| 2021-11-09 13:52:49 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE |
| | REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS |
| | APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT |
| | |
| | 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED |
| | EGRESS |
| | DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS |
| | SHALL BE |
| | PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL |
| | LOCKING SYSTEMS |
| | RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED |
| | THAT ALL OF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF |
| | THE ELECTRICAL |
| | LOCK IS AFFIXED TO THE DOOR LEAF. |
| | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY |
| | OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING |
| | CONDITIONS. |
| | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| | HAND IN THE |
| | DIRECTION OF EGRESS. |
| | (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE |
| | POWER SUPPLY TO |
| | THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE |
| | DIRECTION |
| | OF EGRESS. |
| | (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| | AUTOMATICALLY ELECTRICALLY |
| | UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| | ACCORDANCE WITH |
| | ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS. |
| | |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF CARD READERS WITHIN THE |
| | STAIRWELL. |
| | |
| | |
| | 7.2.1.5.8.1 DOOR ASSEMBLIES ON STAIR ENCLOSURES SHALL |
| | BE PERMITTED TO |
| | BE EQUIPPED WITH HARDWARE THAT PREVENTS RE-ENTRY INTO |
| | THE INTERIOR OF THE |
| | BUILDING, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA |
| | ARE MET: |
| | (1) THERE SHALL BE NOT LESS THAN TWO LEVELS WHERE IT IS |
| | POSSIBLE TO LEAVE |
| | THE STAIR ENCLOSURE TO ACCESS ANOTHER EXIT. |
| | (2) THERE SHALL BE NOT MORE THAN FOUR STORIES |
| | INTERVENING BETWEEN |
| | STORIES WHERE IT IS POSSIBLE TO LEAVE THE STAIR |
| | ENCLOSURE TO ACCESS |
| | ANOTHER EXIT. |
| | (3) RE-ENTRY SHALL BE POSSIBLE ON THE TOP STORY OR |
| | NEXT-TO-TOP STORY |
| | SERVED BY THE STAIR ENCLOSURE, AND SUCH STORY SHALL |
| | ALLOW ACCESS TO |
| | ANOTHER EXIT. |
| | (4) DOOR ASSEMBLIES ALLOWING RE-ENTRY SHALL BE |
| | IDENTIFIED AS SUCH ON |
| | THE STAIR SIDE OF THE DOOR LEAF. |
| | (5) DOOR ASSEMBLIES NOT ALLOWING RE-ENTRY SHALL BE |
| | PROVIDED WITH A |
| | SIGN ON THE STAIR SIDE INDICATING THE LOCATION OF THE |
| | NEAREST DOOR |
| | OPENING, IN EACH DIRECTION OF TRAVEL, THAT ALLOWS |
| | RE-ENTRY OR EXIT. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |