DOORS HAVE "REPLACE
 DOOR".
  
 IF THE DOOR IS NOT INVLOVED IN THE PROPOSED PROJECT IT
 SHOULD NOT BE ON THE DOOR SCHEDULE OR THE COMMENT
 SHOULD INDICATE SUCH.
  
  
 1B) THE DOOR SCHEDULE INDICATES A NUMERIC DESCRIPTION
 HOWEVER, IT DOES NOT INDICATE WHAT IS EXISTING, NEW OR
 AS PER 1A IF IS
 NOT INVLOVED IN THE PROPOSED PROJECT SHOULD NOT BE ON
 THE DOOR SCHEDUE,
  
 FOR THE OFFICIAL RECORD PLEASE CLARIFY WHAT DOOR
 HARDWARE IS EXISTING TO BE PUT ON NEW DOOR, NEW ON
 EXISTING DOOR, NEW ON NEW DOOR, ETC.
 AND ENSURE THAT THE HARDWARE DOES NOT COMPROMISE THE
 REQUIRED FIRE RATING.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-02-28 Cont ID  
Sent By pleduc Date 2022-02-28 Time   Rev Time 0.00
Received By pleduc Date 2022-02-28 Time 11:25 Sent To  
Notes
2022-02-28 11:31:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PLANS ARE BLURRY AND UNREADABLE AND
 COULD NOT BE REVIEWED.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE CLEAR AND
 READABLE PLAN SHEETS.
  
  
 2) THERE IS NO DOOR SCHEDULE ON THE SUBMITTED PLANS
 THAT CAN CLEARLY INDICATE SIZE, LOCATION, FIRE RATING
 AND DOOR HARDWARE.
  
 PLEASE PROVIDE A DOOR SCHEDULE INCLUDING THE SPEEFICS
 OF EACH DOOR.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-25 Cont ID  
Sent By pvalenti Date 2022-03-25 Time 10:09 Rev Time 0.00
Received By pvalenti Date 2022-03-07 Time 14:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-28 Cont ID  
Sent By pvalenti Date 2022-02-28 Time 13:34 Rev Time 0.00
Received By pvalenti Date 2022-01-28 Time 11:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-02-25 Cont ID  
Sent By pvalenti Date 2022-02-25 Time 14:30 Rev Time 0.00
Received By pvalenti Date 2022-02-25 Time 13:05 Sent To  
Notes
***NONE***