| Plan Review Stops For Permit 21101200 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
P |
Date |
2022-02-11 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-02-11 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-02-11 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2022-02-11 11:09:05 | ADDRESS CHANGED TO 128 PALMETTO LN, UPDATED PERMIT. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2022-02-02 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-02-02 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-02-02 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2022-02-02 11:00:07 | PREVIOUS COMMENTS NOT ADDRESSED |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-10-29 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-10-29 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-10-29 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2021-10-29 15:47:22 | A NEW ADDRESS BASED ON THE CITY'S ROAD CENTER LINES AND | | | THE FRONT MAIN ENTRANCE WILL NEED TO BE ESTABLISHED. | | | BASED ON THE PLANS YOU HAVE SUBMITTED; I AM PROPOSING | | | EITHER 128 PALMETTO LN OR 130 PALMETTO LN. PLEASE HAVE | | | THE OWNERS REVIEW THESE OPTIONS AND LET ME KNOW. PLEASE | | | RESPOND TO [email protected] OR CALL 561-805-6659. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2022-08-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-13 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-13 |
Time |
09:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-07-19 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-19 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-19 |
Time |
15:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-06-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-06-14 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-06-10 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2022-06-14 13:13:04 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17 | | | | | | | | | 3RD REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN | | | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER | | | PREVIOUS COMMENTS. | | | | | | | | | 1. CORRECTED | | | | | | 2. (ONLY THE COVER SHEETS FOR FL5822-R8 WERE SUBMITTED | | | FOR REVIEW) | | | | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | NOTE: DESIGNER SHALL SELECT MODEL OF SMART VENT TO BE | | | INSTALLED. | | | | | | 3. CORRECTED. | | | | | | 4. PROVIDE A STRUCTURAL DETAIL OF THE UNDER-SLAB | | | CHANNELS CONNECTING THE SMART VENTS TO THE GARAGE FLOOR | | | AREA. INCLUDE A DETAIL OF HOW THE CHANNEL COMMUNICATES | | | WITH THE GARAGE, | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | (PLEASE PROVIDE A FEMA REFERENCE ON THE USE AND | | | INSTALLATION OF THESE CHANNELS) (PLEASE REVIEW FEMA | | | NFIP TECHNICAL BULLETIN #1) | | | | | | 5. CORRECTED. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-03-10 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-03-10 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-03-02 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2022-03-10 17:15:15 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17 | | | | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | | | | NOTICE: THIS PROJECT IS LOCATED IN A SPECIAL FLOOD | | | HAZARD AREA (SFHA). THE STRUCTURE IS LOCATED WITHIN TWO | | | AE FLOOD ZONES WITH BASE FLOOD ELEVATIONS (BFE) OF | | | 6'0"NAVD AND 7'0" NAVD. THE CITY OF WEST PALM BEACH | | | (THROUGH ORDINANCE NO. 4729-17) REQUIRES AN ADDITIONAL | | | 24 INCHES OF FREEBOARD. THE DESIGN FLOOD ELEVATION | | | (DFE) SHALL BE AT OR ABOVE 9'0"NAVD. | | | | | | CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17 | | | SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT | | | CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE | | | II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL | | | AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH | | | SHALL READ AS FOLLOWS: | | | | | | SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING | | | CODE, RESIDENTIAL. | | | R322.2.1 ELEVATION REQUIREMENTS. | | | 1. BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT | | | DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST | | | FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION | | | PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER | | | IS HIGHER. | | | | | | 1. NOTE ON PLAN PAGE C-1 STATES "EQUIPMENT SHALL BE AT | | | OR ABOVE 8.00' NAVD". EQUIPMENT SERVICING THE BUILDING | | | SHALL BE AT OR ABOVE THE DFE ELEVATION OF 9.00' NAVD. | | | PLEASE CORRECT. | | | BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT | | | DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST | | | FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION | | | PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER | | | IS HIGHER. | | | | | | 2. PRODUCT APPROVAL FL 5822-R7 FOR SMART VENTS HAS | | | EXPIRED. | | | 1.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT | | | APPROVAL FOR THE PROPOSED SMART VENTS. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | NOTE: DESIGNER SHALL SELECT MODEL OF SMART VENT TO BE | | | INSTALLED. | | | | | | 3. IDENTIFY THE SMART VENT MODEL TO BE INSTALLED NEXT | | | TO THE PEDESTRIAN GARAGE DOOR. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 4. PROVIDE A STRUCTURAL DETAIL OF THE UNDER-SLAB | | | CHANNELS CONNECTING THE SMART VENTS TO THE GARAGE FLOOR | | | AREA. INCLUDE A DETAIL OF HOW THE CHANNEL COMMUNICATES | | | WITH THE GARAGE, | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | REF. PLAN PAGE A104 FOR THE FOLLOWING COMMENTS: | | | 5. BASED ON THE RECESSED FLOOR DESIGN, THE SCREENING | | | ROOM WILL BE AT 7.00' NAVD. THE LOWEST FLOOR SHALL BE | | | AT OR ABOVE THE BFE PLUS 2.00' PER R322.2.1. FF ELEV. | | | SHALL BE 9.00' NAVD. | | | BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT | | | DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST | | | FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION | | | PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER | | | IS HIGHER. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-01-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-03 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-12-30 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2022-01-03 15:52:55 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17 | | | | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | | | | 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA (SFHA). THE STRUCTURE IS LOCATED WITHIN TWO AE | | | FLOOD ZONES WITH BASE FLOOD ELEVATIONS (BFE) OF | | | 6'0"NAVD AND 7'0" NAVD. THE CITY OF WEST PALM BEACH | | | (THROUGH ORDINANCE NO. 4729-17) REQUIRES AN ADDITIONAL | | | 24 INCHES OF FREEBOARD. THE DESIGN FLOOD ELEVATION | | | (DFE) SHALL BE AT OR ABOVE 9'0"NAVD. | | | | | | CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17 | | | SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT | | | CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE | | | II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL | | | AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH | | | SHALL READ AS FOLLOWS: | | | | | | SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING | | | CODE, RESIDENTIAL. | | | R322.2.1 ELEVATION REQUIREMENTS. | | | 1. BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT | | | DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST | | | FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION | | | PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER | | | IS HIGHER. | | | | | | 2.PLACE THE FINISHED FLOOR ELEVATION (FFE) OF THE MAIN | | | DWELLING UNIT AND THE ATTACHED GARAGE ON THE SITE PLAN, | | | THE FLOOR PLAN AND THE FOUNDATION PLAN. | | | | | | 3. NOTICE: THE GARAGE FLOOR IS BELOW THE DFE OF 9'0" | | | NAVD. | | | FLOOD OPENINGS ARE REQUIRED. | | | R322.2.2ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION. | | | ENCLOSED AREAS, INCLUDING CRAWL SPACES, THAT ARE BELOW | | | THE DESIGN FLOOD ELEVATION SHALL: | | | 1. 1.BE USED SOLELY FOR PARKING OF VEHICLES, BUILDING | | | ACCESS OR STORAGE. | | | 2. 2.BE PROVIDED WITH FLOOD OPENINGS THAT MEET THE | | | FOLLOWING CRITERIA AND ARE INSTALLED IN ACCORDANCE WITH | | | SECTION R322.2.2.1: | | | 1. 2.1.THE TOTAL NET AREA OF NON-ENGINEERED OPENINGS | | | SHALL BE NOT LESS THAN 1 SQUARE INCH (645 MM2) FOR EACH | | | SQUARE FOOT (0.093 M2) OF ENCLOSED AREA WHERE THE | | | ENCLOSED AREA IS MEASURED ON THE EXTERIOR OF THE | | | ENCLOSURE WALLS, OR THE OPENINGS SHALL BE DESIGNED AS | | | ENGINEERED OPENINGS AND THE CONSTRUCTION DOCUMENTS | | | SHALL INCLUDE A STATEMENT BY A REGISTERED DESIGN | | | PROFESSIONAL THAT THE DESIGN OF THE OPENINGS WILL | | | PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD FORCES ON | | | EXTERIOR WALLS BY ALLOWING FOR THE AUTOMATIC ENTRY AND | | | EXIT OF FLOODWATERS AS SPECIFIED IN SECTION 2.7.2.2 OF | | | ASCE 24. | | | 2. 2.2.OPENINGS SHALL BE NOT LESS THAN 3 INCHES (76 MM) | | | IN ANY DIRECTION IN THE PLANE OF THE WALL. | | | 3. 2.3.THE PRESENCE OF LOUVERS, BLADES, SCREENS AND | | | FACEPLATES OR OTHER COVERS AND DEVICES SHALL ALLOW THE | | | AUTOMATIC FLOW OF FLOODWATER INTO AND OUT OF THE | | | ENCLOSED AREAS AND SHALL BE ACCOUNTED FOR IN THE | | | DETERMINATION OF THE NET OPEN AREA. | | | | | | | | | OPTION: | | | ENGINEERED FLOOD VENTS | | | | | | 1) PROVIDE ENGINEERED FLOOD VENTS. (SMART VENTS) | | | 2) ATTACH A COPY OF THE INDIVIDUAL ENGINEERED FLOOD | | | VENT CERTIFICATION OR EVALUATION SERVICE REPORT ISSUED | | | BY THE INTERNATIONAL CODE COUNCIL EVALUATION SERVICE | | | (ICC ES). | | | 3) PROVIDE FLORIDA PRODUCT APPROVALS FOR PROPOSED SMART | | | VENTS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE | | | 9N-3 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. | | | 5) FLOOD OPENINGS SHALL BE INSTALLED PER | | | R322.2.2.1INSTALLATION OF OPENINGS: | | | 6) SHOW NUMBER AND LOCATION OF FLOOD OPENINGS ON | | | FOUNDATION PLAN. INCLUDE THE FLORIDA PRODUCT APPROVAL | | | NUMBER AND IDENTIFY THE VENT MODEL TO BE INSTALLED. | | | R322.2.2.1INSTALLATION OF OPENINGS. | | | THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS | | | INSTALLED SUCH THAT: | | | 1. 1.THERE SHALL BE NOT LESS THAN TWO OPENINGS ON | | | DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING | | | HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD | | | ELEVATION, EACH AREA SHALL HAVE OPENINGS. | | | 2. 2.THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN | | | 1 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR | | | GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE | | | IMMEDIATELY UNDER EACH OPENING. | | | 3. 3.OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN | | | DOORS AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED | | | OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION. | | | | | | FEMA TECHNICAL BULLETIN #1 | | | LOCATION OF FLOOD OPENINGS | | | THE IRC AND IBC (BY REFERENCE TO ASCE 24) REQUIRE FLOOD | | | OPENINGS ?ON DIFFERENT SIDES OF EACH ENCLOSED AREA? | | | (IRC R322.2.2.1) AND ?IN AT LEAST TWO WALLS OF EACH | | | ENCLOSED AREA? (ASCE 24, SECTION 2.7.3). | | | | | | | | | 4. NOTE: PLAN PAGE C-1 INDICATES FOUR FLOOD VENTS ARE | | | INSTALLED WITH UNDER SLAB CHANNELS. | | | PROVIDE A DETAIL OF THE CHANNELS AND A REFERENCE TO THE | | | FEMA REGULATION THAT ALLOWS THIS TYPE OF INSTALLATION. | | | | | | | | | NOTICE: SUBMIT THE FOLLOWING ELEVATION CERTIFICATES, AS | | | REQUIRED. (SEE NFIP REVIEW COMMENTS) | | | | | | THREE ELEVATION CERTIFICATES (EC) ARE REQUIRED | | | | | | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | | | | A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AT PLACEMENT OF 1ST FLOOR. | | | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | | | | NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL | | | GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE | | | BUILDING. | | | | | | 5. REF. SITE PLAN PAGE C-1 FOR THE FOLLOWING COMMENT: | | | EQUIPMENT SERVICING THE BUILDING SHALL BE AT OR ABOVE | | | 9'0" NAVD. PLEASE CORRECT. | | | | | | 6. REF. PLAN PAGES S-101 AND C-1 FOR THE FOLLOWING | | | COMMENT: PG. S-101 INDICATES TOS TO BE 9'0". PG. C-1 | | | INDICATES TOS TO BE 8.83' WITH FINISHED FLOOR TO BE | | | 9'0" NAVD. PLEASE CLARIFY. | | | | | | 7. PROVIDE COVER SHEETS FOR ALL PRODUCT APPROVALS | | | SUBMITTED FOR REVIEW. | | | PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER | | | SHEETS; THEY SHOW THE APPROVAL NUMBER, CODE VERSION, | | | AND STATUS, FBC R 301. (MIAMI DADE NOAS ARE OK, DO NOT | | | NEED FL COVER PAGE). | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 8. PROVIDE PRODUCT APPROVALS FOR THE WINDOW MULLIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 9. PROVIDE THE ICC-ES REPORT FOR THE SPRAY APPLIED | | | INSULATION. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 10. REF. PLAN PAGE S003 FOR THE FOLLOWING COMMENT: | | | PROVIDE A ROOF SHEATHING FASTENER SCHEDULE BASED ON THE | | | CALCULATED DESIGN PRESSURES. | | | PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN | | | PRESSURES. | | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | | | NOTICE: PROVISO'S | | | PLAN PAGE C-1; SITE WALLS REQUIRE A SEPERATE PERMIT. | | | PLAN PAGE L1.1; POOL REQUIRES A SEPERATE PERMIT. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-08-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-13 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-13 |
Time |
09:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-02-10 |
Time |
20:51 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-02-10 |
Time |
20:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-12-11 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-12-11 |
Time |
21:54 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-12-11 |
Time |
20:35 |
Sent To |
|
|
| Notes |
| 2021-12-11 21:54:31 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NO SMOKE/CO ALARMS SHOWN ON PLAN FBC-R 314 AND 315 | | | | | | 2. PROVIDE NOTE ON PLANS GENERATOR AND LOW VOLTAGE | | | SHOWN ON PLAN REQUIRE SEPARATE PERMITS. FBC 105.1 FBC | | | 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-04-13 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-04-13 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2023-04-13 13:19:35 | LV/DATA ONLY |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2021-11-20 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2021-11-20 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2021-11-20 |
Time |
17:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-08-18 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-08-18 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-08-12 |
Time |
09:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-07-22 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-06-29 |
Time |
15:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-06-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-06-14 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-20 |
Time |
16:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-03-22 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-03-22 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-01-31 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-03 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-11-02 |
Time |
07:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-08-24 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-08-24 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-07-19 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2022-08-15 10:55:36 | MU-2022-034093-0000 - $12,071.20 PAID AO | | 2022-07-19 11:25:09 | 7/19/22 EMAILED IMPACT FOR REVIEW PER REG-AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-01-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-03 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-01-03 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2022-01-03 09:45:58 | IMPACT FEE QUESTIONNAIRE | | | | | | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT | | | LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO | | | THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF. | | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE | | | RECEIPT TO PROJECT DOX OR EMAIL IT TO | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-05-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-04 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-04 |
Time |
07:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-02-09 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-09 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-09 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2022-02-10 08:36:45 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21101200 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IN THE SUPPORTING DOCUMENTS FOLDER THERE ARE 2 FILES | | | NAMED ENERGY CALCULATIONS, ONE IS NAMED ENERGY | | | CALCULATIONS ? V2 DATED 1/31/2022, THE OTHER IS NAMED | | | ENERGY CALCLATIONS DATED 10/26/2021. THE FILE DATED | | | 10/26/2021 IS IN FACT THE ENERGY CALCULATIONS. THE ONE | | | DATED 1/31/2022 IS LABELED WRONG AS IT IS THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS. PLEASE | | | CORRECT THIS. | | | | | | 2) SHEET M101: THERE IS A NOTE THAT READS FINAL DUCT | | | ARRANGEMENTS RESERVED PENDING STRUCTURAL COORDINATION. | | | PLEASE PROVIDE THE FINAL DOCUMENTS AS WE SHOULD BE | | | REVIEWING THE FINAL CODE COMPLIANT DRAWINGS. IF THESE | | | ARE THE FINAL DRAWINGS THEN PLEASE REMOVE THE NOTE. FBC | | | 107.2.1 | | | | | | 3) PLEASE MAKE THE RETURN AIR PATH CLEAR IN ALL AREAS. | | | AHU-1-01 APPEARS TO HAVE THE RETURN TO THE RIGHT SIDE | | | OF THE CLOSET WITH THE LEFT SIDE OF THE UNIT BEING THE | | | SUPPLY SIDE. F12 IS LEAVING THE RIGHT SIDE OF THIS UNIT | | | BUT THE ARROWS INDICTING THE FLOW SHOWS IT IS SUPPLYING | | | AIR TO THE GUEST SUITE 1. F9 DUCT IS LEAVING FROM THE | | | LEFT SIDE OF THE UNIT THAT INDICATES A FLOW TO THE | | | GUEST SUITE 1 BUT THE ARROW AT THE DIFFUSER INDICATES | | | THE FLOW IS RETURNING BACK TO THE UNIT. FBC 107.2.1 | | | | | | 4) PLEASE SHOW THE CONDENSATE DRAIN PIPE SIZES FOR EACH | | | SECTION OF PIPE. IT APPEARS THAT ALL PIPE SIZES LEAVING | | | EACH UNIT IS 1 INCH BUT THE ONLY REFERENCE TO THE | | | DRAINAGE SYSTEM SIZE IS AT THE CONDENSATE GOOSENECK ON | | | THE EXTERIOR OF THE BUILDING WHICH IS 2 INCH PVC. FBC | | | RES M1411.3.2 | | | | | | 5) PLEASE SHOW THE CALCULATIONS FOR THE CONDENSATE PIPE | | | SIZING BASED ON FBC M TABLE 307.2.2 | | | | | | 6) PLEASE SHOW HOW THIS CONDENSATE DRAINAGE DESIGN WILL | | | BE CODE COMPLIANT WITH THE DRAIN LINE MAINTENANCE OF | | | FBC RES M1411.3.3 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | 2022-02-09 13:38:13 | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-11-09 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-11-09 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-11-09 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2021-11-09 09:42:30 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21101200 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS HAVE | | | ONLY 8 SHEETS OUT OF 61. PLEASE SUBMIT THE ENTIRE | | | DOCUMENT FOR REVIEW. FBC 107.2.1 | | | | | | 2) PLEASE SHOW ON THE DRAWING THAT THE COMBUSTION AIR | | | GRILL IS A MINIMUM OF 10 FT AWAY FROM THE GENERATOR | | | EXHAUST. FBC 107.2.1 | | | | | | 3) PLEASE SHOW THE EXHAUST FAN FOR THE SHOWER AREA FOR | | | THE SUITE 3 BATHROOM. FBC RES M1507.4 | | | | | | 4) PLEASE SHOW THE SIZE AND MATERIAL USED FOR THE | | | CONDENSATE PIPING. FBC RES M1411.3 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
4 |
Status |
P |
Date |
2022-07-19 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-19 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-19 |
Time |
15:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
F |
Date |
2022-06-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-06-14 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-06-10 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2022-06-14 13:26:26 | NFIP PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 | | | | | | 1ST REVIEW OF THE CONSTRUCTION DRAWING ELEVATION | | | CERTIFICATE | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. LINE A1-OWNERS NAME IS MISSING. | | | | | | 2. LINE B1-THE COMMUNITY NAME AND NUMBER ENTERED DO NOT | | | APPEAR ON FIRM PANEL 12099C 0591 F. THE COMMUNITY NAME | | | SHOULD BE PALM BEACH COUNTY AND THE COMMUNITY NUMBER | | | SHOULD BE 120192. | | | | | | 3. LINE C2(B)-2ND FLOOR ELEVATION DATA MISSING. | | | | | | 4. C2(H)-GRADE ELEVATION DATA MISSING. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2022-03-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-03-02 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-03-02 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2022-03-02 17:05:19 | NFIP PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA (SFHA). THE STRUCTURE IS LOCATED WITHIN TWO AE | | | FLOOD ZONES WITH BASE FLOOD ELEVATIONS (BFE) OF | | | 6'0"NAVD AND 7'0" NAVD. THE CITY OF WEST PALM BEACH | | | (THROUGH ORDINANCE NO. 4729-17) REQUIRES AN ADDITIONAL | | | 24 INCHES OF FREEBOARD. THE DESIGN FLOOD ELEVATION | | | (DFE) SHALL BE AT OR ABOVE 9'0"NAVD. | | | | | | CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17 | | | SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT | | | CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE | | | II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL | | | AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH | | | SHALL READ AS FOLLOWS: | | | | | | SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING | | | CODE, RESIDENTIAL. | | | R322.2.1 ELEVATION REQUIREMENTS. | | | 1. BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT | | | DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST | | | FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION | | | PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER | | | IS HIGHER. | | | | | | 2. PROVIDE A CONSTRUCTION DRAWING ELEVATION CERTIFICATE | | | FOR REVIEW. | | | FEMA | | | | | | NOTICE: | | | | | | THREE ELEVATION CERTIFICATES (EC) ARE REQUIRED | | | | | | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | | | | A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AT PLACEMENT OF 1ST FLOOR. | | | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | | | | NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL | | | GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE | | | BUILDING. | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2022-01-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-03 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-12-30 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2022-01-03 15:02:45 | SEE COMMENTS UNDER BLDG. REVIEW. EC REQUIRED. CT | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2021-11-20 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2021-11-20 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2021-11-20 |
Time |
15:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-07-26 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-07-26 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2022-07-26 14:45:04 | APPROVED FOR PP INSPECTIONS, ADJUSTED FEE AND UPLOADED | | | NTBO AND SUPPORTING DOCS TO PROJECTDOX |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2022-01-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-03 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-12-30 |
Time |
08:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2022-08-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-13 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-13 |
Time |
09:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-07-19 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-19 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-19 |
Time |
15:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-06-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-06-14 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-06-10 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2022-05-04 08:00:01 | MECHANICAL DIGITALSIGNATURES APPROVED. ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-03-10 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-03-10 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-03-02 |
Time |
10:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-01-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-03 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-12-30 |
Time |
08:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2022-08-24 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2022-08-24 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2022-08-24 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2022-08-24 12:26:44 | 8/24/22- PASSED WITH THE PROVISO THAT A REVISION IS | | | SUBMITTED BEFORE THE FIRST INSPECTION BEYOND THE | | | FOUNDATION IS CALLED IN ADDRESSING ZONING COMMENTS | | | DATED 08/18/22. | | | | | | ANGELLA VANN, AICP | | | PLANNING AND ZONING ADMINISTRATOR |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
2022-08-18 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2022-08-18 |
Time |
12:01 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2022-08-18 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2022-08-18 12:01:31 | FAILED | | | | | | 1) CHIMNEYS ARE PERMITTED TO EXCEED THE DISTRICT HEIGHT | | | REQUIREMENTS BY 10 PERCENT, WHICH WOULD PERMIT THE | | | CHIMNEY AT THIS LOCATION TO BE 33 FEET ABOVE FINISHED | | | GRADE. THIS CHIMNEY HEIGHT ALLOWANCE IS STATED ON THE | | | A-201, YET THE CHIMNEY IS SHOWN AS 33 FEET 1 INCH IN | | | HEIGHT, WHICH EXCEEDS THE PERMITTED HEIGHT ALLOWANCE. | | | THE PLANS MUST SHOW CODE COMPLIANT CONDITIONS. | | | | | | 2) UPDATED REPEAT COMMENT: SHEET L1.0 AND SHEET A-100 | | | SHOW THE SAME CONDITIONS; HOWEVER, THEY DO NOT MATCH | | | SHEET C-1 OR S-101 (WHICH MATCH EACH OTHER). ALL PLANS | | | MUST SHOW CONSISTENT, ACCURATE, CODE COMPLIANT | | | CONDITIONS. | | | | | | 3) SEPARATE PERMITS ARE REQUIRED FOR THE ITEMS LISTED | | | BELOW. PLEASE NOTE THAT STAFF HAS NOT FULLY REVIEWED | | | ANY OF THE ITEMS AS PART OF THIS PERMIT APPLICATION TO | | | VERIFY THAT THE INFORMATION SHOWN COMPLIES WITH CODE | | | BUT HAS NOTED SOME ITEMS AS LISTED. THIS PERMIT REVIEW | | | IS ONLY FOR THE HOUSE. | | | | | | A. IRRIGATION | | | B. POOL - THE POOL CONFIGURATION HAS BEEN CHANGED. FULL | | | COMPLIANCE REVIEW WILL BE WITH THE REQUIRED POOL | | | PERMIT. | | | C. GENERATOR | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2022-07-22 |
Time |
16:30 |
Rev Time |
2.00 |
| Received By |
eschneid |
Date |
2022-07-21 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2022-07-22 16:31:01 | FAILED | | | | | | 1) UPDATED COMMENT: STAFF WILL ACCEPT YOUR WEIGHTED | | | AVERAGE METHODOLOGY; HOWEVER, THE COMMENTS MUST BE | | | ADDRESSED TO SATISFY STAFF THAT THE HOUSE DOES NOT | | | EXCEED THE MAXIMUM HEIGHT ALLOWANCE. | | | | | | A. SHEET A-202 WAS NOT INCLUDED (SHEET A-201 WAS | | | UPLOADED IN ITS PLACE), SO STAFF WAS UNABLE TO VERIFY | | | THE UPDATED AVERAGE GRADE CALCULATION TABLE AND THE | | | SHEET A-100 INFORMATION FOR THE EAST SIDE OF THE | | | BUILDING. | | | B. THANK YOU FOR PROVIDING ELEVATION TAGS ALONG THE | | | SOUTH ELEVATION DRAWING TO MIRROR THE TAGS ON SHEET | | | A-100. THE NORTH, EAST AND WEST ELEVATION DRAWINGS MUST | | | ALSO INCLUDE THESE TAGS SO THAT STAFF CAN VERIFY THE | | | MEASURE POINTS WITHOUT NEEDING TO SCALE THE PLAN. WHEN | | | SCALING THE PLAN, THE WEST GRADE ELEVATION AT THE WEST | | | GUEST 1 (LOWER) AND WEST LAUNDRY (HIGHER) DO NOT MATCH | | | THE TABLE OR SHEET A-100. | | | C. THE SOUTH ELEVATION DRAWING LISTS THE 1ST FLOOR SLAB | | | AT 9.00 NAVD. HOWEVER, THE GRADE TAGS (ALSO SHOWN ON | | | SHEET C-1) AND THE GRADE CROSS HATCH ARE SHOWN ABOVE | | | THIS 9-FOOT MARK. THE GRADE THAT THE SLAB SITS ON | | | CANNOT BE HIGHER THAN THE TOP OF THE SLAB (AS EVIDENCED | | | BY SHEET S-411). ADDITIONALLY, THE AVERAGE FINISHED | | | GRADE IS NOT MEASURED FROM THE TOP OF THE POOL DECK | | | PAVERS, WHICH ARE THE VALUES USED BASED ON SHEET C-1). | | | THE BUILDING HEIGHT IS MEASURED FROM THE AVERAGE | | | FINISHED GRADE. | | | D. PLEASE EXPLAIN WHY THE NORTH ENTRY (37.83 LINEAR | | | FEET AT 6.29 FEET ELEVATION) DOES NOT INCLUDE THE LOWER | | | HEIGHTS SHOWN ADJACENT TO THE NORTH ENTRY WALL ON THE | | | WEST LIB POWDER AND EAST ? GUEST BATH (5.97 FEET | | | ELEVATION) FOR APPROXIMATELY 19 OF THE 38 FEET. THIS | | | WILL BRING THE 6.29-FOOT MEASURE DOWN. | | | | | | 2) UPDATED COMMENT: THERE ARE TWO SEPARATE KITCHEN | | | AREAS SHOWN, WHICH IS NOT PERMITTED IN A SINGLE-FAMILY | | | HOUSE. **** ALL SHEETS NEED TO BE UPDATED TO REFLECT | | | THE REMOVAL OF THE OVEN IN THE BUTLER PANTRY, INCLUDING | | | THE PIPING PLANS, THE POWER PLANS, THE ELECTRIC | | | SCHEDULES, AND THE MECHANICAL PLANS. -- ZONING WILL NOT | | | PASS THIS PERMIT UNTIL ALL PLANS REMOVE THE 2ND OVEN OR | | | INCLUDE THE NOTE THAT THERE WILL BE NO OVEN IN THE | | | BUTLER KITCHEN. HOWEVER, THE ELECTRIC SCHEDULE AND THE | | | POWER PLAN MUST BE REVISED SHOW THE REMOVAL OF THE OVEN | | | CIRCUIT, 240 OUTLET AND OVEN. | | | | | | 3) THE NEWLY SUBMITTED SHEET L1.0 SITE PLAN DOES NOT | | | MATCH THE APPROVED LANDSCAPE PERMIT PLAN, NOR DOES IT | | | MATCH THE LAYOUT SHOW ON SHEETS A-100 ARCHITECTURAL | | | SITE PLAN, C-1 SITE PLAN THE ELEVATION PLANS, AND S-101 | | | FOUNDATION PLAN. ALL PLANS MUST SHOW THE SAME, | | | ACCURATE, CODE COMPLIANT CONDITIONS. NOTE: SHEET C-1 | | | WAS NOT UPDATED TO REFLECT LATEST CHANGES, SO STAFF IS | | | UNABLE TO VERIFY CODE COMPLIANCE. | | | | | | 4) THE NEW SHEET L1.0 SHOWS A BBQ AREA AND OUTDOOR | | | SHOWER ON SCREENING WALL AND EXTENDED DECK WITHIN THE | | | REQUIRED FIVE-FOOT SIDE SETBACK. PROVIDE DETAILS ON | | | EACH OF THESE ITEMS. | | | | | | A. IF THE PAVED DECK IS LESS THAN 18 INCHES ABOVE | | | GRADE, IT MAY NOT BE LOCATED CLOSER THAN TWO FEET FROM | | | THE PROPERTY LINE. THIS WAS A COMMENT MADE UPON THE | | | FIRST PLAN REVIEW FOR THIS LOCATION, WAS CORRECTED AND | | | NOW APPLIES AGAIN. | | | B. A FIXED BBQ GRILL IS AN ACCESSORY STRUCTURE AND MUST | | | CONFORM TO THE REQUIRED MINIMUM SETBACKS. | | | C. THE SHOWER SCREEN WALL MAY NOT EXCEED SIX FEET ABOVE | | | THE GRADE OF THE PROPERTY TO THE SOUTH. THE SURVEY AND | | | SHEET C-1 INDICATE THAT THE EXISTING GRADE AT THE | | | PROPERTY LINE IN THIS LOCATION IS 3.4 FEET, WITH THE | | | PROPOSED DECK ELEVATION AT JUST UNDER NINE FEET. THIS | | | PROHIBITS ANY ADDITIONAL WALL HEIGHT AT THIS LOCATION. | | | D. NONE OF THE PIPING PLANS INCLUDE THIS NEW LAYOUT. | | | | | | 5) PLEASE DESCRIBE WHAT THE STORAGE RACK THAT IS NOW | | | SHOWN ON THE SOUTH SIDE OF THE BUILDING WILL BE USED | | | FOR AND PROVIDE AN ELEVATION DRAWING. | | | | | | 6) SEPARATE PERMITS ARE REQUIRED FOR THE ITEMS LISTED | | | BELOW. PLEASE NOTE THAT STAFF HAS NOT FULLY REVIEWED | | | ANY OF THE ITEMS AS PART OF THIS PERMIT APPLICATION TO | | | VERIFY THAT THE INFORMATION SHOWN COMPLIES WITH CODE | | | BUT HAS NOTED SOME ITEMS AS LISTED. THIS PERMIT REVIEW | | | IS ONLY FOR THE HOUSE. | | | | | | A. IRRIGATION | | | B. POOL - THE POOL CONFIGURATION HAS BEEN CHANGED. FULL | | | COMPLIANCE REVIEW WILL BE WITH THE REQUIRED POOL | | | PERMIT. | | | C. GENERATOR | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2022-05-27 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2022-05-27 |
Time |
11:06 |
Rev Time |
0.75 |
| Received By |
eschneid |
Date |
2022-05-18 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2022-05-18 09:11:16 | FAILED | | | | | | 1) UPDATED COMMENT: THANK YOU FOR PROVIDING THE AVERAGE | | | GRADE CALCULATION TABLE THAT USES A WEIGHTED AVERAGE | | | FOR THE PURPOSE OF ESTABLISHING THE STARTING POINT TO | | | MEASURE THE BUILDING HEIGHT. STAFF HAS NOT PREVIOUSLY | | | REVIEWED THIS AS A AVERAGE GRADE CALCULATION | | | METHODOLOGY AND HAS THE FOLLOWING COMMENTS. | | | | | | A. PROVIDE A 1ST FLOOR BUILDING PLAN THAT CLEARLY SHOWS | | | WHERE THE TABLE LOCATIONS ARE TIED TOO. THE ENTIRE | | | PERIMETER OF THE BUILDING NEEDS TO BE INCLUDED BASED ON | | | THE METHODOLOGY THAT YOU HAVE CHOOSEN. | | | B. THE TABLE NEEDS TO MATCH THE GRADE HEIGHTS SHOWN ON | | | THE ELEVATION DRAWINGS. THE CURRENT ELEVATION PLANS | | | SHOW THE MAJORITY OF THE ELEVATIONS LESS THAN WHAT IS | | | SHOWN ON THE TABLE, TO INCLUDE THE LABEL ON THE SOUTH | | | ELEVATION DRAWING THAT STATES, "8.5 NAVD AVERAGE | | | FINISHED GRADE", WHILE THE TABLE LISTS THE ENTIRE SOUTH | | | ELEVATION HEIGHT AS 9.15 NAVD. ADDITIONALLY, THE ENTIRE | | | SOUTH ELEVATION IS NOT AT EVEN 8.5 NAVD AS THE WEST | | | SIDE GRADE SLOPES DOWN. THERE ALSO SEEM TO BE | | | DISCREPANCIES WITH THE C-1 SITE PLAN AND THE ELEVATIONS | | | AND THE TABLE. | | | C. STAFF REVIEWED THE DRAWINGS AND BASED ON THE NORMAL | | | WAY THAT AVERAGE GRADE IS CALCULATED (CORNER POINTS OF | | | THE BUILDING), THE STAFF CALCULATED AVERAGE GRADE IS | | | APPROXIMATELY 7.5 NAVD, WHICH RESULTS IN THE HOUSE | | | EXCEEDING THE PERMITTED BUILDING HEIGHT. | | | | | | 2) REPEAT COMMENT: THERE ARE TWO SEPARATE KITCHEN AREAS | | | SHOWN, WHICH IS NOT PERMITTED IN A SINGLE-FAMILY HOUSE. | | | **** ALL SHEETS NEED TO BE UPDATED TO REFLECT THE | | | REMOVAL OF THE OVEN IN THE BUTLER PANTRY, INCLUDING THE | | | PIPING PLANS, THE POWER PLANS, THE ELECTRIC SCHEDULES, | | | THE MECHANICAL PLANS, THE REFLECTED CEILING PLAN, AND | | | THE FIRST FLOOR DIMENSION PLAN. -- ZONING WILL NOT PASS | | | THIS PERMIT UNTIL ALL PLANS REMOVE THE 2ND KITCHEN. | | | THIS NEEDS TO BE DONE WITH THIS ORIGINAL PERMIT AND NOT | | | AS A FUTURE REVISION. | | | | | | 34) SEPARATE PERMITS ARE REQUIRED FOR THE ITEMS LISTED | | | BELOW. PLEASE NOTE THAT STAFF HAS NOT FULLY REVIEWED | | | ANY OF THE ITEMS AS PART OF THIS PERMIT APPLICATION TO | | | VERIFY THAT THE INFORMATION SHOWN COMPLIES WITH CODE | | | BUT HAS NOTED SOME ITEMS AS LISTED. THIS PERMIT REVIEW | | | IS ONLY FOR THE HOUSE. | | | | | | A. DRIVEWAY AND APPROACH. | | | B. IRRIGATION | | | C. POOL - BY THE ZONING AND LAND DEVELOPMENT CODE | | | DEFINITION, THE PROPOSED POOL IS AN ABOVE GROUND | | | SWIMMING POOL. ABOVE GROUND SWIMMING POOLS ARE | | | PROHIBITED IN THE CITY OF WEST PALM BEACH. | | | ADDITIONALLY, A PORTION OF THE INFINITY EDGE CAPTURE | | | AREA IS WITHIN THE 25-FOOT FRONT SETBACK, WHICH IS NOT | | | PERMITTED. | | | D. GENERATOR | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-03-22 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2022-03-22 |
Time |
16:36 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2022-03-18 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2022-03-22 16:37:03 | FAILED | | | | | | 1) UPDATED COMMENT: PROVIDE THE HEIGHT DIMENSIONS IN | | | ACCORDANCE WITH THE CITY'S ZONING AND LAND DEVELOPMENT | | | CODE REGULATIONS - THE HEIGHT SHALL BE MEASURED AS THE | | | VERTICAL DISTANCE FROM THE AVERAGE ELEVATION OF THE | | | FINISHED GRADE OF THE BUILDING TO THE HIGHEST POINT OF | | | THE TOP OF THE STRUCTURE OF A FLAT ROOF, OR TO THE DECK | | | LINE OF A MANSARD ROOF, OR TO THE MEAN HEIGHT LEVEL | | | BETWEEN EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL | | | ROOFS. THE MEASURE POINT NEEDS TO START AT THE AVERAGE | | | FINISHED GRADE, NOT THE TOP OF THE FLOOR SLAB AND | | | INCLUDE THE HIGHEST RIDGE AND THE EAVE DIMENSIONS. **** | | | PLEASE PROVIDE HOW YOU DETERMINED THE AVERAGE ELEVATION | | | OF SIX INCHES BELOW THE SLAB WHEN THERE IS A | | | SIGNIFICANT PERCENTAGE OF THE GRADE FOR THE WESTERN | | | PORTION OF THE HOUSE IS 2-3 FEET BELOW THE SLAB. | | | | | | 2) REPEAT COMMENT: THERE ARE TWO SEPARATE KITCHEN AREAS | | | SHOWN, WHICH IS NOT PERMITTED IN A SINGLE-FAMILY HOUSE. | | | **** ALL SHEETS NEED TO BE UPDATED TO REFLECT THE | | | REMOVAL OF THE OVEN IN THE BUTLER PANTRY, INCLUDING THE | | | PIPING PLANS, THE POWER PLANS, THE ELECTRIC SCHEDULES, | | | THE MECHANICAL PLANS, THE REFLECTED CEILING PLAN, AND | | | THE FIRST FLOOR DIMENSION PLAN. | | | | | | 3) UPDATED COMMENT: THE PLANS SHOW ARTIFICIAL TURF, | | | WHICH IS ONLY LOCATED WITHIN THE SIDE OR REAR SETBACK, | | | WHICH IS NOT WHERE YOU HAVE SHOWN IT. **** THE RESPONSE | | | STATES THAT THE LANDSCAPE PLANS DO NOT SHOW ARTIFICIAL | | | TURF; HOWEVER, THERE IS A NOTE ON SHEET L1 THAT STATES, | | | "STRIP DRAIN UNDER ART TURF" AND SHEET C1 HAS AN AREA | | | LABELED AS "ARTIFICIAL TURF". | | | | | | 4) SEPARATE PERMITS ARE REQUIRED FOR THE ITEMS LISTED | | | BELOW. PLEASE NOTE THAT STAFF HAS NOT FULLY REVIEWED | | | ANY OF THE ITEMS AS PART OF THIS PERMIT APPLICATION TO | | | VERIFY THAT THE INFORMATION SHOWN COMPLIES WITH CODE | | | BUT HAS NOTED SOME ITEMS AS LISTED. THIS PERMIT REVIEW | | | IS ONLY FOR THE HOUSE. | | | | | | A. DRIVEWAY AND APPROACH. | | | B. IRRIGATION | | | C. POOL - BY THE ZONING AND LAND DEVELOPMENT CODE | | | DEFINITION, THE PROPOSED POOL IS AN ABOVE GROUND | | | SWIMMING POOL. ABOVE GROUND SWIMMING POOLS ARE | | | PROHIBITED IN THE CITY OF WEST PALM BEACH. | | | ADDITIONALLY, A PORTION OF THE INFINITY EDGE CAPTURE | | | AREA IS WITHIN THE 25-FOOT FRONT SETBACK, WHICH IS NOT | | | PERMITTED. | | | D. GENERATOR | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-12-13 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2021-12-13 |
Time |
13:58 |
Rev Time |
2.00 |
| Received By |
eschneid |
Date |
2021-12-08 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2021-12-13 14:00:29 | FAILED | | | | | | 1) PRIOR TO ZONING APPROVAL OF THIS PERMIT, YOU MUST | | | SUBMIT A LANDSCAPE PERMIT, WITH A CODE COMPLIANT | | | LANDSCAPE PLAN, FOR THE PROPERTY. YOU WILL NEED TO | | | UPLOAD THE LANDSCAPE PLANS THAT WERE PROVIDED WITH THIS | | | PERMIT UNDER A SEPARATE LANDSCAPE PERMIT. | | | | | | 2) STEPS, OPEN UNCOVERED PORCHES OR STOOPS, AND OPEN | | | TERRACES WHICH ARE THREE FEET OR LESS ABOVE GRADE MAY | | | ENCROACH INTO ANY REQUIRED SETBACK AREA TO A POINT NOT | | | CLOSER THAN TWO FEET TO THE PROPERTY LINE. THE TERRACE | | | AREA AND STEPS AT THE SOUTHEAST CORNER OF THE BUILDING | | | DOES NOT COMPLY WITH THIS REQUIREMENT AS IT IS WITHIN | | | TWO FEET OF THE PROPERTY LINE. | | | | | | 3) THERE ARE DISCREPANCIES BETWEEN THE PAVING SHOWN AT | | | THE TRACH AREA BETWEEN THE ENGINEER SITE PLAN AND THE | | | LANDSCAPE SITE PLAN. THE LANDSCAPE SITE PLAN SHOWS THE | | | PAVING TO THE WEST PROPERTY LINE, WHICH IS NOT | | | PERMITTED (TWO-FOOT SETBACK REQUIRED). | | | | | | 4) PROVIDE THE HEIGHT OF THE PATH LIGHTS. | | | | | | 5) PROVIDE THE HEIGHT DIMENSIONS IN ACCORDANCE WITH THE | | | CITY'S ZONING AND LAND DEVELOPMENT CODE REGULATIONS - | | | THE HEIGHT SHALL BE MEASURED AS THE VERTICAL DISTANCE | | | FROM THE AVERAGE ELEVATION OF THE FINISHED GRADE OF THE | | | BUILDING TO THE HIGHEST POINT OF THE TOP OF THE | | | STRUCTURE OF A FLAT ROOF, OR TO THE DECK LINE OF A | | | MANSARD ROOF, OR TO THE MEAN HEIGHT LEVEL BETWEEN EAVES | | | AND RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS. THE | | | MEASURE POINT NEEDS TO START AT THE AVERAGE FINISHED | | | GRADE, NOT THE TOP OF THE FLOOR SLAB AND INCLUDE THE | | | HIGHEST RIDGE AND THE EAVE DIMENSIONS. | | | | | | 6) PROVIDE THE HEIGHT OF THE CHIMNEY FROM THE AVERAGE | | | FINISHED GRADE. THE CHIMNEY MAY NOT EXCEED 33 FEET IN | | | HEIGHT. | | | | | | 7) THERE ARE TWO SEPARATE KITCHEN AREAS SHOWN, WHICH IS | | | NOT PERMITTED IN A SINGLE-FAMILY HOUSE. | | | | | | 8) THE PLANS SHOW ARTIFICIAL TURF, WHICH IS ONLY | | | LOCATED WITHIN THE SIDE OR REAR SETBACK, NOT WHERE YOU | | | HAVE SHOWN IT IN THE FRONT OF THE HOUSE. | | | | | | 9) SEPARATE PERMITS ARE REQUIRED FOR THE ITEMS LISTED | | | BELOW. PLEASE NOTE THAT STAFF HAS NOT FULLY REVIEWED | | | ANY OF THE ITEMS AS PART OF THIS PERMIT APPLICATION TO | | | VERIFY THAT THE INFORMATION SHOWN COMPLIES WITH CODE | | | BUT HAS NOTED SOME ITEMS AS LISTED. THIS PERMIT REVIEW | | | IS ONLY FOR THE HOUSE. | | | | | | A. DRIVEWAY AND APPROACH. | | | B. IRRIGATION | | | C. WALL AND GATES - TOP OF WALL ALONG ALL FRONTAGES | | | EXCEEDS HEIGHT ALLOWANCE OF 6 FEET WHEN MEASURED FROM | | | THE EXTERIOR GRADE AT THE PROPERTY LINE. A PORTION OF | | | THE WALL ENCROACHES INTO THE VISIBILITY TRIANGLE. | | | D. POOL - BY THE ZONING AND LAND DEVELOPMENT CODE | | | DEFINITION, THE PROPOSED POOL IS AN ABOVE GROUND | | | SWIMMING POOL. ABOVE GROUND SWIMMING POOLS ARE | | | PROHIBITED IN THE CITY OF WEST PALM BEACH. | | | ADDITIONALLY, A PORTION OF THE INFINITY EDGE CAPTURE | | | AREA IS WITHIN THE 25-FOOT FRONT SETBACK, WHICH IS NOT | | | PERMITTED. | | | E. GENERATOR | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|