Plan Review Details - Permit 21101169
Plan Review Stops For Permit 21101169
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-10-29 Cont ID  
Sent By cpuell Date 2021-10-29 Time 15:51 Rev Time 0.00
Received By cpuell Date 2021-10-29 Time 15:51 Sent To  
Notes
2021-10-29 15:52:27ADDRESS IS CORRECT FOR THE SCOPE OF WORK.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-12-27 Cont ID  
Sent By jleahy Date 2021-12-27 Time 13:09 Rev Time 0.00
Received By jleahy Date 2021-12-27 Time 13:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-11-09 Cont ID  
Sent By ppetty Date 2021-11-09 Time 09:09 Rev Time 0.00
Received By ppetty Date 2021-11-09 Time 09:06 Sent To  
Notes
2021-11-09 09:09:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A
 DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
 2.PROVIDE CUT SHEETS FOR ALL EQUIPMENT.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-12-17 Cont ID  
Sent By pleduc Date 2021-12-17 Time   Rev Time 0.00
Received By pleduc Date 2021-12-17 Time 10:38 Sent To  
Notes
2021-12-17 10:39:44THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS
 APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT.
  
 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED
 EGRESS
 DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE
 PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL
 LOCKING SYSTEMS
 RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED
 THAT ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF
 THE ELECTRICAL
 LOCK IS AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY
 OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING
 CONDITIONS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE
 DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE
 POWER SUPPLY TO
 THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION
 OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY ELECTRICALLY
 UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-11-15 Cont ID  
Sent By pleduc Date 2021-11-15 Time   Rev Time 0.00
Received By pleduc Date 2021-11-15 Time 09:09 Sent To  
Notes
2021-11-15 09:20:09THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF CARD READERS NO PRODUCTS
 SHEETS NOR POWER WIRING DETAILS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT
 SPEC SHEETS AND POWER WIRING DETAILS.
  
  
 2) THERE IS AN INDICATIONS OF A CARD READER AT ONE OF
 THE EXIT CORRIDOR DOORS THAT MENTIONS A KEY LOCK.
  
 REQUIRED EXIT DOORS AND DOORS WITH EXIT SIGNS OVER THEM
 SHALL HAVE FREE EGRESS.
  
 PLEASE PROVIDE CLARIFICATION AS TO WHAT THIS MEANS. THE
 USE OF A KEY TO EXIT IS NOT APPROVED.
  
  
  
 3) FOR INSTALLATION PURPOSES AND WHERE APPLICABLE;
  
 ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS
 APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT.
  
  
 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED
 EGRESS
 DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE
 PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL
 LOCKING SYSTEMS
 RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED
 THAT ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF
 THE ELECTRICAL
 LOCK IS AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY
 OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING
 CONDITIONS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE
 DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE
 POWER SUPPLY TO
 THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION
 OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY ELECTRICALLY
 UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
 PLEASE INDCATE AT WHAT DOORS THIS IS APPLICABLE OR
 INDICATE FREE EGRESS AT ALL LOCATIONS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-27 Cont ID  
Sent By jleahy Date 2021-12-27 Time 13:09 Rev Time 0.00
Received By jleahy Date 2021-12-14 Time 06:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-15 Cont ID  
Sent By lmarchan Date 2021-11-15 Time 10:28 Rev Time 0.00
Received By lmarchan Date 2021-10-27 Time 08:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-27 Cont ID  
Sent By jleahy Date 2021-12-27 Time 13:08 Rev Time 0.00
Received By jleahy Date 2021-12-27 Time 13:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-09 Cont ID  
Sent By ppetty Date 2021-11-09 Time 09:10 Rev Time 0.00
Received By ppetty Date 2021-11-09 Time 09:09 Sent To  
Notes
2021-11-09 09:11:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A
 DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  