Plan Review Details - Permit 21110247
Plan Review Stops For Permit 21110247
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-07-29 Cont ID  
Sent By cthroop Date 2022-07-29 Time 06:18 Rev Time 0.00
Received By cthroop Date 2022-07-28 Time 15:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-24 Cont ID  
Sent By pvalenti Date 2022-05-24 Time 12:58 Rev Time 0.00
Received By pvalenti Date 2022-05-24 Time 09:39 Sent To  
Notes
2022-05-24 13:13:14PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE PROVIDE A DETAIL OF THE LOAD
 BEARING WALL THAT WILL CARRY THE NEW TIE AND RAKE BEAMS
 AS REFERENCE DETAIL (4/S-3) INDICATES.
  
 NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE ACCESS.
 STRUCTURE. SUBMIT A PERMIT APPLICATION TO
 [email protected]
 PLANS SHALL REMAIN UNDER PERMIT 21110247. PERMIT SHALL
 TRAVEL TOGETHER.
  
 NOTE: A ROOFING PERMIT IS REQUIRED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-05 Cont ID  
Sent By cthroop Date 2022-01-05 Time 08:43 Rev Time 0.00
Received By cthroop Date 2022-01-05 Time 05:54 Sent To  
Notes
2022-01-05 09:12:09BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: VALUE HAS BEEN INCREASED TO $66,616.00 PER THE
 ICC BLDG. VA;LUATION DATA.
  
 NOTICE: A SEPERATE PERMIT IS REQUIRED FOR THE ACCESS.
 STRUCTURE. SUBMIT A PERMIT APPLICATION TO
 [email protected]
 PLANS SHALL REMAIN UNDER PERMIT 21110247. PERMITS SHALL
 TRAVEL TOGETHER.
  
 NOTICE: PROVISO ON PG S-1.00: A SEPERATE ROOFING PERMIT
 IS REQUIRED.
  
 1. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
  
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 2. STATE R-VALUE AND TYPE OF CEILING AND WALL
 INSULATION ON PLANS. IF SPRAY FOAM INSULATION IS USED,
 PROVIDE THE ICC-ES REPORT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. REFERENCE PLAN PAGE S1.00 FOR THE FOLLOWING COMMENT:
 CUT SECTIONS REFERENCE PG. S-1. CUT SECTION DETAILS ARE
 LOCATED ON PG. S3.00. PLEASE CORRECT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. REFERENCE DETAIL 4/S-3 FPR THE FOLLOWING COMMENT:
 PROVIDE A DETAIL OF THE LOAD BEARING WALL THAT WILL
 CARRY THE NEW TIE BEAM AND RAKE BEAM.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-06-30 Cont ID  
Sent By fgiaquin Date 2022-06-30 Time 19:08 Rev Time 0.00
Received By fgiaquin Date 2022-06-30 Time 18:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-20 Cont ID  
Sent By jleahy Date 2022-04-20 Time 08:37 Rev Time 0.00
Received By jleahy Date 2022-04-19 Time 16:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-12-17 Cont ID  
Sent By jleahy Date 2021-12-17 Time 16:38 Rev Time 0.00
Received By jleahy Date 2021-12-17 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-29 Cont ID  
Sent By lmarchan Date 2022-07-29 Time 10:38 Rev Time 0.00
Received By lmarchan Date 2022-06-13 Time 15:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-24 Cont ID  
Sent By pvalenti Date 2022-05-24 Time 13:56 Rev Time 0.00
Received By pvalenti Date 2022-04-01 Time 08:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-05 Cont ID  
Sent By cthroop Date 2022-01-05 Time 09:12 Rev Time 0.00
Received By cthroop Date 2021-11-09 Time 09:06 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-08-12 Cont ID  
Sent By lmarchan Date 2022-08-12 Time 11:52 Rev Time 0.00
Received By lmarchan Date 2022-07-29 Time 10:38 Sent To  
Notes
2022-07-30 09:07:52MU-2022-034804-0000 $1,945.04 PAID AO
2022-07-29 10:38:187/29/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-01-05 Cont ID  
Sent By cthroop Date 2022-01-05 Time 08:27 Rev Time 0.00
Received By cthroop Date 2022-01-05 Time 08:27 Sent To  
Notes
2022-01-05 08:27:56IMPACT FEE QUESTIONNAIRE
  
 PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-06-21 Cont ID  
Sent By medwards Date 2022-06-21 Time 15:12 Rev Time 0.00
Received By medwards Date 2022-06-21 Time 15:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-04-11 Cont ID  
Sent By medwards Date 2022-04-11 Time 12:56 Rev Time 0.00
Received By medwards Date 2022-04-11 Time 12:56 Sent To  
Notes
2022-04-11 13:03:42PLEASE SEE PREVIOUS COMMENTS BELOW:
  
  
 PLEASE PROVIDE A MECHANICAL DRAWING THAT SHOWS THE DOOR
 LOCATIONS TO THE ROOMS, THE BATH EXHAUST FANS-
 INCLUDING THE CFM'S OF EXHAUST, PLEASE ALSO SHOW THE
 CONDENSING UNIT TIE DOWN DETAILS. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By medwards Date 2021-11-18 Time 06:08 Rev Time 0.00
Received By medwards Date 2021-11-18 Time 06:08 Sent To  
Notes
2021-11-18 06:13:42PLEASE PROVIDE A MECHANICAL DRAWING THAT SHOWS THE DOOR
 LOCATIONS TO THE ROOMS, THE BATH EXHAUST FANS-
 INCLUDING THE CFM'S OF EXHAUST, PLEASE ALSO SHOW THE
 CONDENSING UNIT TIE DOWN DETAILS. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-04-04 Cont ID  
Sent By rwbrown Date 2022-04-04 Time 15:58 Rev Time 0.00
Received By rwbrown Date 2022-04-04 Time 15:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-11-28 Cont ID  
Sent By abelisle Date 2021-11-28 Time 15:59 Rev Time 0.00
Received By abelisle Date 2021-11-28 Time 15:11 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-07-15 Cont ID  
Sent By rgathrig Date 2022-07-15 Time 17:30 Rev Time 0.00
Received By rgathrig Date 2022-07-15 Time 17:30 Sent To  
Notes
2022-07-15 17:31:04PRIVATE PROVIDER INSPECTIONS ONLY APPROVED
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2022-05-24 Cont ID  
Sent By pvalenti Date 2022-05-24 Time 13:54 Rev Time 0.00
Received By pvalenti Date 2022-05-24 Time 09:39 Sent To  
Notes
2022-05-24 13:56:12PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ROOFING REVIEW NOT REQUIRED AS A ROOFING PERMIT IS
 REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-01-05 Cont ID  
Sent By cthroop Date 2022-01-05 Time 08:39 Rev Time 0.00
Received By cthroop Date 2022-01-05 Time 05:54 Sent To  
Notes
2022-01-05 08:40:00PROVISO ON PLAN PAGE S-1.00: A SEPERATE ROOFING PERMIT
 IS REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-07-29 Cont ID  
Sent By cthroop Date 2022-07-29 Time 15:45 Rev Time 0.00
Received By cthroop Date 2022-07-29 Time 15:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-07-29 Cont ID  
Sent By cthroop Date 2022-07-29 Time 06:16 Rev Time 0.00
Received By cthroop Date 2022-07-28 Time 15:55 Sent To  
Notes
2022-07-29 06:18:21SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 3RD REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
 SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-24 Cont ID  
Sent By pvalenti Date 2022-05-24 Time 13:56 Rev Time 0.00
Received By pvalenti Date 2022-05-24 Time 09:39 Sent To  
Notes
2022-04-20 08:40:56ELECTRIC PAGE IS NOT SIGNED JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-05 Cont ID  
Sent By cthroop Date 2022-01-05 Time 08:43 Rev Time 0.00
Received By cthroop Date 2022-01-05 Time 05:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-07 Cont ID  
Sent By afowlkes Date 2022-04-07 Time 16:33 Rev Time 0.00
Received By afowlkes Date 2022-04-07 Time 16:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-11-24 Cont ID  
Sent By awooten Date 2021-11-24 Time   Rev Time  
Received By awooten Date 2021-11-24 Time   Sent To  
Notes
***NONE***