Plan Review Details - Permit 21110245
Plan Review Stops For Permit 21110245
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-02-15 Cont ID  
Sent By jwitmer Date 2022-02-15 Time 14:29 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-01-19 Cont ID  
Sent By jwitmer Date 2022-01-19 Time 11:19 Rev Time 0.00
Received By jwitmer Date 2022-01-19 Time 11:00 Sent To  
Notes
2022-01-19 11:19:06WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21110245
 ADD: 2480 PRESIDENTIAL WAY # 1104
 CONT: WRIGHTS IMPACT WINDOW & DOOR LLC
 TEL: 561-588-7353
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. JAN. 19TH/ 2022
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) PLEASE REVIEW THE MIAMI-DADE NOA 21-0728.02 SLIDING
 GLASS DOORS TECHNICAL SHEET 5 OF 23. THE SUBMITTED NOA
 IS SHOWN AS REVISION C. PLEASE GO TO THE MIAMI-DADE
 WEBSITE, THERE IS A NEWER SHEET 5 OF 23 REVISION D
 WHICH DOES HAVE THE SILL HEIGHTS ADDED AND ASSOCIATED
 POSITIVE PRESSURES. PLEASE IDENTIFY WHICH SILL HEIGHTS
 ARE GOING TO BE USED FOR EACH SLIDING DOOR SINCE THE 2
 ? INCH SILL WILL NOT WORK ON ALL OF THE SLIDING GLASS
 DOORS.
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-12-13 Cont ID  
Sent By pvalenti Date 2021-12-13 Time 16:11 Rev Time 0.00
Received By pvalenti Date 2021-12-13 Time 14:17 Sent To  
Notes
2021-12-13 16:33:22PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, ITEM # 2 OF THE LAST REVIEW STILL LEAVES
 SOME UNANSWERED QUESTIONS AS PER COMMENTS BELOW:
  
 A.) SLIDING GLASS DOOR AT OPENING #3 APPEARS TO BE IN A
 ZONE 5 AREA AS IT IS CLEARLY CLOSE TO THE EDGE OF THE
 WALL.
 B.) PLEASE CONFIRM THAT THE CURVATURE OF THE BUILDING
 HAS BEEN TAKEN INTO CONSIDERATION IN CALCULATING THE
 DESIGN WIND PRESSURES AND THAT ALL WINDOW/DOOR
 LOCATIONS ARE NOT IN ZONE 5.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-23 Cont ID  
Sent By jwitmer Date 2021-11-23 Time 16:46 Rev Time 0.00
Received By jwitmer Date 2021-11-23 Time 16:16 Sent To  
Notes
2021-11-23 16:46:53WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21110245
 ADD: 2480 PRESIDENTIAL WAY # 1104
 CONT: WRIGHT?S IMPACT WINDOW & DOOR LLC
 TEL: 561-588-7353
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 23RD/ 2021
 ACTION: DENIED
  
 1) THE WRIGHT?S FLOOR PLAN & OPENING SCHEDULE NEEDS TO
 SHOW WHO THE AUTHOR IS OF THE PLAN. CERTIFICATION BY
 CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  
 2) DRAWING 1 WRIGHT?S FLOOR PLAN DOES NOT SHOW THE
 FLOOR PLAN IN THE OVER ALL CURVATURE OF THE BUILDING,
 NOR THE UNITS THAT ARE PROJECTED FURTHER OUT THAN OTHER
 PORTIONS OF THE WALL LINE. OPENING # 3 IS IN ZONE 5,
 OPENINGS 1, 4, 5 & 6 ARE IN QUESTION ENGINEERING
 EXPRESS SHEET SHOWS FOR COMPLEX BUILDINGS USE CORNER
 ZONES IF AT ALL IN QUESTION. THIS WILL GREATLY AFFECT
 THE PRESSURES ON THESE OPENINGS AND SUBMITTED SCHEDULE.
 BUILDING END ZONES (5). THE FLOOR PLAN LAYOUT INDICATES
 THE WORK TO BE PERFORMED UNDER THIS PERMIT IS A CORNER
 UNIT OF A HIGHRISE BUILDING. THE WIND LOAD CHART UNDER
 NOTES STATES WHAT IS CONSIDERED AN END ZONE 10% OF THE
 LEAST HORIZONTAL DISTANCE OF THE BUILDING OR 40% OF THE
 MRH, BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL
 DISTANCE OR 3 FT. THE CONTRACTOR HAS NOT IDENTIFIED
 WHAT THE LEAST HORIZONTAL DISTANCE IS FOR THE BUILDING
 NOR THE LOCATION OF THE UNIT IN RELATIONSHIP TO THE
 BUILDING AND THE INTERCOASTAL WATERWAY. EXAMPLE ONLY.
 IF THE BUILDING HEIGHT IS APPROXIMATELY 180 FT. (MRH.)
 X 0.40= 72 FEET. THIS WOULD PUT ALL OPENINGS IN WIND
 ZONE 5 OR 10% OF THE LEAST HORIZONTAL DISTANCE OF THE
 BUILDING, ALSO UNKNOWN.
  
 3) THE REVIEW OF THE SUBMITTED PRODUCT APPROVALS CAN
 NOT OCCUR WITH ALL OF THE UNKNOWNS LISTED IN COMMENT 2.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-02-15 Cont ID  
Sent By jwitmer Date 2022-02-15 Time 14:29 Rev Time 0.00
Received By jwitmer Date 2022-02-09 Time 07:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-19 Cont ID  
Sent By jwitmer Date 2022-01-19 Time 11:19 Rev Time 0.00
Received By jwitmer Date 2022-01-11 Time 12:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-13 Cont ID  
Sent By pvalenti Date 2021-12-13 Time 16:33 Rev Time 0.00
Received By pvalenti Date 2021-12-07 Time 12:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-23 Cont ID  
Sent By jwitmer Date 2021-11-23 Time 16:47 Rev Time 0.00
Received By jwitmer Date 2021-11-19 Time 08:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-13 Cont ID  
Sent By pvalenti Date 2021-12-13 Time 16:33 Rev Time 0.00
Received By pvalenti Date 2021-12-13 Time 14:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-01-19 Cont ID  
Sent By jwitmer Date 2022-01-19 Time 11:19 Rev Time 0.00
Received By jwitmer Date 2021-11-23 Time 16:16 Sent To  
Notes
2021-11-23 16:46:17THE WRIGHT?S FLOOR PLAN & OPENING SCHEDULE NEEDS TO
 SHOW WHO THE AUTHOR IS OF THE PLAN. CERTIFICATION BY
 CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.