| 2021-12-01 06:59:38 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21110246 |
| | ADD: 2450 PRESIDENTIAL WAY # 1707 |
| | PCN:74-43-43-18-10-000-1707 |
| | CONT: WRIGHT?S IMPACT WINDOW & DOOR LLC |
| | TEL: 561-588-7353 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. DEC.01ST/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. THE WRIGHT?S FLOOR PLAN & OPENING |
| | SCHEDULE NEEDS TO SHOW WHO THE AUTHOR IS OF THE PLAN. |
| | CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR |
| | (QUALIFIER) THAT CREATED / DREW THE SET OF PLANS WILL |
| | NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. |
| | PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE |
| | NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS |
| | DRAWN. |
| | |
| | 2) 2ND REQUEST. DRAWING 1 WRIGHT?S FLOOR PLAN DOES NOT |
| | SHOW THE FLOOR PLAN IN THE OVERALL CURVATURE OF THE |
| | BUILDING, NOR THE UNITS THAT ARE PROJECTED FURTHER OUT |
| | THAN OTHER PORTIONS OF THE WALL LINE. ENGINEERING |
| | EXPRESS SHEET SHOWS FOR COMPLEX BUILDINGS USE CORNER |
| | ZONES IF AT ALL IN QUESTION. WITH THE CURVATURE OF THE |
| | BUILDING AND OFFSET WALL SECTIONS FOR BOTH SIDES OF THE |
| | BUILDING IT WOULD CREATE SMALL VORTEX POCKETS WHERE THE |
| | BALCONIES ARE DROPPED BACK IN FROM THE FRONT OF THE |
| | BUILDING. THIS WILL GREATLY AFFECT THE PRESSURES ON |
| | THESE OPENINGS AND SUBMITTED SCHEDULE. |
| | BUILDING END ZONES (5). THE FLOOR PLAN LAYOUT INDICATES |
| | THE WORK TO BE PERFORMED UNDER THIS PERMIT IS A CORNER |
| | UNIT OF A HIGHRISE BUILDING. THE WIND LOAD CHART UNDER |
| | NOTES STATES WHAT IS CONSIDERED AN END ZONE 10% OF THE |
| | LEAST HORIZONTAL DISTANCE OF THE BUILDING OR 40% OF THE |
| | MRH, BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL |
| | DISTANCE OR 3 FT. THE CONTRACTOR HAS NOT IDENTIFIED |
| | WHAT THE LEAST HORIZONTAL DISTANCE IS FOR THE BUILDING |
| | NOR THE LOCATION OF THE UNIT IN RELATIONSHIP TO THE |
| | BUILDING AND THE INTERCOASTAL WATERWAY. EXAMPLE ONLY. |
| | IF THE BUILDING HEIGHT IS APPROXIMATELY 180 FT. (MRH.) |
| | X 0.40= 72 FEET. THIS WOULD PUT ALL OPENINGS IN WIND |
| | ZONE 5 OR 10% OF THE LEAST HORIZONTAL DISTANCE OF THE |
| | BUILDING, ALSO UNKNOWN. |
| | |
| | 3) THE REVIEW OF THE SUBMITTED PRODUCT APPROVALS CANNOT |
| | OCCUR WITH ALL OF THE UNKNOWNS LISTED IN COMMENT 2. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |