Plan Review Details - Permit 21101200
Plan Review Stops For Permit 21101200
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-02-11 Cont ID  
Sent By cpuell Date 2022-02-11 Time 11:08 Rev Time 0.00
Received By cpuell Date 2022-02-11 Time 11:08 Sent To  
Notes
2022-02-11 11:09:05ADDRESS CHANGED TO 128 PALMETTO LN, UPDATED PERMIT.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-02-02 Cont ID  
Sent By cpuell Date 2022-02-02 Time 10:59 Rev Time 0.00
Received By cpuell Date 2022-02-02 Time 10:59 Sent To  
Notes
2022-02-02 11:00:07PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-10-29 Cont ID  
Sent By cpuell Date 2021-10-29 Time 15:45 Rev Time 0.00
Received By cpuell Date 2021-10-29 Time 15:45 Sent To  
Notes
2021-10-29 15:47:22A NEW ADDRESS BASED ON THE CITY'S ROAD CENTER LINES AND
 THE FRONT MAIN ENTRANCE WILL NEED TO BE ESTABLISHED.
 BASED ON THE PLANS YOU HAVE SUBMITTED; I AM PROPOSING
 EITHER 128 PALMETTO LN OR 130 PALMETTO LN. PLEASE HAVE
 THE OWNERS REVIEW THESE OPTIONS AND LET ME KNOW. PLEASE
 RESPOND TO [email protected] OR CALL 561-805-6659.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-08-13 Cont ID  
Sent By cthroop Date 2022-08-13 Time 10:40 Rev Time 0.00
Received By cthroop Date 2022-08-13 Time 09:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-07-19 Cont ID  
Sent By pvalenti Date 2022-07-19 Time 17:11 Rev Time 0.00
Received By pvalenti Date 2022-07-19 Time 15:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-06-14 Cont ID  
Sent By cthroop Date 2022-06-14 Time 13:01 Rev Time 0.00
Received By cthroop Date 2022-06-10 Time 16:27 Sent To  
Notes
2022-06-14 13:13:04BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
 CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17
  
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1. CORRECTED
  
 2. (ONLY THE COVER SHEETS FOR FL5822-R8 WERE SUBMITTED
 FOR REVIEW)
  
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 NOTE: DESIGNER SHALL SELECT MODEL OF SMART VENT TO BE
 INSTALLED.
  
 3. CORRECTED.
  
 4. PROVIDE A STRUCTURAL DETAIL OF THE UNDER-SLAB
 CHANNELS CONNECTING THE SMART VENTS TO THE GARAGE FLOOR
 AREA. INCLUDE A DETAIL OF HOW THE CHANNEL COMMUNICATES
 WITH THE GARAGE,
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 (PLEASE PROVIDE A FEMA REFERENCE ON THE USE AND
 INSTALLATION OF THESE CHANNELS) (PLEASE REVIEW FEMA
 NFIP TECHNICAL BULLETIN #1)
  
 5. CORRECTED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-10 Cont ID  
Sent By cthroop Date 2022-03-10 Time 16:54 Rev Time 0.00
Received By cthroop Date 2022-03-02 Time 10:26 Sent To  
Notes
2022-03-10 17:15:15BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
 CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17
  
  
 2ND REVIEW
  
 RESULTS: DENIED
  
  
 NOTICE: THIS PROJECT IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA (SFHA). THE STRUCTURE IS LOCATED WITHIN TWO
 AE FLOOD ZONES WITH BASE FLOOD ELEVATIONS (BFE) OF
 6'0"NAVD AND 7'0" NAVD. THE CITY OF WEST PALM BEACH
 (THROUGH ORDINANCE NO. 4729-17) REQUIRES AN ADDITIONAL
 24 INCHES OF FREEBOARD. THE DESIGN FLOOD ELEVATION
 (DFE) SHALL BE AT OR ABOVE 9'0"NAVD.
  
 CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17
 SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT
 CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE
 II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL
 AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH
 SHALL READ AS FOLLOWS:
  
 SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 R322.2.1 ELEVATION REQUIREMENTS.
 1. BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT
 DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST
 FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION
 PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER
 IS HIGHER.
  
 1. NOTE ON PLAN PAGE C-1 STATES "EQUIPMENT SHALL BE AT
 OR ABOVE 8.00' NAVD". EQUIPMENT SERVICING THE BUILDING
 SHALL BE AT OR ABOVE THE DFE ELEVATION OF 9.00' NAVD.
 PLEASE CORRECT.
 BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT
 DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST
 FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION
 PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER
 IS HIGHER.
  
 2. PRODUCT APPROVAL FL 5822-R7 FOR SMART VENTS HAS
 EXPIRED.
 1.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVAL FOR THE PROPOSED SMART VENTS.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 NOTE: DESIGNER SHALL SELECT MODEL OF SMART VENT TO BE
 INSTALLED.
  
 3. IDENTIFY THE SMART VENT MODEL TO BE INSTALLED NEXT
 TO THE PEDESTRIAN GARAGE DOOR.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. PROVIDE A STRUCTURAL DETAIL OF THE UNDER-SLAB
 CHANNELS CONNECTING THE SMART VENTS TO THE GARAGE FLOOR
 AREA. INCLUDE A DETAIL OF HOW THE CHANNEL COMMUNICATES
 WITH THE GARAGE,
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 REF. PLAN PAGE A104 FOR THE FOLLOWING COMMENTS:
 5. BASED ON THE RECESSED FLOOR DESIGN, THE SCREENING
 ROOM WILL BE AT 7.00' NAVD. THE LOWEST FLOOR SHALL BE
 AT OR ABOVE THE BFE PLUS 2.00' PER R322.2.1. FF ELEV.
 SHALL BE 9.00' NAVD.
 BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT
 DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST
 FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION
 PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER
 IS HIGHER.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-03 Cont ID  
Sent By cthroop Date 2022-01-03 Time 15:02 Rev Time 0.00
Received By cthroop Date 2021-12-30 Time 08:45 Sent To  
Notes
2022-01-03 15:52:55BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
 CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17
  
  
 1ST REVIEW
  
 RESULTS: DENIED
  
  
 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE STRUCTURE IS LOCATED WITHIN TWO AE
 FLOOD ZONES WITH BASE FLOOD ELEVATIONS (BFE) OF
 6'0"NAVD AND 7'0" NAVD. THE CITY OF WEST PALM BEACH
 (THROUGH ORDINANCE NO. 4729-17) REQUIRES AN ADDITIONAL
 24 INCHES OF FREEBOARD. THE DESIGN FLOOD ELEVATION
 (DFE) SHALL BE AT OR ABOVE 9'0"NAVD.
  
 CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17
 SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT
 CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE
 II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL
 AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH
 SHALL READ AS FOLLOWS:
  
 SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 R322.2.1 ELEVATION REQUIREMENTS.
 1. BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT
 DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST
 FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION
 PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER
 IS HIGHER.
  
 2.PLACE THE FINISHED FLOOR ELEVATION (FFE) OF THE MAIN
 DWELLING UNIT AND THE ATTACHED GARAGE ON THE SITE PLAN,
 THE FLOOR PLAN AND THE FOUNDATION PLAN.
  
 3. NOTICE: THE GARAGE FLOOR IS BELOW THE DFE OF 9'0"
 NAVD.
 FLOOD OPENINGS ARE REQUIRED.
 R322.2.2ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION.
 ENCLOSED AREAS, INCLUDING CRAWL SPACES, THAT ARE BELOW
 THE DESIGN FLOOD ELEVATION SHALL:
 1. 1.BE USED SOLELY FOR PARKING OF VEHICLES, BUILDING
 ACCESS OR STORAGE.
 2. 2.BE PROVIDED WITH FLOOD OPENINGS THAT MEET THE
 FOLLOWING CRITERIA AND ARE INSTALLED IN ACCORDANCE WITH
 SECTION R322.2.2.1:
 1. 2.1.THE TOTAL NET AREA OF NON-ENGINEERED OPENINGS
 SHALL BE NOT LESS THAN 1 SQUARE INCH (645 MM2) FOR EACH
 SQUARE FOOT (0.093 M2) OF ENCLOSED AREA WHERE THE
 ENCLOSED AREA IS MEASURED ON THE EXTERIOR OF THE
 ENCLOSURE WALLS, OR THE OPENINGS SHALL BE DESIGNED AS
 ENGINEERED OPENINGS AND THE CONSTRUCTION DOCUMENTS
 SHALL INCLUDE A STATEMENT BY A REGISTERED DESIGN
 PROFESSIONAL THAT THE DESIGN OF THE OPENINGS WILL
 PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD FORCES ON
 EXTERIOR WALLS BY ALLOWING FOR THE AUTOMATIC ENTRY AND
 EXIT OF FLOODWATERS AS SPECIFIED IN SECTION 2.7.2.2 OF
 ASCE 24.
 2. 2.2.OPENINGS SHALL BE NOT LESS THAN 3 INCHES (76 MM)
 IN ANY DIRECTION IN THE PLANE OF THE WALL.
 3. 2.3.THE PRESENCE OF LOUVERS, BLADES, SCREENS AND
 FACEPLATES OR OTHER COVERS AND DEVICES SHALL ALLOW THE
 AUTOMATIC FLOW OF FLOODWATER INTO AND OUT OF THE
 ENCLOSED AREAS AND SHALL BE ACCOUNTED FOR IN THE
 DETERMINATION OF THE NET OPEN AREA.
  
  
 OPTION:
 ENGINEERED FLOOD VENTS
  
 1) PROVIDE ENGINEERED FLOOD VENTS. (SMART VENTS)
 2) ATTACH A COPY OF THE INDIVIDUAL ENGINEERED FLOOD
 VENT CERTIFICATION OR EVALUATION SERVICE REPORT ISSUED
 BY THE INTERNATIONAL CODE COUNCIL EVALUATION SERVICE
 (ICC ES).
 3) PROVIDE FLORIDA PRODUCT APPROVALS FOR PROPOSED SMART
 VENTS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE
 9N-3 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD.
 5) FLOOD OPENINGS SHALL BE INSTALLED PER
 R322.2.2.1INSTALLATION OF OPENINGS:
 6) SHOW NUMBER AND LOCATION OF FLOOD OPENINGS ON
 FOUNDATION PLAN. INCLUDE THE FLORIDA PRODUCT APPROVAL
 NUMBER AND IDENTIFY THE VENT MODEL TO BE INSTALLED.
 R322.2.2.1INSTALLATION OF OPENINGS.
 THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS
 INSTALLED SUCH THAT:
 1. 1.THERE SHALL BE NOT LESS THAN TWO OPENINGS ON
 DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING
 HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD
 ELEVATION, EACH AREA SHALL HAVE OPENINGS.
 2. 2.THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN
 1 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR
 GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE
 IMMEDIATELY UNDER EACH OPENING.
 3. 3.OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN
 DOORS AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED
 OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION.
  
 FEMA TECHNICAL BULLETIN #1
 LOCATION OF FLOOD OPENINGS
 THE IRC AND IBC (BY REFERENCE TO ASCE 24) REQUIRE FLOOD
 OPENINGS ?ON DIFFERENT SIDES OF EACH ENCLOSED AREA?
 (IRC R322.2.2.1) AND ?IN AT LEAST TWO WALLS OF EACH
 ENCLOSED AREA? (ASCE 24, SECTION 2.7.3).
  
  
 4. NOTE: PLAN PAGE C-1 INDICATES FOUR FLOOD VENTS ARE
 INSTALLED WITH UNDER SLAB CHANNELS.
 PROVIDE A DETAIL OF THE CHANNELS AND A REFERENCE TO THE
 FEMA REGULATION THAT ALLOWS THIS TYPE OF INSTALLATION.
  
  
 NOTICE: SUBMIT THE FOLLOWING ELEVATION CERTIFICATES, AS
 REQUIRED. (SEE NFIP REVIEW COMMENTS)
  
 THREE ELEVATION CERTIFICATES (EC) ARE REQUIRED
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  
 5. REF. SITE PLAN PAGE C-1 FOR THE FOLLOWING COMMENT:
 EQUIPMENT SERVICING THE BUILDING SHALL BE AT OR ABOVE
 9'0" NAVD. PLEASE CORRECT.
  
 6. REF. PLAN PAGES S-101 AND C-1 FOR THE FOLLOWING
 COMMENT: PG. S-101 INDICATES TOS TO BE 9'0". PG. C-1
 INDICATES TOS TO BE 8.83' WITH FINISHED FLOOR TO BE
 9'0" NAVD. PLEASE CLARIFY.
  
 7. PROVIDE COVER SHEETS FOR ALL PRODUCT APPROVALS
 SUBMITTED FOR REVIEW.
 PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER
 SHEETS; THEY SHOW THE APPROVAL NUMBER, CODE VERSION,
 AND STATUS, FBC R 301. (MIAMI DADE NOAS ARE OK, DO NOT
 NEED FL COVER PAGE).
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 8. PROVIDE PRODUCT APPROVALS FOR THE WINDOW MULLIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 9. PROVIDE THE ICC-ES REPORT FOR THE SPRAY APPLIED
 INSULATION.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 10. REF. PLAN PAGE S003 FOR THE FOLLOWING COMMENT:
 PROVIDE A ROOF SHEATHING FASTENER SCHEDULE BASED ON THE
 CALCULATED DESIGN PRESSURES.
 PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN
 PRESSURES.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 NOTICE: PROVISO'S
 PLAN PAGE C-1; SITE WALLS REQUIRE A SEPERATE PERMIT.
 PLAN PAGE L1.1; POOL REQUIRES A SEPERATE PERMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-08-13 Cont ID  
Sent By cthroop Date 2022-08-13 Time 10:43 Rev Time 0.00
Received By cthroop Date 2022-08-13 Time 09:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-02-10 Cont ID  
Sent By fgiaquin Date 2022-02-10 Time 20:51 Rev Time 0.00
Received By fgiaquin Date 2022-02-10 Time 20:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-11 Cont ID  
Sent By fgiaquin Date 2021-12-11 Time 21:54 Rev Time 0.00
Received By fgiaquin Date 2021-12-11 Time 20:35 Sent To  
Notes
2021-12-11 21:54:31ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO SMOKE/CO ALARMS SHOWN ON PLAN FBC-R 314 AND 315
  
 2. PROVIDE NOTE ON PLANS GENERATOR AND LOW VOLTAGE
 SHOWN ON PLAN REQUIRE SEPARATE PERMITS. FBC 105.1 FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2023-04-13 Cont ID  
Sent By fgiaquin Date 2023-04-13 Time 13:19 Rev Time 0.00
Received By fgiaquin Date 2023-04-13 Time 13:19 Sent To  
Notes
2023-04-13 13:19:35LV/DATA ONLY

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-11-20 Cont ID  
Sent By abelisle Date 2021-11-20 Time 17:35 Rev Time 0.00
Received By abelisle Date 2021-11-20 Time 17:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-08-18 Cont ID  
Sent By lmarchan Date 2022-08-18 Time 12:42 Rev Time 0.00
Received By lmarchan Date 2022-08-12 Time 09:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-22 Cont ID  
Sent By lmarchan Date 2022-07-22 Time 16:37 Rev Time 0.00
Received By lmarchan Date 2022-06-29 Time 15:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-14 Cont ID  
Sent By cthroop Date 2022-06-14 Time 13:26 Rev Time 0.00
Received By cthroop Date 2022-04-20 Time 16:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-22 Cont ID  
Sent By lmarchan Date 2022-03-22 Time 16:46 Rev Time 0.00
Received By lmarchan Date 2022-01-31 Time 15:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-03 Cont ID  
Sent By cthroop Date 2022-01-03 Time 15:53 Rev Time 0.00
Received By cthroop Date 2021-11-02 Time 07:13 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-08-24 Cont ID  
Sent By lmarchan Date 2022-08-24 Time 15:56 Rev Time 0.00
Received By lmarchan Date 2022-07-19 Time 11:24 Sent To  
Notes
2022-08-15 10:55:36MU-2022-034093-0000 - $12,071.20 PAID AO
2022-07-19 11:25:097/19/22 EMAILED IMPACT FOR REVIEW PER REG-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-01-03 Cont ID  
Sent By cthroop Date 2022-01-03 Time 09:45 Rev Time 0.00
Received By cthroop Date 2022-01-03 Time 09:45 Sent To  
Notes
2022-01-03 09:45:58IMPACT FEE QUESTIONNAIRE
  
 PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-05-04 Cont ID  
Sent By medwards Date 2022-05-04 Time 07:59 Rev Time 0.00
Received By medwards Date 2022-05-04 Time 07:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-02-09 Cont ID  
Sent By medwards Date 2022-02-09 Time 13:37 Rev Time 0.00
Received By medwards Date 2022-02-09 Time 11:15 Sent To  
Notes
2022-02-10 08:36:451ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21101200
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN THE SUPPORTING DOCUMENTS FOLDER THERE ARE 2 FILES
 NAMED ENERGY CALCULATIONS, ONE IS NAMED ENERGY
 CALCULATIONS ? V2 DATED 1/31/2022, THE OTHER IS NAMED
 ENERGY CALCLATIONS DATED 10/26/2021. THE FILE DATED
 10/26/2021 IS IN FACT THE ENERGY CALCULATIONS. THE ONE
 DATED 1/31/2022 IS LABELED WRONG AS IT IS THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS. PLEASE
 CORRECT THIS.
  
 2) SHEET M101: THERE IS A NOTE THAT READS FINAL DUCT
 ARRANGEMENTS RESERVED PENDING STRUCTURAL COORDINATION.
 PLEASE PROVIDE THE FINAL DOCUMENTS AS WE SHOULD BE
 REVIEWING THE FINAL CODE COMPLIANT DRAWINGS. IF THESE
 ARE THE FINAL DRAWINGS THEN PLEASE REMOVE THE NOTE. FBC
 107.2.1
  
 3) PLEASE MAKE THE RETURN AIR PATH CLEAR IN ALL AREAS.
 AHU-1-01 APPEARS TO HAVE THE RETURN TO THE RIGHT SIDE
 OF THE CLOSET WITH THE LEFT SIDE OF THE UNIT BEING THE
 SUPPLY SIDE. F12 IS LEAVING THE RIGHT SIDE OF THIS UNIT
 BUT THE ARROWS INDICTING THE FLOW SHOWS IT IS SUPPLYING
 AIR TO THE GUEST SUITE 1. F9 DUCT IS LEAVING FROM THE
 LEFT SIDE OF THE UNIT THAT INDICATES A FLOW TO THE
 GUEST SUITE 1 BUT THE ARROW AT THE DIFFUSER INDICATES
 THE FLOW IS RETURNING BACK TO THE UNIT. FBC 107.2.1
  
 4) PLEASE SHOW THE CONDENSATE DRAIN PIPE SIZES FOR EACH
 SECTION OF PIPE. IT APPEARS THAT ALL PIPE SIZES LEAVING
 EACH UNIT IS 1 INCH BUT THE ONLY REFERENCE TO THE
 DRAINAGE SYSTEM SIZE IS AT THE CONDENSATE GOOSENECK ON
 THE EXTERIOR OF THE BUILDING WHICH IS 2 INCH PVC. FBC
 RES M1411.3.2
  
 5) PLEASE SHOW THE CALCULATIONS FOR THE CONDENSATE PIPE
 SIZING BASED ON FBC M TABLE 307.2.2
  
 6) PLEASE SHOW HOW THIS CONDENSATE DRAINAGE DESIGN WILL
 BE CODE COMPLIANT WITH THE DRAIN LINE MAINTENANCE OF
 FBC RES M1411.3.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2022-02-09 13:38:13 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-09 Cont ID  
Sent By medwards Date 2021-11-09 Time 09:42 Rev Time 0.00
Received By medwards Date 2021-11-09 Time 09:42 Sent To  
Notes
2021-11-09 09:42:301ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21101200
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS HAVE
 ONLY 8 SHEETS OUT OF 61. PLEASE SUBMIT THE ENTIRE
 DOCUMENT FOR REVIEW. FBC 107.2.1
  
 2) PLEASE SHOW ON THE DRAWING THAT THE COMBUSTION AIR
 GRILL IS A MINIMUM OF 10 FT AWAY FROM THE GENERATOR
 EXHAUST. FBC 107.2.1
  
 3) PLEASE SHOW THE EXHAUST FAN FOR THE SHOWER AREA FOR
 THE SUITE 3 BATHROOM. FBC RES M1507.4
  
 4) PLEASE SHOW THE SIZE AND MATERIAL USED FOR THE
 CONDENSATE PIPING. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2022-07-19 Cont ID  
Sent By pvalenti Date 2022-07-19 Time 16:23 Rev Time 0.00
Received By pvalenti Date 2022-07-19 Time 15:34 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2022-06-14 Cont ID  
Sent By cthroop Date 2022-06-14 Time 13:13 Rev Time 0.00
Received By cthroop Date 2022-06-10 Time 16:27 Sent To  
Notes
2022-06-14 13:26:26NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
  
 1ST REVIEW OF THE CONSTRUCTION DRAWING ELEVATION
 CERTIFICATE
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. LINE A1-OWNERS NAME IS MISSING.
  
 2. LINE B1-THE COMMUNITY NAME AND NUMBER ENTERED DO NOT
 APPEAR ON FIRM PANEL 12099C 0591 F. THE COMMUNITY NAME
 SHOULD BE PALM BEACH COUNTY AND THE COMMUNITY NUMBER
 SHOULD BE 120192.
  
 3. LINE C2(B)-2ND FLOOR ELEVATION DATA MISSING.
  
 4. C2(H)-GRADE ELEVATION DATA MISSING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2022-03-02 Cont ID  
Sent By cthroop Date 2022-03-02 Time 17:03 Rev Time 0.00
Received By cthroop Date 2022-03-02 Time 10:26 Sent To  
Notes
2022-03-02 17:05:19NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE STRUCTURE IS LOCATED WITHIN TWO AE
 FLOOD ZONES WITH BASE FLOOD ELEVATIONS (BFE) OF
 6'0"NAVD AND 7'0" NAVD. THE CITY OF WEST PALM BEACH
 (THROUGH ORDINANCE NO. 4729-17) REQUIRES AN ADDITIONAL
 24 INCHES OF FREEBOARD. THE DESIGN FLOOD ELEVATION
 (DFE) SHALL BE AT OR ABOVE 9'0"NAVD.
  
 CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17
 SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT
 CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE
 II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL
 AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH
 SHALL READ AS FOLLOWS:
  
 SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 R322.2.1 ELEVATION REQUIREMENTS.
 1. BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT
 DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST
 FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION
 PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER
 IS HIGHER.
  
 2. PROVIDE A CONSTRUCTION DRAWING ELEVATION CERTIFICATE
 FOR REVIEW.
 FEMA
  
 NOTICE:
  
 THREE ELEVATION CERTIFICATES (EC) ARE REQUIRED
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-01-03 Cont ID  
Sent By cthroop Date 2022-01-03 Time 14:53 Rev Time 0.00
Received By cthroop Date 2021-12-30 Time 08:45 Sent To  
Notes
2022-01-03 15:02:45SEE COMMENTS UNDER BLDG. REVIEW. EC REQUIRED. CT
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-11-20 Cont ID  
Sent By abelisle Date 2021-11-20 Time 17:35 Rev Time 0.00
Received By abelisle Date 2021-11-20 Time 15:32 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-07-26 Cont ID  
Sent By dbattles Date 2022-07-26 Time 14:43 Rev Time 0.00
Received By dbattles Date 2022-07-26 Time 14:43 Sent To  
Notes
2022-07-26 14:45:04APPROVED FOR PP INSPECTIONS, ADJUSTED FEE AND UPLOADED
 NTBO AND SUPPORTING DOCS TO PROJECTDOX

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2022-01-03 Cont ID  
Sent By cthroop Date 2022-01-03 Time 14:21 Rev Time 0.00
Received By cthroop Date 2021-12-30 Time 08:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-08-13 Cont ID  
Sent By cthroop Date 2022-08-13 Time 10:39 Rev Time 0.00
Received By cthroop Date 2022-08-13 Time 09:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-07-19 Cont ID  
Sent By pvalenti Date 2022-07-19 Time 16:12 Rev Time 0.00
Received By pvalenti Date 2022-07-19 Time 15:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-14 Cont ID  
Sent By cthroop Date 2022-06-14 Time 13:00 Rev Time 0.00
Received By cthroop Date 2022-06-10 Time 16:27 Sent To  
Notes
2022-05-04 08:00:01MECHANICAL DIGITALSIGNATURES APPROVED. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-10 Cont ID  
Sent By cthroop Date 2022-03-10 Time 07:51 Rev Time 0.00
Received By cthroop Date 2022-03-02 Time 10:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-03 Cont ID  
Sent By cthroop Date 2022-01-03 Time 09:45 Rev Time 0.00
Received By cthroop Date 2021-12-30 Time 08:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 6 Status P Date 2022-08-24 Cont ID  
Sent By ajones Date 2022-08-24 Time 12:24 Rev Time 0.00
Received By ajones Date 2022-08-24 Time 12:24 Sent To  
Notes
2022-08-24 12:26:448/24/22- PASSED WITH THE PROVISO THAT A REVISION IS
 SUBMITTED BEFORE THE FIRST INSPECTION BEYOND THE
 FOUNDATION IS CALLED IN ADDRESSING ZONING COMMENTS
 DATED 08/18/22.
  
 ANGELLA VANN, AICP
 PLANNING AND ZONING ADMINISTRATOR

Review Stop Z ZONING
Rev No 5 Status F Date 2022-08-18 Cont ID  
Sent By eschneid Date 2022-08-18 Time 12:01 Rev Time 0.50
Received By eschneid Date 2022-08-18 Time 11:07 Sent To  
Notes
2022-08-18 12:01:31FAILED
  
 1) CHIMNEYS ARE PERMITTED TO EXCEED THE DISTRICT HEIGHT
 REQUIREMENTS BY 10 PERCENT, WHICH WOULD PERMIT THE
 CHIMNEY AT THIS LOCATION TO BE 33 FEET ABOVE FINISHED
 GRADE. THIS CHIMNEY HEIGHT ALLOWANCE IS STATED ON THE
 A-201, YET THE CHIMNEY IS SHOWN AS 33 FEET 1 INCH IN
 HEIGHT, WHICH EXCEEDS THE PERMITTED HEIGHT ALLOWANCE.
 THE PLANS MUST SHOW CODE COMPLIANT CONDITIONS.
  
 2) UPDATED REPEAT COMMENT: SHEET L1.0 AND SHEET A-100
 SHOW THE SAME CONDITIONS; HOWEVER, THEY DO NOT MATCH
 SHEET C-1 OR S-101 (WHICH MATCH EACH OTHER). ALL PLANS
 MUST SHOW CONSISTENT, ACCURATE, CODE COMPLIANT
 CONDITIONS.
  
 3) SEPARATE PERMITS ARE REQUIRED FOR THE ITEMS LISTED
 BELOW. PLEASE NOTE THAT STAFF HAS NOT FULLY REVIEWED
 ANY OF THE ITEMS AS PART OF THIS PERMIT APPLICATION TO
 VERIFY THAT THE INFORMATION SHOWN COMPLIES WITH CODE
 BUT HAS NOTED SOME ITEMS AS LISTED. THIS PERMIT REVIEW
 IS ONLY FOR THE HOUSE.
  
 A. IRRIGATION
 B. POOL - THE POOL CONFIGURATION HAS BEEN CHANGED. FULL
 COMPLIANCE REVIEW WILL BE WITH THE REQUIRED POOL
 PERMIT.
 C. GENERATOR
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 4 Status F Date 2022-07-22 Cont ID  
Sent By eschneid Date 2022-07-22 Time 16:30 Rev Time 2.00
Received By eschneid Date 2022-07-21 Time 10:06 Sent To  
Notes
2022-07-22 16:31:01FAILED
  
 1) UPDATED COMMENT: STAFF WILL ACCEPT YOUR WEIGHTED
 AVERAGE METHODOLOGY; HOWEVER, THE COMMENTS MUST BE
 ADDRESSED TO SATISFY STAFF THAT THE HOUSE DOES NOT
 EXCEED THE MAXIMUM HEIGHT ALLOWANCE.
  
 A. SHEET A-202 WAS NOT INCLUDED (SHEET A-201 WAS
 UPLOADED IN ITS PLACE), SO STAFF WAS UNABLE TO VERIFY
 THE UPDATED AVERAGE GRADE CALCULATION TABLE AND THE
 SHEET A-100 INFORMATION FOR THE EAST SIDE OF THE
 BUILDING.
 B. THANK YOU FOR PROVIDING ELEVATION TAGS ALONG THE
 SOUTH ELEVATION DRAWING TO MIRROR THE TAGS ON SHEET
 A-100. THE NORTH, EAST AND WEST ELEVATION DRAWINGS MUST
 ALSO INCLUDE THESE TAGS SO THAT STAFF CAN VERIFY THE
 MEASURE POINTS WITHOUT NEEDING TO SCALE THE PLAN. WHEN
 SCALING THE PLAN, THE WEST GRADE ELEVATION AT THE WEST
 GUEST 1 (LOWER) AND WEST LAUNDRY (HIGHER) DO NOT MATCH
 THE TABLE OR SHEET A-100.
 C. THE SOUTH ELEVATION DRAWING LISTS THE 1ST FLOOR SLAB
 AT 9.00 NAVD. HOWEVER, THE GRADE TAGS (ALSO SHOWN ON
 SHEET C-1) AND THE GRADE CROSS HATCH ARE SHOWN ABOVE
 THIS 9-FOOT MARK. THE GRADE THAT THE SLAB SITS ON
 CANNOT BE HIGHER THAN THE TOP OF THE SLAB (AS EVIDENCED
 BY SHEET S-411). ADDITIONALLY, THE AVERAGE FINISHED
 GRADE IS NOT MEASURED FROM THE TOP OF THE POOL DECK
 PAVERS, WHICH ARE THE VALUES USED BASED ON SHEET C-1).
 THE BUILDING HEIGHT IS MEASURED FROM THE AVERAGE
 FINISHED GRADE.
 D. PLEASE EXPLAIN WHY THE NORTH ENTRY (37.83 LINEAR
 FEET AT 6.29 FEET ELEVATION) DOES NOT INCLUDE THE LOWER
 HEIGHTS SHOWN ADJACENT TO THE NORTH ENTRY WALL ON THE
 WEST LIB POWDER AND EAST ? GUEST BATH (5.97 FEET
 ELEVATION) FOR APPROXIMATELY 19 OF THE 38 FEET. THIS
 WILL BRING THE 6.29-FOOT MEASURE DOWN.
  
 2) UPDATED COMMENT: THERE ARE TWO SEPARATE KITCHEN
 AREAS SHOWN, WHICH IS NOT PERMITTED IN A SINGLE-FAMILY
 HOUSE. **** ALL SHEETS NEED TO BE UPDATED TO REFLECT
 THE REMOVAL OF THE OVEN IN THE BUTLER PANTRY, INCLUDING
 THE PIPING PLANS, THE POWER PLANS, THE ELECTRIC
 SCHEDULES, AND THE MECHANICAL PLANS. -- ZONING WILL NOT
 PASS THIS PERMIT UNTIL ALL PLANS REMOVE THE 2ND OVEN OR
 INCLUDE THE NOTE THAT THERE WILL BE NO OVEN IN THE
 BUTLER KITCHEN. HOWEVER, THE ELECTRIC SCHEDULE AND THE
 POWER PLAN MUST BE REVISED SHOW THE REMOVAL OF THE OVEN
 CIRCUIT, 240 OUTLET AND OVEN.
  
 3) THE NEWLY SUBMITTED SHEET L1.0 SITE PLAN DOES NOT
 MATCH THE APPROVED LANDSCAPE PERMIT PLAN, NOR DOES IT
 MATCH THE LAYOUT SHOW ON SHEETS A-100 ARCHITECTURAL
 SITE PLAN, C-1 SITE PLAN THE ELEVATION PLANS, AND S-101
 FOUNDATION PLAN. ALL PLANS MUST SHOW THE SAME,
 ACCURATE, CODE COMPLIANT CONDITIONS. NOTE: SHEET C-1
 WAS NOT UPDATED TO REFLECT LATEST CHANGES, SO STAFF IS
 UNABLE TO VERIFY CODE COMPLIANCE.
  
 4) THE NEW SHEET L1.0 SHOWS A BBQ AREA AND OUTDOOR
 SHOWER ON SCREENING WALL AND EXTENDED DECK WITHIN THE
 REQUIRED FIVE-FOOT SIDE SETBACK. PROVIDE DETAILS ON
 EACH OF THESE ITEMS.
  
 A. IF THE PAVED DECK IS LESS THAN 18 INCHES ABOVE
 GRADE, IT MAY NOT BE LOCATED CLOSER THAN TWO FEET FROM
 THE PROPERTY LINE. THIS WAS A COMMENT MADE UPON THE
 FIRST PLAN REVIEW FOR THIS LOCATION, WAS CORRECTED AND
 NOW APPLIES AGAIN.
 B. A FIXED BBQ GRILL IS AN ACCESSORY STRUCTURE AND MUST
 CONFORM TO THE REQUIRED MINIMUM SETBACKS.
 C. THE SHOWER SCREEN WALL MAY NOT EXCEED SIX FEET ABOVE
 THE GRADE OF THE PROPERTY TO THE SOUTH. THE SURVEY AND
 SHEET C-1 INDICATE THAT THE EXISTING GRADE AT THE
 PROPERTY LINE IN THIS LOCATION IS 3.4 FEET, WITH THE
 PROPOSED DECK ELEVATION AT JUST UNDER NINE FEET. THIS
 PROHIBITS ANY ADDITIONAL WALL HEIGHT AT THIS LOCATION.
 D. NONE OF THE PIPING PLANS INCLUDE THIS NEW LAYOUT.
  
 5) PLEASE DESCRIBE WHAT THE STORAGE RACK THAT IS NOW
 SHOWN ON THE SOUTH SIDE OF THE BUILDING WILL BE USED
 FOR AND PROVIDE AN ELEVATION DRAWING.
  
 6) SEPARATE PERMITS ARE REQUIRED FOR THE ITEMS LISTED
 BELOW. PLEASE NOTE THAT STAFF HAS NOT FULLY REVIEWED
 ANY OF THE ITEMS AS PART OF THIS PERMIT APPLICATION TO
 VERIFY THAT THE INFORMATION SHOWN COMPLIES WITH CODE
 BUT HAS NOTED SOME ITEMS AS LISTED. THIS PERMIT REVIEW
 IS ONLY FOR THE HOUSE.
  
 A. IRRIGATION
 B. POOL - THE POOL CONFIGURATION HAS BEEN CHANGED. FULL
 COMPLIANCE REVIEW WILL BE WITH THE REQUIRED POOL
 PERMIT.
 C. GENERATOR
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2022-05-27 Cont ID  
Sent By eschneid Date 2022-05-27 Time 11:06 Rev Time 0.75
Received By eschneid Date 2022-05-18 Time 08:30 Sent To  
Notes
2022-05-18 09:11:16FAILED
  
 1) UPDATED COMMENT: THANK YOU FOR PROVIDING THE AVERAGE
 GRADE CALCULATION TABLE THAT USES A WEIGHTED AVERAGE
 FOR THE PURPOSE OF ESTABLISHING THE STARTING POINT TO
 MEASURE THE BUILDING HEIGHT. STAFF HAS NOT PREVIOUSLY
 REVIEWED THIS AS A AVERAGE GRADE CALCULATION
 METHODOLOGY AND HAS THE FOLLOWING COMMENTS.
  
 A. PROVIDE A 1ST FLOOR BUILDING PLAN THAT CLEARLY SHOWS
 WHERE THE TABLE LOCATIONS ARE TIED TOO. THE ENTIRE
 PERIMETER OF THE BUILDING NEEDS TO BE INCLUDED BASED ON
 THE METHODOLOGY THAT YOU HAVE CHOOSEN.
 B. THE TABLE NEEDS TO MATCH THE GRADE HEIGHTS SHOWN ON
 THE ELEVATION DRAWINGS. THE CURRENT ELEVATION PLANS
 SHOW THE MAJORITY OF THE ELEVATIONS LESS THAN WHAT IS
 SHOWN ON THE TABLE, TO INCLUDE THE LABEL ON THE SOUTH
 ELEVATION DRAWING THAT STATES, "8.5 NAVD AVERAGE
 FINISHED GRADE", WHILE THE TABLE LISTS THE ENTIRE SOUTH
 ELEVATION HEIGHT AS 9.15 NAVD. ADDITIONALLY, THE ENTIRE
 SOUTH ELEVATION IS NOT AT EVEN 8.5 NAVD AS THE WEST
 SIDE GRADE SLOPES DOWN. THERE ALSO SEEM TO BE
 DISCREPANCIES WITH THE C-1 SITE PLAN AND THE ELEVATIONS
 AND THE TABLE.
 C. STAFF REVIEWED THE DRAWINGS AND BASED ON THE NORMAL
 WAY THAT AVERAGE GRADE IS CALCULATED (CORNER POINTS OF
 THE BUILDING), THE STAFF CALCULATED AVERAGE GRADE IS
 APPROXIMATELY 7.5 NAVD, WHICH RESULTS IN THE HOUSE
 EXCEEDING THE PERMITTED BUILDING HEIGHT.
  
 2) REPEAT COMMENT: THERE ARE TWO SEPARATE KITCHEN AREAS
 SHOWN, WHICH IS NOT PERMITTED IN A SINGLE-FAMILY HOUSE.
 **** ALL SHEETS NEED TO BE UPDATED TO REFLECT THE
 REMOVAL OF THE OVEN IN THE BUTLER PANTRY, INCLUDING THE
 PIPING PLANS, THE POWER PLANS, THE ELECTRIC SCHEDULES,
 THE MECHANICAL PLANS, THE REFLECTED CEILING PLAN, AND
 THE FIRST FLOOR DIMENSION PLAN. -- ZONING WILL NOT PASS
 THIS PERMIT UNTIL ALL PLANS REMOVE THE 2ND KITCHEN.
 THIS NEEDS TO BE DONE WITH THIS ORIGINAL PERMIT AND NOT
 AS A FUTURE REVISION.
  
 34) SEPARATE PERMITS ARE REQUIRED FOR THE ITEMS LISTED
 BELOW. PLEASE NOTE THAT STAFF HAS NOT FULLY REVIEWED
 ANY OF THE ITEMS AS PART OF THIS PERMIT APPLICATION TO
 VERIFY THAT THE INFORMATION SHOWN COMPLIES WITH CODE
 BUT HAS NOTED SOME ITEMS AS LISTED. THIS PERMIT REVIEW
 IS ONLY FOR THE HOUSE.
  
 A. DRIVEWAY AND APPROACH.
 B. IRRIGATION
 C. POOL - BY THE ZONING AND LAND DEVELOPMENT CODE
 DEFINITION, THE PROPOSED POOL IS AN ABOVE GROUND
 SWIMMING POOL. ABOVE GROUND SWIMMING POOLS ARE
 PROHIBITED IN THE CITY OF WEST PALM BEACH.
 ADDITIONALLY, A PORTION OF THE INFINITY EDGE CAPTURE
 AREA IS WITHIN THE 25-FOOT FRONT SETBACK, WHICH IS NOT
 PERMITTED.
 D. GENERATOR
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-03-22 Cont ID  
Sent By eschneid Date 2022-03-22 Time 16:36 Rev Time 1.00
Received By eschneid Date 2022-03-18 Time 11:26 Sent To  
Notes
2022-03-22 16:37:03FAILED
  
 1) UPDATED COMMENT: PROVIDE THE HEIGHT DIMENSIONS IN
 ACCORDANCE WITH THE CITY'S ZONING AND LAND DEVELOPMENT
 CODE REGULATIONS - THE HEIGHT SHALL BE MEASURED AS THE
 VERTICAL DISTANCE FROM THE AVERAGE ELEVATION OF THE
 FINISHED GRADE OF THE BUILDING TO THE HIGHEST POINT OF
 THE TOP OF THE STRUCTURE OF A FLAT ROOF, OR TO THE DECK
 LINE OF A MANSARD ROOF, OR TO THE MEAN HEIGHT LEVEL
 BETWEEN EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL
 ROOFS. THE MEASURE POINT NEEDS TO START AT THE AVERAGE
 FINISHED GRADE, NOT THE TOP OF THE FLOOR SLAB AND
 INCLUDE THE HIGHEST RIDGE AND THE EAVE DIMENSIONS. ****
 PLEASE PROVIDE HOW YOU DETERMINED THE AVERAGE ELEVATION
 OF SIX INCHES BELOW THE SLAB WHEN THERE IS A
 SIGNIFICANT PERCENTAGE OF THE GRADE FOR THE WESTERN
 PORTION OF THE HOUSE IS 2-3 FEET BELOW THE SLAB.
  
 2) REPEAT COMMENT: THERE ARE TWO SEPARATE KITCHEN AREAS
 SHOWN, WHICH IS NOT PERMITTED IN A SINGLE-FAMILY HOUSE.
 **** ALL SHEETS NEED TO BE UPDATED TO REFLECT THE
 REMOVAL OF THE OVEN IN THE BUTLER PANTRY, INCLUDING THE
 PIPING PLANS, THE POWER PLANS, THE ELECTRIC SCHEDULES,
 THE MECHANICAL PLANS, THE REFLECTED CEILING PLAN, AND
 THE FIRST FLOOR DIMENSION PLAN.
  
 3) UPDATED COMMENT: THE PLANS SHOW ARTIFICIAL TURF,
 WHICH IS ONLY LOCATED WITHIN THE SIDE OR REAR SETBACK,
 WHICH IS NOT WHERE YOU HAVE SHOWN IT. **** THE RESPONSE
 STATES THAT THE LANDSCAPE PLANS DO NOT SHOW ARTIFICIAL
 TURF; HOWEVER, THERE IS A NOTE ON SHEET L1 THAT STATES,
 "STRIP DRAIN UNDER ART TURF" AND SHEET C1 HAS AN AREA
 LABELED AS "ARTIFICIAL TURF".
  
 4) SEPARATE PERMITS ARE REQUIRED FOR THE ITEMS LISTED
 BELOW. PLEASE NOTE THAT STAFF HAS NOT FULLY REVIEWED
 ANY OF THE ITEMS AS PART OF THIS PERMIT APPLICATION TO
 VERIFY THAT THE INFORMATION SHOWN COMPLIES WITH CODE
 BUT HAS NOTED SOME ITEMS AS LISTED. THIS PERMIT REVIEW
 IS ONLY FOR THE HOUSE.
  
 A. DRIVEWAY AND APPROACH.
 B. IRRIGATION
 C. POOL - BY THE ZONING AND LAND DEVELOPMENT CODE
 DEFINITION, THE PROPOSED POOL IS AN ABOVE GROUND
 SWIMMING POOL. ABOVE GROUND SWIMMING POOLS ARE
 PROHIBITED IN THE CITY OF WEST PALM BEACH.
 ADDITIONALLY, A PORTION OF THE INFINITY EDGE CAPTURE
 AREA IS WITHIN THE 25-FOOT FRONT SETBACK, WHICH IS NOT
 PERMITTED.
 D. GENERATOR
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-12-13 Cont ID  
Sent By aaponte Date 2021-12-13 Time 13:58 Rev Time 2.00
Received By eschneid Date 2021-12-08 Time 09:09 Sent To  
Notes
2021-12-13 14:00:29FAILED
  
 1) PRIOR TO ZONING APPROVAL OF THIS PERMIT, YOU MUST
 SUBMIT A LANDSCAPE PERMIT, WITH A CODE COMPLIANT
 LANDSCAPE PLAN, FOR THE PROPERTY. YOU WILL NEED TO
 UPLOAD THE LANDSCAPE PLANS THAT WERE PROVIDED WITH THIS
 PERMIT UNDER A SEPARATE LANDSCAPE PERMIT.
  
 2) STEPS, OPEN UNCOVERED PORCHES OR STOOPS, AND OPEN
 TERRACES WHICH ARE THREE FEET OR LESS ABOVE GRADE MAY
 ENCROACH INTO ANY REQUIRED SETBACK AREA TO A POINT NOT
 CLOSER THAN TWO FEET TO THE PROPERTY LINE. THE TERRACE
 AREA AND STEPS AT THE SOUTHEAST CORNER OF THE BUILDING
 DOES NOT COMPLY WITH THIS REQUIREMENT AS IT IS WITHIN
 TWO FEET OF THE PROPERTY LINE.
  
 3) THERE ARE DISCREPANCIES BETWEEN THE PAVING SHOWN AT
 THE TRACH AREA BETWEEN THE ENGINEER SITE PLAN AND THE
 LANDSCAPE SITE PLAN. THE LANDSCAPE SITE PLAN SHOWS THE
 PAVING TO THE WEST PROPERTY LINE, WHICH IS NOT
 PERMITTED (TWO-FOOT SETBACK REQUIRED).
  
 4) PROVIDE THE HEIGHT OF THE PATH LIGHTS.
  
 5) PROVIDE THE HEIGHT DIMENSIONS IN ACCORDANCE WITH THE
 CITY'S ZONING AND LAND DEVELOPMENT CODE REGULATIONS -
 THE HEIGHT SHALL BE MEASURED AS THE VERTICAL DISTANCE
 FROM THE AVERAGE ELEVATION OF THE FINISHED GRADE OF THE
 BUILDING TO THE HIGHEST POINT OF THE TOP OF THE
 STRUCTURE OF A FLAT ROOF, OR TO THE DECK LINE OF A
 MANSARD ROOF, OR TO THE MEAN HEIGHT LEVEL BETWEEN EAVES
 AND RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS. THE
 MEASURE POINT NEEDS TO START AT THE AVERAGE FINISHED
 GRADE, NOT THE TOP OF THE FLOOR SLAB AND INCLUDE THE
 HIGHEST RIDGE AND THE EAVE DIMENSIONS.
  
 6) PROVIDE THE HEIGHT OF THE CHIMNEY FROM THE AVERAGE
 FINISHED GRADE. THE CHIMNEY MAY NOT EXCEED 33 FEET IN
 HEIGHT.
  
 7) THERE ARE TWO SEPARATE KITCHEN AREAS SHOWN, WHICH IS
 NOT PERMITTED IN A SINGLE-FAMILY HOUSE.
  
 8) THE PLANS SHOW ARTIFICIAL TURF, WHICH IS ONLY
 LOCATED WITHIN THE SIDE OR REAR SETBACK, NOT WHERE YOU
 HAVE SHOWN IT IN THE FRONT OF THE HOUSE.
  
 9) SEPARATE PERMITS ARE REQUIRED FOR THE ITEMS LISTED
 BELOW. PLEASE NOTE THAT STAFF HAS NOT FULLY REVIEWED
 ANY OF THE ITEMS AS PART OF THIS PERMIT APPLICATION TO
 VERIFY THAT THE INFORMATION SHOWN COMPLIES WITH CODE
 BUT HAS NOTED SOME ITEMS AS LISTED. THIS PERMIT REVIEW
 IS ONLY FOR THE HOUSE.
  
 A. DRIVEWAY AND APPROACH.
 B. IRRIGATION
 C. WALL AND GATES - TOP OF WALL ALONG ALL FRONTAGES
 EXCEEDS HEIGHT ALLOWANCE OF 6 FEET WHEN MEASURED FROM
 THE EXTERIOR GRADE AT THE PROPERTY LINE. A PORTION OF
 THE WALL ENCROACHES INTO THE VISIBILITY TRIANGLE.
 D. POOL - BY THE ZONING AND LAND DEVELOPMENT CODE
 DEFINITION, THE PROPOSED POOL IS AN ABOVE GROUND
 SWIMMING POOL. ABOVE GROUND SWIMMING POOLS ARE
 PROHIBITED IN THE CITY OF WEST PALM BEACH.
 ADDITIONALLY, A PORTION OF THE INFINITY EDGE CAPTURE
 AREA IS WITHIN THE 25-FOOT FRONT SETBACK, WHICH IS NOT
 PERMITTED.
 E. GENERATOR
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy