Plan Review Details - Permit 21110232
Plan Review Stops For Permit 21110232
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-02-08 Cont ID  
Sent By jwitmer Date 2022-02-08 Time 11:05 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-01-05 Cont ID  
Sent By jwitmer Date 2022-01-05 Time 14:24 Rev Time 0.00
Received By jwitmer Date 2022-01-05 Time 13:37 Sent To  
Notes
2022-01-05 14:24:38COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-04-27 Cont ID  
Sent By jwitmer Date 2022-04-27 Time 10:37 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-02-08 Cont ID  
Sent By jwitmer Date 2022-02-08 Time 11:12 Rev Time 0.00
Received By jwitmer Date 2022-02-08 Time 11:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-05 Cont ID  
Sent By jwitmer Date 2022-01-05 Time 14:23 Rev Time 0.00
Received By jwitmer Date 2022-01-05 Time 13:37 Sent To  
Notes
2022-01-05 14:23:47WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21110232
 ADD: 218 DATURA ST. / 2ND FLOOR EXPANSION
 CONT: SIMON CONTRACTING SERVICES
 TEL: 561-371-5519
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 05TH/ 2022
 ACTION: DENIED
  
 1) SHEET A-600 DETAIL # 5 SHOWS THE SNACK ROOM
 COUNTERTOP AND SINK AT AN ELEVATION 3 FEET ABOVE FINISH
 FLOOR. PLEASE REFER TO THE 2020 FBC-ACCESSIBILITY CODE
 SECTION:
 606 LAVATORIES AND SINKS> 2020 FBC-ACCESSIBILITY CODE
 SECTION 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2) SHEET A-600 IN DETAIL # 3THE CONFERENCE ROOM
 COUNTERTOP IS ALSO AT AN ELEVATION OF 3 FEET TO THE TOP
 OF THE COUNTERTOP. SEE 2020 FBC-ACCESSIBILITY CODE
 SECTION 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL
 BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 3) SHEET A-600 DETAIL # 5 SHOWS THE SNACK ROOM WITH
 MICROWAVE SHELF (BOTTOM OF SHELF) AT 4 FEET 6 INCHES
 ABOVE FINISH FLOOR. 2020 FBC-ACCESSIBILITY CODE
 SECTIONS:
  
 3A) 308 REACH RANGES.
 308.2 FORWARD REACH / 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 3B) 309 OPERABLE PARTS.
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 4) SHEET A-300 & A-700 THE DOOR SCHEDULE SHOWS DOORS TO
 STAIRWELLS DOOR 200.1 EX. STAIR # 1 AND DOOR 210.1 TO
 EXIT STAIR # 2 THEY ARE EXISTING, BUT NO FIRE RATING IS
 PROVIDED. 2020 FBC-B TABLE 716.5.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-14 Cont ID  
Sent By fgiaquin Date 2022-01-14 Time 21:42 Rev Time 0.00
Received By fgiaquin Date 2022-01-14 Time 19:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-04-22 Cont ID  
Sent By pleduc Date 2022-04-22 Time   Rev Time 0.00
Received By pleduc Date 2022-04-22 Time 09:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-12-20 Cont ID  
Sent By pleduc Date 2021-12-20 Time   Rev Time 0.00
Received By pleduc Date 2021-12-20 Time 10:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pleduc Date 2021-12-17 Time 12:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2022-05-04 Time   Rev Time 0.00
Received By aoliver Date 2022-05-03 Time 10:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2022-04-27 Time   Rev Time 0.00
Received By lmarchan Date 2022-04-21 Time 15:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2022-03-30 Time   Rev Time 0.00
Received By lmarchan Date 2022-03-24 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-03-07 Cont ID  
Sent By rmcphers Date 2022-03-07 Time 10:19 Rev Time 0.00
Received By rmcphers Date 2022-02-22 Time 09:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-17 Cont ID  
Sent By lmarchan Date 2022-02-17 Time 10:03 Rev Time 0.00
Received By lmarchan Date 2022-02-07 Time 12:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-19 Cont ID  
Sent By lmarchan Date 2022-01-19 Time 14:45 Rev Time 0.00
Received By lmarchan Date 2021-12-16 Time 08:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-03-03 Cont ID  
Sent By medwards Date 2022-03-03 Time 17:11 Rev Time 0.00
Received By medwards Date 2022-03-03 Time 17:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-02-16 Cont ID  
Sent By medwards Date 2022-02-16 Time 08:49 Rev Time 0.00
Received By medwards Date 2022-02-16 Time 08:49 Sent To  
Notes
2022-02-16 08:51:57SHEET M-200 IS LABELED EXISTING MECHANICAL FOR
 REFERENCE, PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS,
 THERE ARE NO CALCULATIONS ON THIS OR SHEET M204. PLEASE
 BASE THESE CALCULATIONS ON THE 2020 FBC M 403.3.1.1 AND
 TABLE 403.3.1.1.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-20 Cont ID  
Sent By medwards Date 2021-12-20 Time 14:38 Rev Time 0.00
Received By medwards Date 2021-12-20 Time 14:38 Sent To  
Notes
2021-12-20 14:38:401ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21110232
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-200: ASHRAE 62.1-1999 IS REFERENCED IN THE
 VENTILATION RATES BOX. PLEASE REFERENCE THE CURRENT
 ASHRAE 62.1-2013 EDITION OR THE FBC M 2017 EDITION.
  
 2) PLEASE REFERENCE THE CURRENT EDITION OF 2020 FBC
 MECHANICAL.
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS. FBC M
 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2022-05-04 Cont ID  
Sent By ccole Date 2022-05-04 Time 15:24 Rev Time 0.00
Received By ccole Date 2022-05-04 Time 14:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2022-04-27 Cont ID  
Sent By ccole Date 2022-04-27 Time 13:20 Rev Time 0.00
Received By ccole Date 2022-04-27 Time 13:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2022-03-30 Cont ID  
Sent By ccole Date 2022-03-30 Time 17:20 Rev Time 0.00
Received By ccole Date 2022-03-30 Time 16:09 Sent To  
Notes
2022-03-30 17:21:424TH REVIEW FBC-2020 PLUMBING
 PERMIT- 21110232
 2/9/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) BASED ON SECTION 810.1 FBC EX AND TABLE 403.1 FBC P.
 THE PLAN SHOWS A DEFICIENCY OF ONE MALE WATER CLOSET.
 COMMENTS FROM THE 1ST, 2ND, AND 3RD REVIEWS COPIED
 BELOW- PLEASE COMPLY.
  
 2) SHEET G110: THE PLAN APPEARS TO SHOW THE OCCUPANT
 LOAD OF THE STORY HAS INCREASED OVER 20%. REFER TO SEC.
 810.1 FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS
 IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 NUMBER OF PLUMBING FIXTURES. PLEASE NOTE THAT DRINKING
 FOUNTAINS AND SERVICE SINKS ARE REQUIRED FOR B
 OCCUPANCIES. THE CALCULATIONS AND PLANS ARE NOT IN
 COMPLIANCE WITH TABLE 403.1 FBC WHICH REQUIRES A
 MINIMUM OF 3 MALE WATER CLOSETS EACH AND 2 MALE AND 2
 FEMALE LAVATORIES EACH. PLEASE NOTE SEPARATE FACILITIES
 ARE REQUIRED FOR MALE AND FEMALE USE- SEC. 403.2.
  
 3) SHEET G110: PLEASE SEE SEC. 403.1.1 FBC PLUMBING.
 THE TOTAL OCCUPANT LOAD 0F 154 SHALL BE DIVIDED IN
 HALF. TO DETERMINE THE NUMBER OF FIXTURES, THE FIXTURE
 RATIO OR RATIOS FOR EACH FIXTURE TYPE SHALL BE APPLIED
 TO THE OCCUPANT LOAD OF EACH SEX IN ACCORDANCE WITH
 TABLE 403.1 FBC P. BUSINESS OCCUPANCY WITH 154
 OCCUPANTS REQUIRES 3 MALE AND 3 FEMALE WATER CLOSETS,
 AND 2 MALE AND 2 FEMALE LAVATORIES- TABLE 403.1. PLEASE
 NOTE SHEET G100 SPECIFIES 176 OCCUPANTS. WHICH OCCUPANT
 LOAD IS CORRECT?
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-02-23 Cont ID  
Sent By ccole Date 2022-02-23 Time 14:30 Rev Time 0.00
Received By ccole Date 2022-02-23 Time 13:02 Sent To  
Notes
2022-02-23 14:49:243RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21110232
 2/9/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENT # 1 FROM
 THE 1ST AND 2ND REVIEWS IS LISTED BELOW. PLEASE SEE
 SEC. 403.1.1 FBC PLUMBING. THE TOTAL OCCUPANT LOAD 0F
 154 SHALL BE DIVIDED IN HALF. TO DETERMINE THE NUMBER
 OF FIXTURES, THE FIXTURE RATIO OR RATIOS FOR EACH
 FIXTURE TYPE SHALL BE APPLIED TO THE OCCUPANT LOAD OF
 EACH SEX IN ACCORDANCE WITH TABLE 403.1 FBC P. BUSINESS
 OCCUPANCY WITH 154 OCCUPANTS REQUIRES 3 MALE AND 3
 FEMALE WATER CLOSETS, AND 2 MALE AND 2 FEMALE
 LAVATORIES- TABLE 403.1. PLEASE NOTE SHEET G100
 SPECIFIES 176 OCCUPANTS. WHICH OCCUPANT LOAD IS
 CORRECT?
  
 1) FAILED. G110: THE PLAN APPEARS TO SHOW THE OCCUPANT
 LOAD OF THE STORY HAS INCREASED OVER 20%. REFER TO SEC.
 810.1 FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS
 IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 NUMBER OF PLUMBING FIXTURES. PLEASE NOTE THAT DRINKING
 FOUNTAINS AND SERVICE SINKS ARE REQUIRED FOR B
 OCCUPANCIES. THE CALCULATIONS AND PLANS ARE NOT IN
 COMPLIANCE WITH TABLE 403.1 FBC WHICH REQUIRES A
 MINIMUM OF 3 MALE WATER CLOSETS EACH AND 2 MALE AND 2
 FREMALE LAVATORIES EACH. PLEASE NOTE SEPARATE
 FACILITIES ARE REQUIRED FOR MALE AND FEMALE USE- SEC.
 403.2
  
 NEW COMMENT.
  
 2) SHEET P200 WAS NOT UPLOADED FOR REVIEW WITH THE 2ND
 SUBMITTAL. THE SHEET IS NAMED P200 IN PROJECT DOX BUT
 IS ACTUALLY SHEET P201
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-02-09 Cont ID  
Sent By ccole Date 2022-02-09 Time 13:05 Rev Time 0.00
Received By ccole Date 2022-02-09 Time 11:22 Sent To  
Notes
2022-02-09 13:08:152ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21110232
 2/9/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAPS FOR FURTHER CLARIFICATION.
  
 1) FAILED. G110: THE PLAN APPEARS TO SHOW THE OCCUPANT
 LOAD OF THE STORY HAS INCREASED OVER 20%. REFER TO SEC.
 810.1 FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS
 IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 NUMBER OF PLUMBING FIXTURES. PLEASE NOTE THAT DRINKING
 FOUNTAINS AND SERVICE SINKS ARE REQUIRED FOR B
 OCCUPANCIES. THE CALCULATIONS AND PLANS ARE NOT IN
 COMPLIANCE WITH TABLE 403.1 FBC WHICH REQUIRES A
 MINIMUM OF 3 MALE WATER CLOSETS AND 2 MALE LAVATORIES.
 PLEASE NOTE SEPARATE FACILITIES ARE REQUIRED FOR MALE
 AND FEMALE USE- SEC. 403.2
  
 6) FAILED. P-200: PLEASE SHOW THE LOCATIONS OF THE
 REQUIRED CHECK VALVES AND FULL OPEN VALVES ON THE PUMP
 DISCHARGE PIPES AND SHOW HOW ACCESS TO THE VALVES WILL
 BE PROVIDED- SEC. 712.2 FBC P. THE CORRECTED SHEET
 P-200 WAS NOT RESUBMITTED FOR REVIEW.
  
 NEW COMMENT.
  
 1) SHEET P-201: HOT WATER AT A MINIMUM TEMPERATURE OF
 110 DEGREES REQUIRED F AT THE NEW SINKS PER SECS. 202 &
 607.1 FBC P. PLACE A NOTE ON THE WATER HEATER EQUIPMENT
 SCHEDULE OR SUBMIT SPECS TO VERIFY THE EEMAX WATER
 HEATERS DO NOT HAVE INTEGRAL DEVICES THAT WILL LIMIT
 THE WATER TEMPERATURE TO LESS THAN 110 DEGREES F.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-05 Cont ID  
Sent By ccole Date 2022-01-05 Time 16:23 Rev Time 0.00
Received By ccole Date 2022-01-05 Time 14:34 Sent To  
Notes
2022-01-05 16:24:451ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21110232
 1/5/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) G110: THE PLAN APPEARS TO SHOW THE OCCUPANT LOAD OF
 THE STORY HAS INCREASED OVER 20%. REFER TO SEC. 810.1
 FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF
 PLUMBING FIXTURES. PLEASE NOTE THAT DRINKING FOUNTAINS
 AND SERVICE SINKS ARE REQUIRED FOR B OCCUPANCIES.
  
 2) G110, A300, & A600: SHOW THE CLEAR FLOOR SPACE
 APPROACH DIAGRAMS AND DIMENSIONS AT THE SINKS,
 DISHWASHER AND REFRIGERATOR- SECTIONS 305, 606.2,
 804.6.3 & 804.6.6 FBC ACC.
  
 3) A600 DETAILS 5 & 6: PLEASE INDICATE THE SINKS SHALL
 BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOORS- SEC. 606.3 FBC ACC.
  
 4) A600: THE CONTROLS AND HANDLE FOR THE MICROWAVE
 APPEAR TO BE ABOVE THE MAXIMUM REACH RANGES AS
 INDICATED IN SEC 308 FBC ACC.
  
 5) A600: VERIFY THE FREEZER INSIDE THE REFRIGERATOR HAS
 A MINIMUM OF 50 PERCENT OF FREEZER SPACE 54-INCHES
 MAXIMUM FROM THE FINISHED FLOOR- SEC. 804.6.6 FBC ACC.
  
 6) P-200: PLEASE SHOW THE LOCATIONS OF THE REQUIRED
 CHECK VALVES AND FULL OPEN VALVES ON THE PUMP DISCHARGE
 PIPES, AND SHOW HOW ACCESS TO THE VALVES WILL BE
 PROVIDED- SEC. 712.2 FBC P.
  
 7) P-300: FULL OPEN DEDICATED VALVES ARE REQUIRED FOR
 THE COLD WATER SUPPLY LINES TO THE WATER HEATERS- SECS.
 503.1 & 606.1 (8) FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2022-05-04 Cont ID  
Sent By ccole Date 2022-05-04 Time 15:25 Rev Time 0.00
Received By ccole Date 2022-05-04 Time 14:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2022-04-27 Cont ID  
Sent By ccole Date 2022-04-27 Time 13:20 Rev Time 0.00
Received By ccole Date 2022-04-27 Time 13:01 Sent To  
Notes
2022-04-27 13:23:10SIGNATURE REVIEW FBC- 2020
 PERMIT- 21110232
 4/27/22
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST: THE SUBMITTED PLAN SHEET P-200 IS NOT
 DIGITALLY SIGNED AND SEALED BYT THE ENGINEER OF RECORD.
 PLANS PREPARED BY FL. LICENSED ENGINEERS THAT ARE
 TRANSMITTED ELECTRONICALLY SHALL BEAR VERIFIABLE
 DIGITAL SEALS AND SIGNATURES OF THE ENGINEER- FL.
 STATUTE 471.025, AND SECTION 61G15-23.005 FAC.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2022-03-30 Cont ID  
Sent By ccole Date 2022-03-30 Time 17:24 Rev Time 0.00
Received By ccole Date 2022-03-30 Time 17:24 Sent To  
Notes
2022-03-30 17:26:18SIGNATURE REVIEW FBC- 2020
 PERMIT- 21110232
 3/30/22
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
 1) THE SUBMITTED PLAN SHEET P-200 IS NOT DIGITALLY
 SIGNED AND SEALED BYT THE ENGINEER OF RECORD. PLANS
 PREPARED BY FL. LICENSED ENGINEERS THAT ARE TRANSMITTED
 ELECTRONICALLY SHALL BEAR VERIFIABLE DIGITAL SEALS AND
 SIGNATURES OF THE ENGINEER- FL. STATUTE 471.025, AND
 SECTION 61G15-23.005 FAC.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-03-07 Cont ID  
Sent By rmcphers Date 2022-03-07 Time 10:05 Rev Time 0.00
Received By rmcphers Date 2022-03-07 Time 10:05 Sent To  
Notes
2022-03-03 17:12:14DIGITAL SIGNATURES FOR MECHANICAL DRAWINGS APPROVED. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-16 Cont ID  
Sent By medwards Date 2022-02-16 Time 08:52 Rev Time 0.00
Received By medwards Date 2022-02-16 Time 08:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-18 Cont ID  
Sent By mpeterso Date 2022-01-18 Time 12:58 Rev Time  
Received By mpeterso Date   Time   Sent To  
Notes
2022-01-18 12:58:19REVIEW OF SIGNATURE AND SEAL ON DIGITAL PLANS APPROVED