Plan Review Details - Permit 21110142
Plan Review Stops For Permit 21110142
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-01-07 Cont ID  
Sent By medwards Date 2022-01-07 Time 11:06 Rev Time 0.00
Received By medwards Date 2022-01-07 Time 11:06 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-12-03 Cont ID  
Sent By dbattles Date 2021-12-03 Time 09:08 Rev Time 0.00
Received By dbattles Date 2021-12-03 Time 09:08 Sent To  
Notes
2021-12-03 09:09:41PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION.
 HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA
 EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT
 LINE.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-02-15 Cont ID  
Sent By rmcphers Date 2022-02-15 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2022-02-15 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-18 Cont ID  
Sent By rmcphers Date 2022-01-18 Time 15:33 Rev Time 0.00
Received By rmcphers Date 2022-01-18 Time 15:20 Sent To  
Notes
2022-01-18 15:33:08OFFICE BUILDOUT (PP AUDIT)
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A8-1 SHOWS WOOD FRAMING AS FIRE RATED -
 SHOULD BE NOTED AS FIRE RETARDANT TREATED PER FBC 603.1
 ALLOWABLE MATERIALS. (1).FIRE-RETARDANT-TREATED WOOD
  
 2) DRAWING A8-11 AND A8-12 SHOWS PLYWOOD USED IN A DROP
 CEILING - MATERIALS SHOULD BE NON CUMBUSTIBLE PER FBC
 803.13.2.1
  
 3) ACCESSIBLE RESTROOM - DRAWING A7-4 SHOWS A CABINET
 (ACS-04) ABOVE THE TOILET GRAB BAR - PLEASE SHOW THE
 REQUIRED 12 INCH CLEARANCE ABOVE THE GRAB BAR PER FBC
 609.3 "THE SPACE BETWEEN THE GRAB BAR AND PROJECTING
 OBJECTS ABOVE SHALL BE 12 INCHES (305 MM) MINIMUM."

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-02-18 Cont ID  
Sent By jleahy Date 2022-02-18 Time 08:51 Rev Time 0.00
Received By jleahy Date 2022-02-18 Time 08:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-01-18 Cont ID  
Sent By jleahy Date 2022-01-18 Time 13:22 Rev Time 0.00
Received By jleahy Date 2022-01-18 Time 07:21 Sent To  
Notes
2022-01-18 13:15:48ELECTRICAL AUDIT
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-201
  
 CONFERENCE ROOMS 11-05, AND 11-18 NEED WALL OUTLETS
 INSTALLED PER 210.71(B)(1)
  
 210.71 MEETING ROOMS.
 (A) GENERAL. EACH MEETING ROOM OF NOT MORE THAN 93 M2
 (1000 FT2) IN OTHER THAN DWELLING UNITS SHALL HAVE
 OUTLETS FOR
 NONLOCKING-TYPE, 125-VOLT, 15- OR 20-AMPERE
 RECEPTACLES. THE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH 210.71(B). WHERE
 A ROOM OR SPACE IS PROVIDED WITH MOVABLE PARTITION(S),
 EACH ROOM SIZE SHALL BE DETERMINED WITH THE PARTITION
 IN THE POSITION
 THAT RESULTS IN THE SMALLEST SIZE MEETING ROOM.
 (B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER OF
 RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND
 RECEPTACLE OUTLETS IN
 FIXED FURNITURE, SHALL NOT BE LESS THAN AS DETERMINED
 IN (1) AND (2). THESE RECEPTACLE OUTLETS SHALL BE
 PERMITTED TO BE LOCATED AS
 DETERMINED BY THE DESIGNER OR BUILDING OWNER.
 (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE
 OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH
 210.52(A)(1) THROUGH (A)(4).
 (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT
 LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF
 AT LEAST 20 M2
 (215 FT2) SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 LOCATED IN THE FLOOR AT A DISTANCE NOT LESS THAN 1.8 M
 (6 FT) FROM ANY FIXED WALL
 FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR
 SPACE.

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status N Date 2022-01-19 Cont ID  
Sent By jleahy Date 2022-01-18 Time 13:22 Rev Time 0.00
Received By jleahy Date 2022-01-18 Time 07:21 Sent To  
Notes
2022-01-18 13:23:08SEPARATE LOW VOLTAGE PERMITS ARE REQUIRED JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-01-10 Cont ID  
Sent By pleduc Date 2022-01-10 Time   Rev Time 0.00
Received By pleduc Date 2022-01-10 Time 12:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-11-30 Cont ID  
Sent By pleduc Date 2021-11-30 Time   Rev Time 0.00
Received By pleduc Date 2021-11-29 Time 16:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2022-02-28 Cont ID  
Sent By medwards Date 2022-02-28 Time 15:40 Rev Time 0.00
Received By medwards Date 2022-02-24 Time 08:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2022-02-18 Cont ID  
Sent By jleahy Date 2022-02-18 Time 08:51 Rev Time 0.00
Received By jleahy Date 2022-02-07 Time 17:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2022-02-02 Cont ID  
Sent By jgomez Date 2022-02-02 Time 08:53 Rev Time 0.00
Received By jgomez Date 2022-01-30 Time 08:22 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-01-19 Cont ID  
Sent By lcrespo Date 2022-01-19 Time 08:38 Rev Time 0.00
Received By lcrespo Date 2022-01-11 Time 12:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-01-11 Cont ID  
Sent By medwards Date 2022-01-11 Time 11:46 Rev Time 0.00
Received By medwards Date 2022-01-11 Time 10:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-01-11 Cont ID  
Sent By lmarchan Date 2022-01-11 Time 09:24 Rev Time 0.00
Received By lmarchan Date 2022-01-08 Time 07:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-07 Cont ID  
Sent By medwards Date 2022-01-07 Time 11:06 Rev Time 0.00
Received By medwards Date 2022-01-05 Time 16:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-27 Cont ID  
Sent By shill Date 2021-12-27 Time 11:41 Rev Time 0.00
Received By shill Date 2021-12-23 Time 07:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-03 Cont ID  
Sent By dbattles Date 2021-12-03 Time 09:09 Rev Time 0.00
Received By dbattles Date 2021-11-23 Time 15:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-02-15 Cont ID  
Sent By medwards Date 2022-02-15 Time 09:47 Rev Time 0.00
Received By medwards Date 2022-02-15 Time 09:11 Sent To  
Notes
2022-02-15 09:48:05MECHANICAL AUDIT ONLY. ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-18 Cont ID  
Sent By medwards Date 2022-01-18 Time 09:40 Rev Time 0.00
Received By medwards Date 2022-01-18 Time 09:40 Sent To  
Notes
2022-01-18 09:42:19MECHANICAL AUDIT:
  
 WHERE ARE THE MECHANICAL VENTILATION OUTDOOR AIR
 CALCULATIONS FOR THIS TENANT SPACE? FBC M 403.3.1.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-02-16 Cont ID  
Sent By lcrespo Date 2022-02-16 Time 10:55 Rev Time 0.00
Received By lcrespo Date 2022-02-16 Time 10:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-19 Cont ID  
Sent By lcrespo Date 2022-01-18 Time 11:52 Rev Time 0.00
Received By lcrespo Date 2022-01-18 Time 11:52 Sent To  
Notes
2022-01-19 08:37:2101/19/22 1ST PLUMBING ADULT **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A1-1;
  
 A. IN THE TOILETS OF THE WOMEN'S AND MEN'S HANDICAP,
 WOULD YOU PLEASE SHOW THE TURNING SPACE OF FIVE FEET
 603.2.1, 304.3.1 CIRCULAR SPACE.
  
 B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM
 AND DIMENSIONS FOR THE LAVATORY IN OPEN SPACE, URINAL,
 WATER CLOSETS, MOTHER QUARTER, AND BREAKROOM PER THE
 2020 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 C. THE SERVICE SINK (MOP SINK, JANITORS) SURROUNDING
 THE WALL SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE
 WITH THE 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC
 SEC. P 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
  
 2. ON SHEET P-001;
  
 A. WOULD YOU PLEASE ADD TO APPLICABLE CODE THE FLORIDA
 BUILDING ACCESIBILITY, 7 TH EDITION PER THE WPB
 AMENDMENTS TO FBC 102.3 APPLICATION OF REFERENCES.
  
 B. ON GENERAL NOTE # 34, WOULD YOU PLEASE CORRECT TO
 CEMAKER, AND THE COFFEE MAKER SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2020 FBC SEC. 608.13.10.
  
 3. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE PIPPING
 THROUGH RATED WALLS OR THE FLOORS. PLEASE SUBMIT THE
 COMPLETE ASSEMBLY DETAILS FOR THE SYSTEMS PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 9 Status P Date 2022-02-28 Cont ID  
Sent By medwards Date 2022-02-28 Time 15:31 Rev Time 0.00
Received By medwards Date 2022-02-28 Time 15:31 Sent To  
Notes
2022-02-28 15:32:37PRIVATE PROVIDER AFFIDAVIT ONLY. ME

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 8 Status P Date 2022-02-10 Cont ID  
Sent By ccole Date 2022-02-10 Time 14:00 Rev Time 0.00
Received By ccole Date 2022-02-10 Time 11:41 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 7 Status F Date 2022-02-01 Cont ID  
Sent By jgomez Date 2022-02-01 Time 17:41 Rev Time 0.00
Received By jgomez Date 2022-02-01 Time 15:13 Sent To  
Notes
2022-02-01 17:42:34PRIVATE PROVIDER SEC. 553.791 F.S.
  
  
 PRIVATE PROVIDER PLAN REVIEW COMPLIANCE AFFIDAVIT
 AUDIT.
 PERMIT # 21110142
  
 (1) PRIVATE PROVIDER PLAN REVIEW COMPLIANCE AFFIDAVIT
 SIGNED ON 1/28/2020:
  
 (A)DRAWINGS E-201, M-401, P001 AND P-501 ARE MARKED AS
 "ISSUED FOR PLAN REVIEW-1/18/22".
 THE LAST REVISION SHOWN ON THESE DRAWINGS STATE "ISSUED
 FOR PERMIT 11/09/21".
 IT IS NOT CLEAR IF THESE DRAWINGS WERE REVISED FOR PLAN
 REVIEW OR NOT. IF THEY WERE REVISED, THEN THEY WERE NOT
 UPLOADED TO PROJECTDOX. REVISE AS REQUIRED TO MATCH.
  
 (B)THE REVISION DATE SHOWN ON DRAWING A7-4 FOR "ISSUED
 FOR PLAN REVIEW" IS 01/19/22. PRIVATE PROVIDER PLAN
 REVIEW COMPLIANCE AFFIDAVIT SHOWS 01/18/22. REVISE AS
 REQUIRED TO MATCH.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 6 Status P Date 2022-01-11 Cont ID  
Sent By medwards Date 2022-01-11 Time 11:46 Rev Time 0.00
Received By medwards Date 2022-01-11 Time 11:46 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 5 Status F Date 2022-01-11 Cont ID  
Sent By medwards Date 2022-01-11 Time 06:57 Rev Time 0.00
Received By medwards Date 2022-01-11 Time 06:57 Sent To  
Notes
2022-01-11 07:00:45SHEET A9-2: THE DOCUMENT LOG INDICATES THE LAST VERSION
 THAT THE PRIVATE PROVIDER REVIEWED HAS A DATE OF
 09/29/2021. THE SHEET A9-2 LATEST VERSION HAS A DATE OF
 10/01/2021. PLEASE SHOW ON THE DOCUMENT LOG THAT THE
 PRIVATE PROVIDER HAS IN FACT REVIEWED THE LATEST
 VERSION OF A9-2.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status F Date 2022-01-07 Cont ID  
Sent By medwards Date 2022-01-07 Time 11:03 Rev Time 0.00
Received By medwards Date 2022-01-07 Time 10:20 Sent To  
Notes
2022-01-07 11:03:28THERE ARE MISSING SHEETS AND THE LATEST VERSIONS ARE
 MISSING FROM THE SUBMITTED DOCUMENTS. I SENT AN EMAIL
 TO THE PRIVATE PROVIDER (CC SAMANTHA HILL, DYLAN
 BATTLES) WITH A DETAIL OF EXACTLY WHAT IS MISSING. SEE
 SUPPORTING DOCUMENTS FOR THE DETAILED DOCUMENTS FOR
 THIS AUDIT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status F Date 2021-12-27 Cont ID  
Sent By shill Date 2021-12-27 Time 11:40 Rev Time 0.00
Received By shill Date 2021-12-27 Time 11:39 Sent To  
Notes
2021-12-27 11:41:48FS553.791, AFFIDAVIT REQUIRED PRIOR TO BUILDING
 DIVISION AUDIT.
  
 AFFIDAVIT INCLUDES A9-2, INDEX ALSO INCLUDES THIS PAGE,
 BUT IT WAS NOT UPLOADED.
  
 THE DATES FOR E501, E601, E901 ARE NOT CORRECT. CHECK
 ALL AS A SPOT CHECK WAS DONE, COMMENT MAY APPLY TO
 OTHER PAGES. IT APPEARS THAT THERE IS A MORE RECENT
 VERSION OF THE PAGES THAT HAVE NOT BEEN UPLOADED.
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2021-12-03 Cont ID  
Sent By dbattles Date 2021-12-03 Time 09:06 Rev Time 0.00
Received By dbattles Date 2021-12-03 Time 09:06 Sent To  
Notes
2021-12-03 09:08:47553.791, F.S. PRIVATE PROVIDER PLAN REVIEW COMPLIANCE
 AFFIDAVIT.
 - PLEASE PROVIDE PLAN REVIEW COMPLIANCE AFFIDAVIT.
 UPLOAD INTO SUPPORTING DOCUMENTS IN PROJECTDOX.
 LIST ALL PLANS SHEETS REVIEWED AND OTHER SUPPORTING
 DOCUMENTS REVIEWED.
  
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2021-11-09 Cont ID  
Sent By dbattles Date 2021-11-09 Time 13:05 Rev Time 0.00
Received By dbattles Date 2021-11-09 Time 13:05 Sent To  
Notes
2021-11-09 13:06:44CREDENTIALS-OK
 PLAN REVIEW AFFIDAVIT TO BE REVIEWED AFTER THE OTHER
 AGENCY APPROVALS.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-02-28 Cont ID  
Sent By medwards Date 2022-02-28 Time 15:37 Rev Time 0.00
Received By medwards Date 2022-02-28 Time 15:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-02-15 Cont ID  
Sent By rmcphers Date 2022-02-15 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2022-02-15 Time 11:08 Sent To  
Notes
2022-02-15 11:10:08SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A7-4 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-18 Cont ID  
Sent By rmcphers Date 2022-01-18 Time 15:54 Rev Time 0.00
Received By rmcphers Date 2022-01-18 Time 15:54 Sent To  
Notes
***NONE***