Plan Review Details - Permit 21101107
Plan Review Stops For Permit 21101107
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-03-08 Cont ID  
Sent By jbrooks Date 2022-03-08 Time 12:52 Rev Time 0.00
Received By jbrooks Date 2022-03-08 Time 08:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-02-10 Cont ID  
Sent By rmcphers Date 2022-02-10 Time 13:47 Rev Time 0.00
Received By rmcphers Date 2022-02-10 Time 13:47 Sent To  
Notes
2022-02-10 13:47:31ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) ATTACHMENT DETAIL ON DRAWING A-03 DOES NOT SHOW THE
 ON CENTER SPACING OF THE BASE SHEET ATTACHMENTS FOR THE
 LAP AND NUMBER OF NAILING ROWS AND ON CENTER SPACING IN
 THE FIELD. ROOFING SYSTEM TO BE USED ON THE PROVIDED
 PRODUCT APPROVAL (18-0919.07) REQUIRES ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL (-52.5) - SEE GENERAL LIMITATION NUMBER 7 ON
 THE PRODUCT APPROVAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 07:32 Rev Time 0.00
Received By rmcphers Date 2021-12-15 Time 07:32 Sent To  
Notes
2021-12-15 07:32:48ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL (18-0919.07) REQUIRES ADDITIONAL SIGNED AND
 SEALED ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER
 FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER
 PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL
 (-52.5) - SEE GENERAL LIMITATION NUMBER 7 ON THE
 PRODUCT APPROVAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 10:29 Rev Time 0.00
Received By rmcphers Date 2021-10-27 Time 10:29 Sent To  
Notes
2021-10-27 10:32:31ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL (18-0919.07) REQUIRES ADDITIONAL SIGNED AND
 SEALED ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER
 FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER
 PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL
 (-52.5) - SEE GENERAL LIMITATION NUMBER 7 ON THE
 PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR
 DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED
 TO BE USED IN ELECTRONIC PLAN REVIEW. SHOW THE WIND
 DESIGN DATA USED PER 2020 FBC AND ASCE 7-16 - WIND
 SPEED - EXPOSURE - RISK CATEGORY - ETC.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-11-02 Cont ID  
Sent By amhamilt Date 2021-11-02 Time 12:00 Rev Time 0.00
Received By amhamilt Date 2021-11-02 Time 12:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-03-08 Cont ID  
Sent By jbrooks Date 2022-03-08 Time 12:51 Rev Time 0.00
Received By jbrooks Date 2022-03-01 Time 14:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-10 Cont ID  
Sent By rmcphers Date 2022-02-10 Time 13:53 Rev Time 0.00
Received By rmcphers Date 2022-02-08 Time 16:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 07:39 Rev Time 0.00
Received By rmcphers Date 2021-12-14 Time 07:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-03 Cont ID  
Sent By rmcphers Date 2021-11-03 Time 09:54 Rev Time 0.00
Received By lmarchan Date 2021-10-26 Time 07:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-03-02 Cont ID  
Sent By rmcdouga Date 2022-03-02 Time 09:16 Rev Time 0.00
Received By rmcdouga Date 2022-03-02 Time 09:16 Sent To  
Notes
2022-03-02 09:36:47SIGNED AND SEALED PLAN SHEET A-03 SENT TO STORAGE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-02-09 Cont ID  
Sent By pvalenti Date 2022-02-09 Time 08:26 Rev Time 0.00
Received By pvalenti Date 2022-02-09 Time 08:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-17 Cont ID  
Sent By lcrespo Date 2021-12-17 Time 07:27 Rev Time 0.00
Received By lcrespo Date 2021-12-17 Time 07:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 07:33 Rev Time 0.00
Received By rmcphers Date 2021-12-15 Time 07:33 Sent To  
Notes
2021-12-15 07:38:49SIGNATURE REVIEW
  
 DRAWING A-03 DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  