Plan Review Details - Permit 21110264
Plan Review Stops For Permit 21110264
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-11-05 Cont ID  
Sent By jleahy Date 2021-11-05 Time 10:57 Rev Time 0.00
Received By jleahy Date 2021-11-05 Time 10:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-12-01 Cont ID  
Sent By pleduc Date 2021-12-01 Time   Rev Time 0.00
Received By pleduc Date 2021-12-01 Time 14:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-11-29 Cont ID  
Sent By pleduc Date 2021-11-29 Time   Rev Time 0.00
Received By pleduc Date 2021-11-29 Time 15:59 Sent To  
Notes
2021-11-29 16:02:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION WHERE THE GENERATORS WILL BE
 PLACED/OPERATED ON THE SITE PLAN.
  
 PLEASE INDICATE THE LOCATIONS AND DIMENSIONS FROM ALL
 BUILDINGS AND PUBLIC WALKWAYS/SIDEWALKS/ROADS/STREETS.
  
 1A) PLEASE PROVIDE HOW POWER CORDS WILL BE PROTECTED
 FROM PUBLIC WALKWAYS/SIDEWALKS/VEHICLE TRAFFIC IF
 APPLICABLE.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-01 Cont ID  
Sent By amcgrego Date 2021-12-01 Time 15:30 Rev Time 0.00
Received By amcgrego Date 2021-11-30 Time 17:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-30 Cont ID  
Sent By ppetty Date 2021-11-30 Time 08:46 Rev Time 0.00
Received By ppetty Date 2021-11-05 Time 09:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-01 Cont ID  
Sent By ppetty Date 2021-12-01 Time 07:45 Rev Time 0.00
Received By ppetty Date 2021-12-01 Time 07:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-30 Cont ID  
Sent By ppetty Date 2021-11-30 Time 08:44 Rev Time 0.00
Received By ppetty Date 2021-11-30 Time 08:44 Sent To  
Notes
2021-11-30 08:45:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A
 DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-11-29 Cont ID  
Sent By ajones Date 2021-11-29 Time 13:51 Rev Time 0.00
Received By ajones Date 2021-11-29 Time 13:51 Sent To  
Notes
***NONE***