| Plan Review Stops For Permit 21110232 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-02-08 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2022-01-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-01-05 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2022-01-05 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2022-01-05 14:24:38 | COMMERCIAL ASBESTOS | | | TO THE BUILDING CONTRACTOR: | | | PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION | | | THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE. | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN | | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT | | | LINE. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-04-27 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-02-08 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2022-02-08 |
Time |
11:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-01-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-01-05 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2022-01-05 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2022-01-05 14:23:47 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2020 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 21110232 | | | ADD: 218 DATURA ST. / 2ND FLOOR EXPANSION | | | CONT: SIMON CONTRACTING SERVICES | | | TEL: 561-371-5519 | | | E-MAIL: [email protected] | | | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: WED. JAN. 05TH/ 2022 | | | ACTION: DENIED | | | | | | 1) SHEET A-600 DETAIL # 5 SHOWS THE SNACK ROOM | | | COUNTERTOP AND SINK AT AN ELEVATION 3 FEET ABOVE FINISH | | | FLOOR. PLEASE REFER TO THE 2020 FBC-ACCESSIBILITY CODE | | | SECTION: | | | 606 LAVATORIES AND SINKS> 2020 FBC-ACCESSIBILITY CODE | | | SECTION 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE | | | INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR | | | COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. | | | | | | 2) SHEET A-600 IN DETAIL # 3THE CONFERENCE ROOM | | | COUNTERTOP IS ALSO AT AN ELEVATION OF 3 FEET TO THE TOP | | | OF THE COUNTERTOP. SEE 2020 FBC-ACCESSIBILITY CODE | | | SECTION 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL | | | BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE | | | FINISH FLOOR OR GROUND. | | | | | | 3) SHEET A-600 DETAIL # 5 SHOWS THE SNACK ROOM WITH | | | MICROWAVE SHELF (BOTTOM OF SHELF) AT 4 FEET 6 INCHES | | | ABOVE FINISH FLOOR. 2020 FBC-ACCESSIBILITY CODE | | | SECTIONS: | | | | | | 3A) 308 REACH RANGES. | | | 308.2 FORWARD REACH / 308.2.1 UNOBSTRUCTED/ 308.2.2 | | | OBSTRUCTED HIGH REACH. | | | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 | | | OBSTRUCTED HIGH REACH. | | | | | | 3B) 309 OPERABLE PARTS. | | | 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE | | | OR MORE OF THE REACH RANGES SPECIFIED IN 308. | | | 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH | | | ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, | | | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED | | | TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM. | | | | | | 4) SHEET A-300 & A-700 THE DOOR SCHEDULE SHOWS DOORS TO | | | STAIRWELLS DOOR 200.1 EX. STAIR # 1 AND DOOR 210.1 TO | | | EXIT STAIR # 2 THEY ARE EXISTING, BUT NO FIRE RATING IS | | | PROVIDED. 2020 FBC-B TABLE 716.5. | | | | | | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | | | | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING | | | FROM CITY HALL. | | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | | PART-TIME/ RETIRED. | | | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | | BACK INTO THE OFFICE CALL | | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | | THANK YOU. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-01-14 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-01-14 |
Time |
21:42 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-01-14 |
Time |
19:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2022-04-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-04-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-04-22 |
Time |
09:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2021-12-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-12-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-12-20 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-12-17 |
Time |
12:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-05-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-05-03 |
Time |
10:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-04-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-04-21 |
Time |
15:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-03-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-03-24 |
Time |
16:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-03-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-07 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-02-22 |
Time |
09:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-02-17 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-02-17 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-02-07 |
Time |
12:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-19 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-01-19 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-12-16 |
Time |
08:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-03-03 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-03 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-03 |
Time |
17:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-02-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-16 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-16 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2022-02-16 08:51:57 | SHEET M-200 IS LABELED EXISTING MECHANICAL FOR | | | REFERENCE, PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS, | | | THERE ARE NO CALCULATIONS ON THIS OR SHEET M204. PLEASE | | | BASE THESE CALCULATIONS ON THE 2020 FBC M 403.3.1.1 AND | | | TABLE 403.3.1.1. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-12-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-12-20 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-12-20 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2021-12-20 14:38:40 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21110232 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-200: ASHRAE 62.1-1999 IS REFERENCED IN THE | | | VENTILATION RATES BOX. PLEASE REFERENCE THE CURRENT | | | ASHRAE 62.1-2013 EDITION OR THE FBC M 2017 EDITION. | | | | | | 2) PLEASE REFERENCE THE CURRENT EDITION OF 2020 FBC | | | MECHANICAL. | | | | | | 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS. FBC M | | | 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2022-05-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-05-04 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-05-04 |
Time |
14:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-04-27 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-04-27 |
Time |
13:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2022-03-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-03-30 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-03-30 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2022-03-30 17:21:42 | 4TH REVIEW FBC-2020 PLUMBING | | | PERMIT- 21110232 | | | 2/9/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) BASED ON SECTION 810.1 FBC EX AND TABLE 403.1 FBC P. | | | THE PLAN SHOWS A DEFICIENCY OF ONE MALE WATER CLOSET. | | | COMMENTS FROM THE 1ST, 2ND, AND 3RD REVIEWS COPIED | | | BELOW- PLEASE COMPLY. | | | | | | 2) SHEET G110: THE PLAN APPEARS TO SHOW THE OCCUPANT | | | LOAD OF THE STORY HAS INCREASED OVER 20%. REFER TO SEC. | | | 810.1 FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS | | | IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A | | | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED | | | NUMBER OF PLUMBING FIXTURES. PLEASE NOTE THAT DRINKING | | | FOUNTAINS AND SERVICE SINKS ARE REQUIRED FOR B | | | OCCUPANCIES. THE CALCULATIONS AND PLANS ARE NOT IN | | | COMPLIANCE WITH TABLE 403.1 FBC WHICH REQUIRES A | | | MINIMUM OF 3 MALE WATER CLOSETS EACH AND 2 MALE AND 2 | | | FEMALE LAVATORIES EACH. PLEASE NOTE SEPARATE FACILITIES | | | ARE REQUIRED FOR MALE AND FEMALE USE- SEC. 403.2. | | | | | | 3) SHEET G110: PLEASE SEE SEC. 403.1.1 FBC PLUMBING. | | | THE TOTAL OCCUPANT LOAD 0F 154 SHALL BE DIVIDED IN | | | HALF. TO DETERMINE THE NUMBER OF FIXTURES, THE FIXTURE | | | RATIO OR RATIOS FOR EACH FIXTURE TYPE SHALL BE APPLIED | | | TO THE OCCUPANT LOAD OF EACH SEX IN ACCORDANCE WITH | | | TABLE 403.1 FBC P. BUSINESS OCCUPANCY WITH 154 | | | OCCUPANTS REQUIRES 3 MALE AND 3 FEMALE WATER CLOSETS, | | | AND 2 MALE AND 2 FEMALE LAVATORIES- TABLE 403.1. PLEASE | | | NOTE SHEET G100 SPECIFIES 176 OCCUPANTS. WHICH OCCUPANT | | | LOAD IS CORRECT? | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2022-02-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-02-23 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-02-23 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2022-02-23 14:49:24 | 3RD REVIEW FBC-2020 PLUMBING | | | PERMIT- 21110232 | | | 2/9/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. FAILED COMMENT # 1 FROM | | | THE 1ST AND 2ND REVIEWS IS LISTED BELOW. PLEASE SEE | | | SEC. 403.1.1 FBC PLUMBING. THE TOTAL OCCUPANT LOAD 0F | | | 154 SHALL BE DIVIDED IN HALF. TO DETERMINE THE NUMBER | | | OF FIXTURES, THE FIXTURE RATIO OR RATIOS FOR EACH | | | FIXTURE TYPE SHALL BE APPLIED TO THE OCCUPANT LOAD OF | | | EACH SEX IN ACCORDANCE WITH TABLE 403.1 FBC P. BUSINESS | | | OCCUPANCY WITH 154 OCCUPANTS REQUIRES 3 MALE AND 3 | | | FEMALE WATER CLOSETS, AND 2 MALE AND 2 FEMALE | | | LAVATORIES- TABLE 403.1. PLEASE NOTE SHEET G100 | | | SPECIFIES 176 OCCUPANTS. WHICH OCCUPANT LOAD IS | | | CORRECT? | | | | | | 1) FAILED. G110: THE PLAN APPEARS TO SHOW THE OCCUPANT | | | LOAD OF THE STORY HAS INCREASED OVER 20%. REFER TO SEC. | | | 810.1 FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS | | | IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A | | | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED | | | NUMBER OF PLUMBING FIXTURES. PLEASE NOTE THAT DRINKING | | | FOUNTAINS AND SERVICE SINKS ARE REQUIRED FOR B | | | OCCUPANCIES. THE CALCULATIONS AND PLANS ARE NOT IN | | | COMPLIANCE WITH TABLE 403.1 FBC WHICH REQUIRES A | | | MINIMUM OF 3 MALE WATER CLOSETS EACH AND 2 MALE AND 2 | | | FREMALE LAVATORIES EACH. PLEASE NOTE SEPARATE | | | FACILITIES ARE REQUIRED FOR MALE AND FEMALE USE- SEC. | | | 403.2 | | | | | | NEW COMMENT. | | | | | | 2) SHEET P200 WAS NOT UPLOADED FOR REVIEW WITH THE 2ND | | | SUBMITTAL. THE SHEET IS NAMED P200 IN PROJECT DOX BUT | | | IS ACTUALLY SHEET P201 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-02-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-02-09 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-02-09 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2022-02-09 13:08:15 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 21110232 | | | 2/9/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE | | | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN | | | CAPS FOR FURTHER CLARIFICATION. | | | | | | 1) FAILED. G110: THE PLAN APPEARS TO SHOW THE OCCUPANT | | | LOAD OF THE STORY HAS INCREASED OVER 20%. REFER TO SEC. | | | 810.1 FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS | | | IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A | | | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED | | | NUMBER OF PLUMBING FIXTURES. PLEASE NOTE THAT DRINKING | | | FOUNTAINS AND SERVICE SINKS ARE REQUIRED FOR B | | | OCCUPANCIES. THE CALCULATIONS AND PLANS ARE NOT IN | | | COMPLIANCE WITH TABLE 403.1 FBC WHICH REQUIRES A | | | MINIMUM OF 3 MALE WATER CLOSETS AND 2 MALE LAVATORIES. | | | PLEASE NOTE SEPARATE FACILITIES ARE REQUIRED FOR MALE | | | AND FEMALE USE- SEC. 403.2 | | | | | | 6) FAILED. P-200: PLEASE SHOW THE LOCATIONS OF THE | | | REQUIRED CHECK VALVES AND FULL OPEN VALVES ON THE PUMP | | | DISCHARGE PIPES AND SHOW HOW ACCESS TO THE VALVES WILL | | | BE PROVIDED- SEC. 712.2 FBC P. THE CORRECTED SHEET | | | P-200 WAS NOT RESUBMITTED FOR REVIEW. | | | | | | NEW COMMENT. | | | | | | 1) SHEET P-201: HOT WATER AT A MINIMUM TEMPERATURE OF | | | 110 DEGREES REQUIRED F AT THE NEW SINKS PER SECS. 202 & | | | 607.1 FBC P. PLACE A NOTE ON THE WATER HEATER EQUIPMENT | | | SCHEDULE OR SUBMIT SPECS TO VERIFY THE EEMAX WATER | | | HEATERS DO NOT HAVE INTEGRAL DEVICES THAT WILL LIMIT | | | THE WATER TEMPERATURE TO LESS THAN 110 DEGREES F. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-01-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-01-05 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-01-05 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2022-01-05 16:24:45 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21110232 | | | 1/5/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) G110: THE PLAN APPEARS TO SHOW THE OCCUPANT LOAD OF | | | THE STORY HAS INCREASED OVER 20%. REFER TO SEC. 810.1 | | | FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS IN | | | COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE | | | THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF | | | PLUMBING FIXTURES. PLEASE NOTE THAT DRINKING FOUNTAINS | | | AND SERVICE SINKS ARE REQUIRED FOR B OCCUPANCIES. | | | | | | 2) G110, A300, & A600: SHOW THE CLEAR FLOOR SPACE | | | APPROACH DIAGRAMS AND DIMENSIONS AT THE SINKS, | | | DISHWASHER AND REFRIGERATOR- SECTIONS 305, 606.2, | | | 804.6.3 & 804.6.6 FBC ACC. | | | | | | 3) A600 DETAILS 5 & 6: PLEASE INDICATE THE SINKS SHALL | | | BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR | | | COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH | | | FLOORS- SEC. 606.3 FBC ACC. | | | | | | 4) A600: THE CONTROLS AND HANDLE FOR THE MICROWAVE | | | APPEAR TO BE ABOVE THE MAXIMUM REACH RANGES AS | | | INDICATED IN SEC 308 FBC ACC. | | | | | | 5) A600: VERIFY THE FREEZER INSIDE THE REFRIGERATOR HAS | | | A MINIMUM OF 50 PERCENT OF FREEZER SPACE 54-INCHES | | | MAXIMUM FROM THE FINISHED FLOOR- SEC. 804.6.6 FBC ACC. | | | | | | 6) P-200: PLEASE SHOW THE LOCATIONS OF THE REQUIRED | | | CHECK VALVES AND FULL OPEN VALVES ON THE PUMP DISCHARGE | | | PIPES, AND SHOW HOW ACCESS TO THE VALVES WILL BE | | | PROVIDED- SEC. 712.2 FBC P. | | | | | | 7) P-300: FULL OPEN DEDICATED VALVES ARE REQUIRED FOR | | | THE COLD WATER SUPPLY LINES TO THE WATER HEATERS- SECS. | | | 503.1 & 606.1 (8) FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
6 |
Status |
P |
Date |
2022-05-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-05-04 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-05-04 |
Time |
14:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
F |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-04-27 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-04-27 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2022-04-27 13:23:10 | SIGNATURE REVIEW FBC- 2020 | | | PERMIT- 21110232 | | | 4/27/22 | | | | | | CODES IN EFFECT: | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) 2ND REQUEST: THE SUBMITTED PLAN SHEET P-200 IS NOT | | | DIGITALLY SIGNED AND SEALED BYT THE ENGINEER OF RECORD. | | | PLANS PREPARED BY FL. LICENSED ENGINEERS THAT ARE | | | TRANSMITTED ELECTRONICALLY SHALL BEAR VERIFIABLE | | | DIGITAL SEALS AND SIGNATURES OF THE ENGINEER- FL. | | | STATUTE 471.025, AND SECTION 61G15-23.005 FAC. | | | | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR | | | ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND | | | DOCUMENTS. | | | A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL | | | ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY | | | CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION. | | | THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE | | | A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES | | | NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.) | | | YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE | | | ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT | | | USE A THIRD PARTY. | | | YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT | | | IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE | | | AND DOCUMENT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2022-03-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-03-30 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-03-30 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2022-03-30 17:26:18 | SIGNATURE REVIEW FBC- 2020 | | | PERMIT- 21110232 | | | 3/30/22 | | | | | | CODES IN EFFECT: | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | PLAN REVIEW RESULTS: DENIED. | | | 1) THE SUBMITTED PLAN SHEET P-200 IS NOT DIGITALLY | | | SIGNED AND SEALED BYT THE ENGINEER OF RECORD. PLANS | | | PREPARED BY FL. LICENSED ENGINEERS THAT ARE TRANSMITTED | | | ELECTRONICALLY SHALL BEAR VERIFIABLE DIGITAL SEALS AND | | | SIGNATURES OF THE ENGINEER- FL. STATUTE 471.025, AND | | | SECTION 61G15-23.005 FAC. | | | | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR | | | ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND | | | DOCUMENTS. | | | A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL | | | ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY | | | CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION. | | | THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE | | | A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES | | | NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.) | | | YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE | | | ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT | | | USE A THIRD PARTY. | | | YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT | | | IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE | | | AND DOCUMENT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-03-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-07 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-07 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2022-03-03 17:12:14 | DIGITAL SIGNATURES FOR MECHANICAL DRAWINGS APPROVED. ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-02-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-16 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-16 |
Time |
08:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-01-18 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-18 |
Time |
12:58 |
Rev Time |
|
| Received By |
mpeterso |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-01-18 12:58:19 | REVIEW OF SIGNATURE AND SEAL ON DIGITAL PLANS APPROVED |
|
|