| 2021-11-22 16:49:21 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 21101398 |
| | REVIEWED: NOVEMBER 22, 2021 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,7TH EDITION (2020) |
| | FBC[AMENDED] = 2020 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | PLEASE PROVIDE TEST REPORTS TO MEET THE FLOOR TYPE AND |
| | THICKNESS. |
| | WHAT IS THE THICHNESS OF FLOOR? |
| | WHAT IS THE MATERIAL OF FLOOR? CONCRETE? |
| | REPORTS SHOULD BE FOR PROFLEX SUPER SIM 90 |
| | |
| | 1. [FBC 1207.2]AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| | OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| | LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E90. |
| | |
| | 2. [FBC 1207.3]STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES |
| | BETWEEN DWELLING UNITS AND SLEEPING UNITS OR BETWEEN A |
| | DWELLING |
| | UNIT OR SLEEPING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN |
| | THE STRUCTURE SHALL HAVE AN IMPACT INSULATION CLASS |
| | RATING OF |
| | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| | WHEN TESTED |
| | IN ACCORDANCE WITH ASTM E492. |
| | |
| | 3. [FBC 603.1]ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | *WE HAVE SOME APPROVED REPORTS AVAILABLE SO PLEASE |
| | CONTACT ME WITH YOU FLOOR TYPE AND THICKNESS AND I CAN |
| | SEE IF WE HAVE THE REPORTS ALREADY. |
| | |
| | 4. WE ONLY HAVE ONE ELECTRICAL SHEET AND ONE PLUMBING |
| | SHEET IN THE DRAWINGS FOLDER |
| | PLEASE ADD ANY MISSING SHEETS SUCH AS DEMO AND FLOOR |
| | PLAN. |
| | ALSO, NEED MECHANICAL (SEE MECHANICAL COMMENTS) |
| | |
| | 5. PLEASE UPDATE CODE EDITION ON SHEET ID-00 TO FLORIDA |
| | BUILDING CODE 2020 7TH EDITION |
| | |