Plan Review Details - Permit 21110234
Plan Review Stops For Permit 21110234
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-01-20 Cont ID  
Sent By rmcdouga Date 2022-01-20 Time 10:21 Rev Time 0.00
Received By rmcdouga Date 2022-01-20 Time 10:21 Sent To  
Notes
2022-01-20 10:35:01PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [NOT ADDRESSED. THE MANUFACTURE'S AND OR SHOP
 DRAWINGS ARE REQUIRED IN ORDER TO DETERMINE IF THE
 GENERATORS WILL COMPLY WITH THE FLORIDA BUILDING CODE
 FOR WINDLOADING, SOUND AND OTHER REQUIREMENTS. THE
 DETAILS OF HOW THE GENERATORS WILL BE ATTACHED TO THE
 EXISTING SLABS IS ALSO REQUIRED. THIS INFORMATION IS
 REQUIRED BEFORE THE PERMIT CAN BE ISSUED AND CAN NOT BE
 DEFERRED.] SUBMIT SHOP DRAWINGS THAT DETAIL EQUIPMENT
 ASSEMBLIES AND INDICATE DIMENSIONS, WEIGHTS, LOADS,
 REQUIRED CLEARANCES, METHOD OF FIELD ASSEMBLY,
 COMPONENTS, AND LOCATION AND SIZE OF EACH FIELD
 CONNECTION.
 A) DIMENSIONED OUTLINE PLAN AND ELEVATION DRAWINGS OF
 ENGINE-GENERATOR SET AND OTHER COMPONENTS SPECIFIED.
 B) VIBRATION ISOLATION BASE DETAILS: DETAIL
 FABRICATION, INCLUDING ANCHORAGES AND ATTACHMENTS TO
 STRUCTURE AND TO SUPPORTED EQUIPMENT. INCLUDE WEIGHTS.
 SHOW THAT ANCHORING WILL RESIST WINDLOADS ON EQUIPMENT.
  
 2) [THE LETTER RESPONCE LETTER STATES THAT ALL OF THE
 GENERATORS ARE LOCATED MORE THAN 10 FEET FROM THE
 BUILDINGS. THIS NEEDS TO BE STATED ON THE SITE PLAN OR
 SURVEY.] THE GENERATOR EXHAUST IS REQUIRED TO BE AT
 LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING.
 R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-14 Cont ID  
Sent By rmcdouga Date 2021-12-14 Time 08:05 Rev Time 0.00
Received By rmcdouga Date 2021-12-14 Time 08:05 Sent To  
Notes
2021-12-14 08:05:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT SHOP DRAWINGS THAT DETAIL EQUIPMENT
 ASSEMBLIES AND INDICATE DIMENSIONS, WEIGHTS, LOADS,
 REQUIRED CLEARANCES, METHOD OF FIELD ASSEMBLY,
 COMPONENTS, AND LOCATION AND SIZE OF EACH FIELD
 CONNECTION.
 A) DIMENSIONED OUTLINE PLAN AND ELEVATION DRAWINGS OF
 ENGINE-GENERATOR SET AND OTHER COMPONENTS SPECIFIED.
 B) VIBRATION ISOLATION BASE DETAILS: DETAIL
 FABRICATION, INCLUDING ANCHORAGES AND ATTACHMENTS TO
 STRUCTURE AND TO SUPPORTED EQUIPMENT. INCLUDE WEIGHTS.
 SHOW THAT ANCHORING WILL RESIST WINDLOADS ON EQUIPMENT.
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-01-15 Cont ID  
Sent By jleahy Date 2022-01-15 Time 09:34 Rev Time 0.00
Received By jleahy Date 2022-01-15 Time 09:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-20 Cont ID  
Sent By jleahy Date 2021-12-20 Time 12:55 Rev Time 0.00
Received By jleahy Date 2021-12-20 Time 11:02 Sent To  
Notes
2021-12-20 12:57:23ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE PROVIDE CUT SHEETS FOR THE GENERATORS, AND
 TRANSFER SWITCHES. ARE THE ALL THE SAME SIZE? 110.3
  
 WHAT LOADS ARE BEING FED BY GENERATOR, PLEASE PROVIDE A
 PANEL SCHEDUULE. 215.5

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-17 Cont ID  
Sent By pleduc Date 2021-12-17 Time   Rev Time 0.00
Received By pleduc Date 2021-12-17 Time 10:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-01-20 Cont ID  
Sent By ccole Date 2021-12-21 Time 13:47 Rev Time 0.00
Received By ccole Date 2021-12-21 Time 10:59 Sent To  
Notes
2021-12-21 13:49:161ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21110234
 12/21/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR BEARING THE REVIEW AND APPROVAL STAMP OF THE
 DESIGN PROFESSIONAL OF RECORD- SECS. 107.2.1 & 107.3.4
 WPB. THE SPECS SHALL INDICATE THE GENERATOR IS UL 2200
 APPROVED- SEC. 616.1 FBC FG.
  
 2) GAS PIPING:
 A) PROVIDE A GAS PIPING CONNECTION DETAIL OR ISOMETRIC
 DRAWING SHOWING THE TYPE AND SIZE OF EXISTING GAS
 PIPING, LOCATION OF NEW OR EXISTING REGULATOR, SHUTOFF
 VALVE, PIPE UNIONS, AND NEW FLEX CONNECTOR TO THE
 GENERATOR-107.3.5.1.3 WPB. SUBMIT SPECS FOR THE FLEX
 CONNECTOR REVIEWED AND APPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD- SECS. 411.1.3, 411.1.5, & 616.2
 FBC FG.
  
 B) PROVIDE THE SYSTEM AND INLET PRESSURE AT THE
 REGULATOR, AND OUTPUT PRESSURE AT THE GENERATOR. SUBMIT
 SPECS FOR THE REGULATOR REVIEWED AND APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD- SEC. 410.2 FBC FG.
  
 C) VERIFY THE EXISTING GAS PIPING SERVING THE GENERATOR
 IS CONNECTED ON THE SUPPLY SIDE (UPSTREAM) OF THE MAIN
 GAS SHUTOFF VALVE AND MARKED AS SUPPLYING AN EMERGENCY
 GENERATOR- SEC. 7.9.7 NFPA 110.
  
 D) VERIFY THE BUILDING'S MAIN GAS SHUTOFF VALVE IS
 MARKED OR TAGGED TO INDICATE THE EXISTENCE OF THE
 SEPARATE EPS (GENERATOR) SHUTOFF VALVE- SEC. 7.9.8 NFPA
 110.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-20 Cont ID  
Sent By lmarchan Date 2022-01-20 Time 12:53 Rev Time 0.00
Received By lmarchan Date 2022-01-12 Time 08:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-12-21 Time   Rev Time 0.00
Received By cdecoeur Date 2021-11-09 Time 08:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-12-21 Cont ID  
Sent By ccole Date 2021-12-21 Time 13:49 Rev Time 0.00
Received By ccole Date 2021-12-21 Time 10:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-01-20 Cont ID  
Sent By rmcdouga Date 2022-01-20 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2022-01-20 Time 10:36 Sent To  
Notes
2022-01-20 10:44:47THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED PLANS. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & 61G1 OR FS 471 & 61G15
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-12-21 Cont ID  
Sent By ccole Date 2021-12-21 Time 14:01 Rev Time 0.00
Received By ccole Date 2021-12-21 Time 10:59 Sent To  
Notes
2021-12-21 14:06:03SIGNATURE REVIEW
 PERMIT-21110234
 12/21/2021
  
 1) THE ELECTRIC PLANS SHALL ARE NOT DIGITALLY SIGNED
 AND SEALED BY THE ENGINEER OF RECORD- FL. STATUTE
 471.025, AND SECTION 61G15-23.005 FAC.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-01-20 Cont ID  
Sent By llouie Date 2022-01-20 Time   Rev Time 0.00
Received By llouie Date 2022-01-20 Time   Sent To  
Notes
2022-01-20 12:11:37ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) EACH GENERATOR SHALL BE SCREENED. SCREENING
 ADEQUACY WILL BE DETERMINED AT TIME OF INSPECTION.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-11-19 Cont ID  
Sent By llouie Date 2021-11-19 Time   Rev Time  
Received By llouie Date 2021-11-19 Time   Sent To  
Notes
2021-11-19 14:28:54** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY
 REQUIRED.
  
 2.) HIGHLIGHT THE AREA IN THE SITE PLAN WHERE THE
 GENERATOR(S) ARE TO BE CHANGED OUT.
  
 3.) HOW TALL ARE THE PROPOSED GENERATOR(S)? ADDITIONAL
 SCREENING MAY BE REQUIRED.
  
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: MF32
  