Plan Review Details - Permit 21110157
Plan Review Stops For Permit 21110157
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-02-22 Cont ID  
Sent By jwitmer Date 2022-02-22 Time 07:18 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-12-07 Cont ID  
Sent By jwitmer Date 2021-12-07 Time 15:20 Rev Time 0.00
Received By jwitmer Date 2021-12-07 Time 12:42 Sent To  
Notes
2021-12-07 15:20:11COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-02-22 Cont ID  
Sent By jwitmer Date 2022-02-22 Time 08:04 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-07 Cont ID  
Sent By jwitmer Date 2021-12-07 Time 15:19 Rev Time 0.00
Received By jwitmer Date 2021-12-07 Time 12:42 Sent To  
Notes
2021-12-07 15:19:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21110157
 ADD: 1401 CLARE AVE. # 700
 CONT: TIDAL CONSTRUCTION GROUP
 TEL: 954-459-0814
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 07TH/ 2021
 ACTION: DENIED
  
 1) A0.00 THE COVERSHEET:
 1A) APPLICABLE CODES DOES NOT SHOW THE 2020 FLORIDA
 BUILDING CODE 7TH EDITION. 2020 EXISTING BUILDING CODE.
 801.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1B) SCOPE OF WORK INDICATES THIS TENANT SPACE TO BE A
 LEVEL 2 ALTERATION. THE MASTERPLAN 16090639 SHOULD THIS
 TENANT LOCATION AS A A3 EXERCISE/ GYM. THAT WOULD MAKE
 THIS PERMIT A CHANGE OF OCCUPANCY REQUIRING A
 CERTIFICATE OF OCCUPANCY.
  
 1C) THE PROJECT DATA DOES NOT LIST THE BUILDING
 CLASSIFICATION PER TABLE 506.2 OR TABLE 601OF THE 2020
 FBC-BUILDING CODE.
  
 2) LIFE SAFETY PLAN:
 2A) THE LIFE SAFETY PLAN IS TAKING A OCCUPANT LOAD
 FACTOR OF 1/7 NET S. F. PLEASE REFER TO THE 2020
 FBC-BUILDING CODE TABLE 1004.5 FOR TABLES AND CHAIRS
 THE OCCUPANT LOAD FACTOR IS TO BE TAKEN AT 15 NET.
 PLEASE UPDATE PLANS. 1621/15= 108.06 ALWAYS ROUND UP TO
 109 OCCUPANTS.
  
 2B) THE LIFE SAFETY PLAN IS MISSING THE EXIT LIGHTS,
 DIRECTIONAL EXIT LIGHTS EMERGENCY BATTERY PACKS THE
 SYMBOL LEGEND HAS THEM IN THEIR LIST, PER 1013.1 HERE
 REQUIRED.
  
 2C) THE LIFE SAFETY PLAN INDICATES WITH THE OCCUPANT
 LOAD 2 REQUIRED EXITS. WHAT THE FLOOR PLAN DOES NOT
 SHOW ARE 2 ACCESSIBLE EXITS. 2020 FBC-ACCESSIBILITY
 CODE SECTION 207.1 MEANS OF EGRESS SHALL COMPLY WITH
 SECTION 1003.2.13 OF THE INTERNATIONAL BUILDING CODE
 (2000 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF
 THE INTERNATIONAL BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 2D) THE EGRESS DOORS ARE NOT LABELED ON EITHER THE LIFE
 SAFETY PLAN OR A1.01 FLOOR PLAN. THE EXIT PASSAGEWAY
 THAT LEADS TO THIS TENANT SPACE IS SHOWN AS A SINGLE
 OUTSWING DOOR ON BOTH THE LS-1 PLAN AND A1.01. WHEREAS
 THE INTERIOR DEMO PERMIT (21091014) OF THIS SPACE SHOWS
 2 OUTSWING DOORS AS WELL AS 16090639 MASTER PLANS.
 DISCREPANCY IN PLANS. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2E) THE LIFE SAFETY PLAN DOES NOT SHOW COMPLIANCE WITH
 SECTION 1018.2, 1029.12.1 AND 1029.12.1.1.
  
 2F) THE LIFE SAFETY PLAN NOR THE SITE PLAN PROVIDE
 WHERE THE BACK PROPERTY LINE IS LOCATED OR THE BACK
 EXIT HOW FAR THE PROPERTY LINE AND SIDE PROPERTY LINE
 ARE LOCATED AND COMPLIANCE WITH PLEASE SHOW COMPLIANCE
 WITH THE 2020 FBC-BUILDING CODE FOR SECTIONS 1028.4 AND
 1028.5. PLEASE PROVIDE A SURVEY OF THE PROPERTY TO SEE
 DISTANCES TO THE PROPERTY LINES.
  
 3) SHEET A1.01:
 3A) THE FLOOR PLAN INDICATES 90 INTERIOR SEATS AND 60
 OUTSIDE SEASONAL SEATS OR A TOTAL OF 150 SEATS. THE
 FLOOR PLAN SHOWS 4 ACCESSIBLE SEATS. THE 2020 FLORIDA
 ACCESSIBILITY CODE SECTION 226.1 WHERE DINING SURFACES
 ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT
 LEAST 5 PERCENT (150 X 0.05= 7.5 SEATS ALWAYS ROUND UP
 OR 8 ACCESSIBLE SEATS) OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902.
  
 3B) THERE ARE NO ACCESSIBLE SEATS LOCATED AT THE BAR.
 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 3B)(1) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, BARS, INCLUDING RAISED
 OR SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 3B)(2) 902.1. DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 3C)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4) SHEET A3.00 THE ENLARGED RESTROOM FLOOR PLAN AND
 ELEVATIONS:
 4A) BOTH DETAILS A & C BOTH SOW THE GRAB RAILS
 DIMENSIONED FROM FINISH FLOOR TO CENTERLINE OF THE GRAB
 BAR, NOT THE TOP OF THE GRASPING SURFACE. 2020
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 4B) DETAILS A & B BOTH SHOW A FRAMED MIRROR. DETAIL A
 SHOWS THE DIMENSION OF 40 INCHES TO THE BOTTOM OF THE
 MIRROR FRAME NOT THE REFLECTIVE SURFACE. 603.3 MIRRORS.
 2020 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 4C) NEITHER DETAIL A NOR B SHOW COMPLIANCE WITH THE 220
 FBC-ACCESS. CODE SECTION 606.5 EXPOSED PIPES AND
 SURFACES. WATER SUPPLY & DRAINPIPES UNDER LAVATORIES
 AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT.
  
 4D) DETAIL C IS MISSING DIMENSIONS TO SHOW COMPLIANCE
 WITH TOILET PAPER DISPENSERS. 604.7. THE TOILET PAPER
 DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES
 MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER.
  
 5) SHEET A0.01 21 AND 22 STATE THE USE OF MOISTURE
 RESISTANT BOARD, OR SIMILAR SURFACES. 2020 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2020 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION"(SIMILAR SURFACES). CONSTRUCTION DOCUMENTS
 SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 6) 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 6A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 6B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 6C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 7) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA
 PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO: [email protected].
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-05 Cont ID  
Sent By jleahy Date 2022-01-05 Time 14:49 Rev Time 0.00
Received By jleahy Date 2022-01-05 Time 14:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-22 Cont ID  
Sent By cwalker Date 2022-02-22 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-02-22 10:41:21FIRE PROVISO COMMENT:
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR CLASS B IN ALL CORRIDORS AND LOBBIES AND
 CLASS A, CLASS B, OR CLASS C IN ALL GENERAL ASSEMBLY
 AREAS FOR WALLS AND CEILING. NFPA 101 12.3.3 THE
 INTERIOR FLOOR FINISH SHALL COMPLY WITH NFPA 101 10.2
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-11-12 Cont ID  
Sent By cwalker Date 2021-11-12 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2021-11-12 13:43:35PROVIDE RAMP DIMENSIONS/DETAILS FOR 2ND EXIT. NFPA 101
 7.2.5
 PROVIDE EXIT PASSAGEWAY WIDTH FOR 2ND EXIT INCLUDING
 CAPACITY. NFPA 101 7.2.6.4
 PROVIDE EXIT DOOR HARDWARE TO BE INSTALLED. NFPA 101
 12.2.2.2
 INDICATE ON PLAN EMERGENCY LIGHTING LOCATIONS. NFPA 101
 12.2.9
 INDICATE ON PLAN LOCATION OF EXIT SIGNAGE. NFPA 101
 12.2.10
 COMMERCIAL COOKING/SUPPRESSION TO BE SUBMITTED UNDER A
 SEPARATE PERMIT. NFPA 101 12.3.2.2, NFPA 1 50.2.1
 IDENTIFY INTERIOR FINISHES THAT COMPLY WITH NFPA 101
 12.3.3
 ANY FIRE SPRINKLER CHANGES/MODIFICATIONS TO BE
 SUBMITTED UNDER A SEPARATE PERMIT.
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2022-04-07 Cont ID  
Sent By ccole Date 2022-04-07 Time 10:57 Rev Time 0.00
Received By ccole Date 2022-04-07 Time 09:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2022-03-16 Cont ID  
Sent By ccole Date 2022-03-16 Time 11:20 Rev Time 0.00
Received By ccole Date 2022-03-15 Time 16:51 Sent To  
Notes
2022-03-16 11:22:413RD REVIEW FBC-2020 FUEL GAS
 PERMIT- 21110157
 3/16/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW AND 2ND REVIEW ARE LISTED BELOW WITH
 ADDITIONAL NOTES. PLEASE COMPLY WITH THE COMMENTS AND
 NOTES.
  
 4) FAILED. P2.1: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE REGULATORS, THE COOKING APPLIANCES, AND THE GAS
 WATER HEATER- SECTIONS 410.2, 623.1, AND 624.1 FBC FG.
 THE RANGE SUBMITTAL INDICATES THE APPLIANCE HAS A
 280,000 BTU LOAD HOWEVER THE RISER INDICATES 70,000
 BTU. PLEASE CORRECT THE RISER DRAWING ACCORDINGLY.
  
 5) FAILED. P2.1: PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE COOKING APPLIANCES AND INDICATE HOW THE AIR
 WILL BE SUPPLIED- SECTION 304.1 FBC FG. NOT PROVIDED.
 THE NARRATIVE RESPONSE REFERENCES THE CAPTIVE AIRE
 DRAWINGS HOWEVER MAKE-UP AIR FOR HOOD EEXHAUST IS NOT
 COMBUSTION AIR FOR APPLLIANCES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-03-02 Cont ID  
Sent By ccole Date 2022-03-02 Time 12:29 Rev Time 0.00
Received By ccole Date 2022-03-01 Time 16:23 Sent To  
Notes
2022-03-02 12:29:462ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21110157
 3/2/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISRTED BELOW WITH ADDITIONAL NOTES.
 PLEASE COMPLY WITH THE COMMENTS AND NOTES.
  
 4) FAILED. P2.1: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE REGULATORS, THE COOKING APPLIANCES, AND THE GAS
 WATER HEATER- SECTIONS 410.2, 623.1, AND 624.1 FBC FG.
 THE RANGE SUBMITTAL INDICATES THE APPLIANCE HAS A
 280,000 BTU LOAD HOWEVER THE RISER INDICATES 70,000
 BTU. PLEASE CORRECT THE RISER DRAWING ACCORDINGLY.
  
 5) FAILED. P2.1: PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE COOKING APPLIANCES AND INDICATE HOW THE AIR
 WILL BE SUPPLIED- SECTION 304.1 FBC FG. NOT PROVIDED.
 THE NARRATIVE RESPONSE REFERENCES THE CAPTIVE AIRE
 DRAWINGS HOWEVER MAKE-UP AIR FOR HOOD EEXHAUST IS NOT
 COMBUSTION AIR FOR APPLLIANCES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-11-30 Cont ID  
Sent By ccole Date 2021-11-30 Time 15:01 Rev Time 0.00
Received By ccole Date 2021-11-30 Time 13:48 Sent To  
Notes
2021-11-30 15:01:581ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21110157
 11/30/21
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P2.1: PLEASE INCLUDE THE 199,900-WATER HEATER
 BTU?S TO THE TOTAL GAS CONSUMPTION TABLE- SECTION 402.2
 FBC FG.
  
 2) P2.1: INDICATE THE SIZE OF THE SUPPLY PIPE FROM THE
 REGULATOR TO THE WATER HEATER- SECTION 402.3 FBC FG.
  
 3) P2.1: SHOW PIPE UNIONS WITHIN 1 FT. OF EACH SIDE OF
 THE REGULATORS IN ACCORDANCE WITH SECTION 410.2 (7) FBC
 FG.
  
 4) P2.1: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 REGULATORS, THE COOKING APPLIANCES, AND THE GAS WATER
 HEATER- SECTIONS 410.2, 623.1, AND 624.1 FBC FG.
  
 5) P2.1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 COOKING APPLIANCES AND INDICATE HOW THE AIR WILL BE
 SUPPLIED- SECTION 304.1 FBC FG
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-04-11 Cont ID  
Sent By medwards Date 2022-04-11 Time 16:07 Rev Time 0.00
Received By medwards Date 2022-04-05 Time 06:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-03-16 Time   Rev Time 0.00
Received By aoliver Date 2022-03-14 Time 15:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-03 Cont ID  
Sent By medwards Date 2022-03-03 Time 08:02 Rev Time 0.00
Received By medwards Date 2022-02-18 Time 07:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-05 Cont ID  
Sent By jleahy Date 2022-01-05 Time 14:52 Rev Time 0.00
Received By jleahy Date 2021-11-10 Time 09:19 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2022-02-22 Cont ID  
Sent By jwitmer Date 2022-02-22 Time 08:04 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-12-07 Cont ID  
Sent By jwitmer Date 2021-12-07 Time 15:17 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-12-07 15:17:47IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-04-11 Cont ID  
Sent By medwards Date 2022-04-11 Time 15:59 Rev Time 0.00
Received By medwards Date 2022-04-11 Time 15:59 Sent To  
Notes
2022-04-11 16:00:39 
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-03-03 Cont ID  
Sent By medwards Date 2022-03-03 Time 07:55 Rev Time 0.00
Received By medwards Date 2022-03-03 Time 07:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By medwards Date 2021-11-18 Time 08:54 Rev Time 0.00
Received By medwards Date 2021-11-18 Time 08:09 Sent To  
Notes
2021-11-18 08:54:411ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21110157
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 FBC 403.3.1.1 AND TABLE 403.3.1.1 AND NOT THE
 ARCHITECTURAL OCCUPANCY COUNTS.
  
 2) PLEASE SHOW THE CONDENSATE DRAIN PIPING AND
 TERMINATION LOCATION ON THE MECHANICAL DRAWING. FBC M
 307
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-04-07 Cont ID  
Sent By ccole Date 2022-04-07 Time 10:57 Rev Time 0.00
Received By ccole Date 2022-04-07 Time 09:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-03-16 Cont ID  
Sent By ccole Date 2022-03-16 Time 11:16 Rev Time 0.00
Received By ccole Date 2022-03-15 Time 16:51 Sent To  
Notes
2022-03-16 11:17:423RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21110157
 3/16/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #4 FROM THE
 1ST AND COMMENT #1 FROM THE 2ND REVIEW ARE LISTED BELOW
 WITH ADDITONAL NOTES. PLEASE COMPLY WITH THE COMMENTS
 AND NOTES.
  
 4) FAILED. P1.1 & P2.1: THE CLEAR WATER WASTE FROM THE
 HAND SINK, WALK-IN COOLER EVAPORATOR AND THE ICE
 MACHINE SHALL NOT DRAIN INTO THE GREASE WASTE LINE AND
 INTERCEPTOR- SECTION 1003.3.1 FBC P. THE CONDENSATE
 FROM THE EVAPORATOR IS ALSO RESTRICTED FROM DRAINING
 INTO THE SANITARY SYSTEM AND SHALL BE DISCHARGED TO AN
 APPROVED LOCATION SUCH AS THE STORM DRAIN SYSTEM OR
 DRYWELL- SEC. 90-126 WPB CODE OF ORDINANCES. RISER NOT
 CORRECTED. HAND SINK (28) BY 3-COMPARTMENT SINK IS
 DRAINING INTO THE GREASE WASTE LINE.
  
 1) FAILED. SHEETS P1.1 & P1.2: REFER TO SEC. 607.1.1
 FBC P AND PROVIDE EITHER A MASTER THERMOSTATIC MIXING
 VALVE AT THE WATER HEATER OR INDIVIDUAL MIXING VALVES
 AT FIXTURES SUPPLYING HOT WATER INCLUDING THE HAND
 SINKS, MOP SINKS, AND 3-COMPARTMENT SINKS. PLEASE NOTE
 THE LAVATORY SINKS ARE APPROVED FOR DELIVERY OF
 TEMPERED WATER USING THE ASSE 1070 MIXING VALVES. THE
 NARRATIVE RESPONSE REFER TO KEYNOTE 5 ON P1.1 WHICH
 ONLY APPLIES TO THE LAVATORIES. WHAT ABOUT TEMPERATURE
 CONTROL FOR THE OTHER SINKS? AS STATED IN SEC. 607.1.1
 THE THERMOSTAT ON THE WATER HEATER CANNOT SERVE AS THE
 TEMPERATURE LIMITING MEANS FOR HOT WATER SUPPLIES TO
 THE MOP SINK AND BREAK ROOM SINK. PLEASE PROVIDE EITHER
 A MASTER THERMOSTATIC MIXING VALVE OR MIXING VALVES AT
 EACH FIXTURE- HAND SINKS, 1 AND 3-COMPARTMENT SINKS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-03-02 Cont ID  
Sent By ccole Date 2022-03-02 Time 12:10 Rev Time 0.00
Received By ccole Date 2022-03-01 Time 16:23 Sent To  
Notes
2022-03-02 12:11:172ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21110157
 3/2/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITONAL NOTES.
 PLEASE COMPLY WITH THE COMMENTS AND NOTES.
  
 4) FAILED. P1.1 & P2.1: THE CLEAR WATER WASTE FROM THE
 HAND SINK, WALK-IN COOLER EVAPORATOR AND THE ICE
 MACHINE SHALL NOT DRAIN INTO THE GREASE WASTE LINE AND
 INTERCEPTOR- SECTION 1003.3.1 FBC P. THE CONDENSATE
 FROM THE EVAPORATOR IS ALSO RESTRICTED FROM DRAINING
 INTO THE SANITARY SYSTEM AND SHALL BE DISCHARGED TO AN
 APPROVED LOCATION SUCH AS THE STORM DRAIN SYSTEM OR
 DRYWELL- SEC. 90-126 WPB CODE OF ORDINANCES. PLAN AND
 RISER NOT CORRECTED.
  
 5) FAILED P1.1 & P2.1: SHOW DRAINAGE AND VENT PIPING
 FOR THE UNDERCOUNTER DISHWASHER- SECTION 1003.3.1 FBC
 P. FLOOR SINK NOT VENTED- SEE SECS. 910.1, 911.1,
 915.1, AND TABLE 909.1 FBC P. PLAN AND RISER ALSO DO
 NOT PROVIDE THE DRAIN PIPE SIZE (DIAMETER).
  
 7) FAILED. P1.1 & P2.1: SHOW THE LOCATIONS OF REQUIRED
 BACKFLOW PREVENTERS FOR WATER LINE CONNECTIONS TO THE
 DISHWASHERS, BEVERAGE DISPENSERS, COFFEE BREWER,
 EXPRESSO MACHINE, WATER FILTER ETC.- SECTION 608.3 FBC
 P. PLEASE INCLUDE A DEVICE SCHEDULE INDICATING MAKES,
 MODELS AND COMPLIANCE STANDARDS. THE BACKFLOW
 PREVENTERS SHALL BE INSTALLED INDIVIDUALLY ON THE
 SUPPLY LINES TO THE COFFEE MAKER AND EXPRESSO MACHINE-
 SEC. 608.3 FBC P.
  
 12) FAILED. ENERGYGAUGE COMPLIANCE FORM: INCORRECT
 COMPLIANCE DATA FOR THE WATER HEATER AND WATER PIPING
 HAS BEEN ENTERED. THE WATER HEATER IS GAS, NOT
 ELECTRIC, HW TEMPERATURE IS HIGHER THAN 105 DEGREES F,
 PIPING IS LARGER THAN 0.25. PLEASE SEE SECTION C404.1
 FBC EC. FORM NOT CORRECTED.
  
 NEW COMMENTS:
  
 1) SHEETS P1.1 & P1.2: REFER TO SEC. 607.1.1 FBCP AND
 PROVIDE EITHER A MASTER THERMOSTATIC MIXING VALVE AT
 THE WATER HEATER OR INDIVIDUAL MIXING VALVES AT
 FIXTURES SUPPLYING HOT WATER INCLUDING THE HAND SINKS,
 MOP SINKS, AND 3-COMPARTMENT SINKS. PLEASE NOTE THE
 LAVATORY SINKS ARE APPROVED FOR DELIVERY OF TEMPERED
 WATER USING THE ASSE 1070 MIXING VALVES.
  
 2) P1.1: MAKES AND MODELS FOR THE FOOD EQUIPMENT
 FIXTURES AND APPLIANCES HAVE NOT BEEN PROVIDED. IN
 ACCORDANCE WITH SEC. 107.4.1 WPB. PLEASE NOTE THOSE
 ITEMS AS DEFERRED SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-11-30 Cont ID  
Sent By ccole Date 2021-11-30 Time 13:44 Rev Time 0.00
Received By ccole Date 2021-11-30 Time 10:30 Sent To  
Notes
2021-11-30 13:47:551ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21101057
 11/30/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1.00 & P0.1: PROVIDE PLUMBING FIXTURE
 CALCULATIONS FOR THE NEW RESTAURANT IN COMPLIANCE WITH
 TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED NUMBER OF PLUMBING FIXTURES.
 BASED ON THE TABLE AND THE OCCUPANT LOAD OF 240
 PERSONS, THE PLANS APPEAR TO SHOW A DEFICIENCY OF 1
 MALE WATER CLOSET AND 1 FEMALE WATER CLOSET. PLEASE
 NOTE DRINKING FOUNTAINS ARE REQUIRED FIXTURES FOR
 RESTAURANTS UNLESS WATER WILL BE SERVED IN CONTAINERS
 FREE OF CHARGE IN ACCORDANCE WITH SECTION 410.4 FBC P.
 PLEASE REVISE THE PLANS TO INDICATE WHICH METHOD WILL
 BE USED AND ALSO TO SHOW THE ADDITION MALE AND FEMALE
 WATER CLOSETS- SECTION 107.2.1 WPB.
  
 2) A3.00: FBC- 2020 ACCESSIBILITY COMPLIANCES:
 A) DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAMS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAMS FOR THE
 LAVATORIES- 606.2.
 C) TURNING SPACE DIAMETERS- 304.3.
 D) DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAM BEYOND
 THE ARC OF THE DOOR- 603.2.3
 E) HEIGHTS OF THE WATER CLOSET SEATS (NOT THE RIMS OF
 THE BOWLS) FROM THE FINISHED FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- 603.3. THE DETAIL SHOWS THE
 MEASUREMENT TO THE BOTTOM OF MIRROR FRAME.
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF THE GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. ADD A NOTE TO THE SIDE BAR
 GRAB BAR TO INDICATE IT SHALL EXTEND A MINIMUM OF 54
 INCHES FROM THE REAR WALL. SHOW THE REAR GRAB WILL
 EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES TOWARDS THE SIDE WALL AND 24 INCHES ON THE OTHER
 SIDE.
 H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- 604.6.
 I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- 606.2
 AND FIGURES 306.2 & 306.3.
  
 2) A3.00: PLEASE INDICATE THE WALL SURROUND FINISH
 MATERIALS TO BE INSTALLED IN THE BATHROOMS AND AT THE
 MOP SINK- SECTION 310.3 FBC P AND 1210.2.2 FBC B- WALLS
 AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 3) P0.1 & A1.01: THE GREASE INTERCEPTOR CALCULATIONS ON
 P0.1 INDICATE 70 SEATS HOWEVER 160 SEATS ARE INDICATED
 ON A1.01. PLEASE REVISE THE CALCULATIONS- SECTION
 1003.3 FBC P. BASED ON THE FORMULA USED THE REQUIRED
 INTERCEPTOR CAPACITY IS 1920 GALLONS. SPECIFICATIONS
 FOR THE GB-250 INDICATE THE INTERCEPTORS ARE UNDERSIZED
 FOR THE LOAD- GREASE RETENTION CAPACITY IS BASED ON
 100/200 GPM FLOW WITH 200 GPM BEING THE MAXIMUM OF EACH
 OF THE 3 INTERCEPTORS.
  
 4) P1.1 & P2.1: THE CLEAR WATER WASTE FROM THE HAND
 SINK, WALK-IN COOLER EVAPORATOR AND THE ICE MACHINE
 SHALL NOT DRAIN INTO THE GREASE WASTE LINE AND
 INTERCEPTOR- SECTION 1003.3.1 FBC P. THE CONDENSATE
 FROM THE EVAPORATOR IS ALSO RESTRICTED FROM DRAINING
 INTO THE SANITARY SYSTEM AND SHALL BE DISCHARGED TO AN
 APPROVED LOCATION SUCH AS THE STORM DRAIN SYSTEM OR
 DRYWELL- SEC. 90-126 WPB CODE OF ORDINANCES.
  
 5) P1.1 & P2.1: SHOW DRAINAGE AND VENT PIPING FOR THE
 UNDERCOUNTER DISHWASHER- SECTION 1003.3.1 FBC P.
  
 6) P1.1 & P2.1: SHOW THE WATER LINE CONNECTIONS TO THE
 UNDERCOUNTER DISHWASHER, BEVERAGE DISPENSERS, COFFEE
 BREWER, EXPRESSO MACHINE ETC.- SECTION 107.2.1 WPB.
 CLARIFY IF A WATER FILTERING SYSTEM WILL BE INSTALLED
 AND ADD IT TO THE DRAWINGS AND EQUIPMENT SCHEDULE IF
 APPLICABLE.
  
 7) P1.1 & P2.1: SHOW THE LOCATIONS OF REQUIRED BACKFLOW
 PREVENTERS FOR WATER LINE CONNECTIONS TO THE
 DISHWASHERS, BEVERAGE DISPENSERS, COFFEE BREWER,
 EXPRESSO MACHINE, WATER FILTER ETC.- SECTION 608.3 FBC
 P. PLEASE INCLUDE A DEVICE SCHEDULE INDICATING MAKES,
 MODELS AND COMPLIANCE STANDARDS.
  
 8) P120: PROVIDE WATER HAMMER ARRESTOR SYMBOLS ON THE
 WATER ISOMETRIC DRAWING- SECTION 604.9 FBC P.
  
 9) P120: PROVIDE AN ENLARGED WATER FILTER PIPING
 DRAWING (IF INSTALLED) INDICATING COMPLIANCE WITH
 SECTIONS 608.3 & 608.4 FBC P.
  
 10) P120: THE PLAN SHOWS NON-COMPLIANCE WITH SECTION &
 TABLE C404.5.1 FBC EC. A 1/2 INCH HW PIPE HAS A MAXIMUM
 ALLOWABLE LENGTH OF 2 FT. FROM THE NEAREST HOT WATER
 SOURCE TO THE FIXTURE SUPPLY PIPE AT THE LAVATORIES.
 PLEASE PROVIDE EITHER POINT OF USE WATER HEATERS AT THE
 LAVATORIES OR A HOT WATER RECIRCULATION PUMP.
  
 11) P0.1: PLEASE PROVIDE A PLUMBING FIXTURE SCHEDULE OR
 INDICATE WHICH FIXTURES WILL BE DEFERRED SUBMITTALS-
 SECTION 107.1 & 107.3.4.1 WPB. CLARIFY IF THE WATER
 CLOSETS WILL BE FLUSH TANKS OR FLUSH VALVES- SEE TABLE
 604.3 FBC P.
  
 12) ENERGYGAUGE COMPLIANCE FORM: INCORRECT COMPLIANCE
 DATA FOR THE WATER HEATER AND WATER PIPING HAS BEEN
 ENTERED. THE WATER HEATER IS GAS, NOT ELECTRIC, HW
 TEMPERATURE IS HIGHER THAN 105 DEGREES F, PIPING IS
 LARGER THAN 0.25. PLEASE SEE SECTION C404.1 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-04-07 Cont ID  
Sent By ccole Date 2022-04-07 Time 10:58 Rev Time 0.00
Received By ccole Date 2022-04-07 Time 10:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-03-16 Cont ID  
Sent By ccole Date 2022-03-16 Time 11:23 Rev Time 0.00
Received By ccole Date 2022-03-15 Time 16:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-03 Cont ID  
Sent By medwards Date 2022-03-03 Time 08:02 Rev Time 0.00
Received By medwards Date 2022-03-03 Time 08:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-05 Cont ID  
Sent By jleahy Date 2022-01-05 Time 14:50 Rev Time 0.00
Received By jleahy Date 2022-01-05 Time 14:50 Sent To  
Notes
***NONE***