Plan Review Details - Permit 21110233
Plan Review Stops For Permit 21110233
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-01-11 Cont ID  
Sent By lmarchan Date 2022-01-11 Time 12:19 Rev Time 0.00
Received By lmarchan Date 2022-01-11 Time 12:19 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-01-04 Cont ID  
Sent By jwitmer Date 2022-01-04 Time 07:45 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-01-04 07:45:53COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-12-01 Cont ID  
Sent By jwitmer Date 2021-12-01 Time 15:24 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-12-01 15:24:01COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-02-01 Cont ID  
Sent By jwitmer Date 2022-02-01 Time 12:20 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-01-04 Cont ID  
Sent By jwitmer Date 2022-01-04 Time 07:43 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-01 Cont ID  
Sent By jwitmer Date 2021-12-01 Time 15:24 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-12-01 15:23:41WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21110233
 ADD: 6901 OKEECHOBEE BLVD. # E2
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL: [email protected] LAURIE MCEACHERN
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC. 01/2021
 ACTION: DENIED
  
 1) THE LIFE SAFETY PLAN GIVES IN THE UPPER LEFT HAND OF
 THE SHEET DESIGN OCCUPANT LOAD OF 47
 AND A TOTAL SQUARE FOOTAGE OF 1691 SQ. FT. THE SAME
 PAGE UNDER THE HEADING OF TENANT SPACE DATA
 THE TENANT IMPROVEMENT AREA IS LISTED AT 2,257 SQ. FT.
 DISCREPANCY IN SQUARE FOOTAGE & OCCUPANCY.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET S100 SHOWS IN DETAIL #3-7 ADDITIONAL STEEL
 BRACING AND L ANGLE (WELDING REQUIRED) FOR INFILL FOR
 NEW RTU UNIT. WELDED OR BOLTED CONNECTIONS. THIS
 BUILDING CONTAINS EITHER BOLTED AND OR WELDED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-02-04 Cont ID  
Sent By jleahy Date 2022-02-04 Time 15:31 Rev Time 0.00
Received By jleahy Date 2022-02-04 Time 15:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-01-22 Cont ID  
Sent By fgiaquin Date 2022-01-22 Time 18:21 Rev Time 0.00
Received By fgiaquin Date 2022-01-22 Time 15:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-12-17 Cont ID  
Sent By jleahy Date 2021-12-17 Time 16:12 Rev Time 0.00
Received By jleahy Date 2021-12-17 Time 16:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2021-11-17 Time   Rev Time 0.00
Received By bdolan Date 2021-11-15 Time 14:10 Sent To  
Notes
2021-11-15 14:14:55PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-02-01 Cont ID  
Sent By ccole Date 2022-02-01 Time 17:02 Rev Time 0.00
Received By ccole Date 2022-02-01 Time 15:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-01-05 Cont ID  
Sent By ccole Date 2022-01-05 Time 12:25 Rev Time 0.00
Received By ccole Date 2022-01-05 Time 07:30 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-11-29 Cont ID  
Sent By ccole Date 2021-11-29 Time 15:27 Rev Time 0.00
Received By ccole Date 2021-11-29 Time 14:52 Sent To  
Notes
2021-11-29 15:29:001ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21110233
 11/29/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P120: PROVIDE A COMPLETE GAS RISER DRAWING
 THAT INCLUDES ALL NEW AND EXISTING GAS PIPING SERVING
 APPLIANCES AND EQUIPMENT- SECTIONS 401.3 & 401.4 FBC
 FG. REFER TO FBC CHAPTER 4 FUEL FBC- THE RISER SHALL
 INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) P120: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR
 THE WATER HEATER INDICATING THE MAKE AND MODEL, BTU
 CAPACITY, INPUT PRESSURE, AND EFFICIENCY RATING-
 SECTION 624.1 FBC FG, AND TABLE C404.1 FBC EC.
  
 3) P120: SHOW THE WATER HEATER DIRECT VENT COMBUSTION
 AIR INTAKE DUCT AND VENT RUNS AND TERMINATION
 LOCATIONS- SECTIONS 503.2.3, 503.6.5 & 624.1 FBC FG.
  
 4) P120: PROVIDE A ULL TESTED AND APPROVED FIRESTOPPING
 ASSEMBLY DETAIL FOR SEALING THE ANNUAL SPACE AROUND THE
 GAS PIPE WALL AND ROOF PENETRATIONS- SECTION 714.4.1.2
 FBC B.
  
 5) P120: PROVIDE A PIPE SUPPORT DETAIL FOR THE GAS
 PIPING ON THE ROOF- SECTION 404.9 FBC FG.
  
 6) P120: PLEASE REMOVE THE IFGC 2012 REFERENCE FROM THE
 PLAN NOTE. THE PROPOSED GAS INSTALLATIONS SHALL BE IN
 COMPLIANCE WITH THE FLORIDA FUEL GAS CODE 7TH EDITION
 2020.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-04 Cont ID  
Sent By jleahy Date 2022-02-04 Time 15:38 Rev Time 0.00
Received By jleahy Date 2022-01-27 Time 16:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-22 Cont ID  
Sent By fgiaquin Date 2022-01-22 Time 18:22 Rev Time 0.00
Received By fgiaquin Date 2021-12-29 Time 11:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-17 Cont ID  
Sent By jleahy Date 2021-12-17 Time 16:14 Rev Time 0.00
Received By jleahy Date 2021-11-09 Time 07:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-02-03 Cont ID  
Sent By medwards Date 2022-02-03 Time 11:25 Rev Time 0.00
Received By medwards Date 2022-02-03 Time 11:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-01-03 Cont ID  
Sent By medwards Date 2022-01-03 Time 16:08 Rev Time 0.00
Received By medwards Date 2022-01-03 Time 16:08 Sent To  
Notes
2022-01-03 16:11:28THE PERMIT RESPONSE LETTER STATES THAT THE DESIGNER HAS
 ADDED CONDENSATE DRAINAGE NOTE TO SHEET M150 IN
 REFERENCE TO COMMENT 6 OF THE 1ST REVIEW CYCLE LISTED
 BELOW. THIS REVIEWER DOES NOT SEE A NOTE ON M150 THAT
 MENTIONS THE CONDENSATE DRAINAGE. PLEASE CORRECT THIS.
  
 6) PLEASE SHOW THE CONDENSATE DRAIN SIZE, MATERIAL AND
 TERMINATION LOCATION FOR ALL CONDENSATION. FBC M 307
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-17 Cont ID  
Sent By medwards Date 2021-11-17 Time 08:33 Rev Time 0.00
Received By medwards Date 2021-11-17 Time 08:33 Sent To  
Notes
2021-11-17 08:33:511ST REVIEW FBC-2020 MECHANICAL
 PERMIT- 21110233
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE
 REFRIGERATION EQUIPMENT MUST HAVE A SEPARATE PERMIT
 APPLICATION, SEPARATE PLAN REVIEW AND DOCUMENTATION FOR
 THE REVIEW AS IT WILL NOT BE REVIEWED UNDER THIS
 PERMIT.
  
 2) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE
 KITCHEN HOOD EQUIPMENT MUST HAVE A SEPARATE PERMIT
 APPLICATION, SEPARATE PLAN REVIEW AND DOCUMENTATION FOR
 THE REVIEW AS IT WILL NOT BE REVIEWED UNDER THIS
 PERMIT.
  
 3) PLEASE PROVIDE DOCUMENTATION FOR THE APPLIANCE THAT
 WOULD REQUIRE THE TYPE I HOOD OR PROVIDE THE
 DOCUMENTATION TO MEET THE EXCEPTION OF FBC M 507.2
  
 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 5) PLEASE EXPLAIN THE LOCATION OF EF-4 AND THE USE OF
 THIS EXHAUST FAN. FBC 107.2.1
  
 6) PLEASE SHOW THE CONDENSATE DRAIN SIZE, MATERIAL AND
 TERMINATION LOCATION FOR ALL CONDENSATION. FBC M 307
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-02-01 Cont ID  
Sent By ccole Date 2022-02-01 Time 17:03 Rev Time 0.00
Received By ccole Date 2022-02-01 Time 15:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-01-05 Cont ID  
Sent By ccole Date 2022-01-05 Time 11:30 Rev Time 0.00
Received By ccole Date 2022-01-05 Time 07:30 Sent To  
Notes
2022-01-05 11:31:272ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21110233
 1/5/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A123 DETAIL 2: THE TOILET PAPER DISPENSERS
 SHALL BE LOCATED 7 INCHES MINIMUM AND 9 INCHES MAXIMUM
 IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINES OF THE DISPENSERS- SEC. AND FIGURE 604.7
 FBC P.
  
 2) P110: PLEASE RELOCATE THE FIXTURE DRAIN LINE FOR THE
 FLOOR DRAIN IN THE KITCHEN AREA TO THE GREASE WASTE
 LINE- SEC. 1003.3.1 FBC P.
  
 3) P120: THE CONDENSATE DRAINAGE FROM THE RTU?S SHALL
 BE PIPED TO AN APPROVED PLACE OF DISPOSAL, AND SHALL
 NOT FLOW OUT ONTO THE ROOF SURFACE- SEC. 314.2.1 FBC P.
  
 4) P001 & P120: SHOW THE LOCATIONS OF THE ICE MAKER
 BFP, AND THE RPZ. PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR NEW OR REPLACEMENT POTABLE WATER SERVICE
 BACKFLOW PREVENTERS- SECTION 105.1 & 107.1 WPB.
  
 5) P 120 & P430 DETAIL 8: PROVIDE A BACKFLOW PREVENTER
 FOR THE FEED WATER SUPPLY LINE UPSTREAM OF THE FILTERS-
 SEC. 608.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-11-29 Cont ID  
Sent By ccole Date 2021-11-29 Time 14:48 Rev Time 0.00
Received By ccole Date 2021-11-24 Time 16:32 Sent To  
Notes
2021-11-29 14:51:051ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21110233
 11/29/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A123- FBC ACC COMPLIANCES REQUIRED:
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SECTION 604.3.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) THE SIDE WALL GRAB BARS SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL-
 SECTION AND FIGURE 604.5.1
 E) THE REAR WALL GRAB BARS SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE- SECTION AND FIGURE 604.5.2.
 F) REMOVE THE VERTICAL GRAB BARS. THEY ARE NOT REQUIRED
 AND IN CONFLICT WITH SECTION 609.4 WHICH REQUIRES GRAB
 BARS TO BE INSTALLED IN HORIZONTAL POSITIONS.
 G) SHOW THE 3'-4" MEASUREMENT TO THE REFLECTIVE
 SURFACES OF THE MIRRORS- 603.3.
  
 2) P110: THE MOP SINK SHALL DRAIN INTO THE GREASE WASTE
 INTERCEPTOR LINE- SECTION 1003.3.1 FBC P.
  
 3) P110: PROVIDE A VENT FOR THE FLOOR DRAIN SHOWN BY
 THE FOOD PREP AREA- SECTION AND TABLE 909.1 FBC P.
  
 4) P110: THE CLEAR WATER DRAINAGE FROM THE ICE BIN (P4)
 SHALL NOT DISCHARGE INTO THE GREASE WASTE INTERCEPTOR-
 SECTION 1003.3.1 FBC P.
  
 5) P120: PROVIDE WATER HAMMER ARRESTOR SYMBOLS ON THE
 WATER ISOMETRIC DRAWING- SECTION 604.9 FBC P.
  
 6) P120: PROVIDE ENLARGED WATER FILTER PIPING DRAWINGS
 INDICATING COMPLIANCE WITH SECTIONS 608.3 & 608.4 FBC
 P.
  
 7) P001 & P120: SHOW THE LOCATIONS OF THE ICE MAKER
 BFP, AND THE RPZ. PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR NEW OR REPLACEMENT POTABLE WATER SERVICE
 BACKFLOW PREVENTERS- SECTION 105.1 & 107.1 WPB.
  
 8) P120: THE PLAN SHOWS NON-COMPLIANCE WITH SECTION &
 TABLE C404.5.1 FBC EC. A 1/2 INCH HW PIPE HAS A MAXIMUM
 ALLOWABLE LENGTH OF 2FT. FROM THE NEAREST HOT WATER
 SOURCE TO THE FIXTURE SUPPLY PIPE AT THE LAVATORIES.
 PLEASE PROVIDE EITHER POINT OF USE WATER HEATERS AT THE
 LAVATORIES OR A HOT WATER RECIRCULATION PUMP.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-02-04 Cont ID  
Sent By jleahy Date 2022-02-04 Time 15:31 Rev Time 0.00
Received By jleahy Date 2022-02-04 Time 15:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-01-22 Cont ID  
Sent By fgiaquin Date 2022-01-22 Time 18:21 Rev Time 0.00
Received By fgiaquin Date 2022-01-22 Time 18:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-12-17 Cont ID  
Sent By jleahy Date 2021-12-17 Time 16:14 Rev Time 0.00
Received By jleahy Date 2021-12-17 Time 16:14 Sent To  
Notes
***NONE***