| 2021-11-05 11:19:41 | 1ST REVIEW FBC-2020 RES. BUILDING. |
| | PERMIT- 21101340 |
| | 11/5/21 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED PRODUCT APPROVAL FOR THE FLAT ROOF- |
| | FL2533-R24 IS OUTDATED. THE LATEST APPROVED REVISION |
| | THAT MUST BE SUBMITTED IS FL2533-R26. PLEASE RESUBMIT |
| | THE UPDATED PRODUCT APPROVAL WITH THE SYSTEM TO BE |
| | INSTALLED EITHER MARKED OR HIGHLIGHTED- SEE PAGES 7-75 |
| | FOR THE LISTS OF SYSTEMS AND SUBSTRATES. REFER TO PAGE |
| | 3- LIMITATIONS NOTE #9 AND BE ADVISED THAT ENHANCED |
| | BASE SHEET CALCULATIONS AND FASTENING MAY BE REQUIRED |
| | FOR THE ELEVATED PRESSURES ZONES 2 & 3 (PERIMETERS AND |
| | CORNERS). THE CALCULATIONS SHALL BE PREPARED BY A FL. |
| | LICENSED DESIGN PROFESSION-TYPICALLY A STRUCTURAL |
| | ENGINEER. |
| | |
| | 2) FL. APPROVAL FL26482-R6 SHINGLE UNDERLAYMENT: YOU |
| | HAVE SUBMITTED THE EVALUATION REPORT FOR HVHZ. WEST |
| | PALM BEACH IS NON-HVHZ. PLEASE SUBMIT THE NON-HVHZ |
| | REPORT MARKED OR HIGHLIGHTED TO SHOW WHICH UNDERLAYMENT |
| | PRODUCT WILL BE INSTALLED- RULE 9N-3 FAC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |