Plan Review Details - Permit 21101102
Plan Review Stops For Permit 21101102
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-11-23 Cont ID  
Sent By medwards Date 2021-11-23 Time 07:44 Rev Time 0.00
Received By medwards Date 2021-11-22 Time 11:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-16 Cont ID  
Sent By medwards Date 2021-11-16 Time 10:26 Rev Time 0.00
Received By medwards Date 2021-11-15 Time 13:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-03 Cont ID  
Sent By medwards Date 2021-11-03 Time 13:59 Rev Time 0.00
Received By medwards Date 2021-11-01 Time 06:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-28 Cont ID  
Sent By medwards Date 2021-10-28 Time 10:41 Rev Time 0.00
Received By medwards Date 2021-10-26 Time 08:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-11-23 Cont ID  
Sent By medwards Date 2021-11-23 Time 07:43 Rev Time 0.00
Received By medwards Date 2021-11-23 Time 07:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-11-16 Cont ID  
Sent By medwards Date 2021-11-16 Time 10:23 Rev Time 0.00
Received By medwards Date 2021-11-16 Time 10:23 Sent To  
Notes
2021-11-16 10:25:54PLEASE SEE 1ST CYCLE COMMENTS LISTED BELOW. THE DRAWING
 SUBMITTED IS FOR A SINGLE SYSTEM. THE ORIGINAL PERMIT
 APPLICATION LISTED 3 SYSTEM, THE NEW PERMIT APPLICATION
 IS FOR 2 SYSTEMS. PLEASE PROVIDE DRAWINGS TO REFLECT
 THE INFORMATION ON THE PERMIT APPLICATION.
  
 PLEASE SEE 1ST CYCLE REVIEW NOTES BELOW.
  
 1) THE PERMIT APPLICATION IS FOR AC CHANGE OUT OF 3
 LENNOX SYSTEMS W/ DUCTWORK REPLACEMENT BUT THE DRAWING
 PROVIDED SHOWS ONLY 1 SYSTEM. PLEASE PROVIDE DRAWINGS
 FOR EACH SYSTEM AS INDICATED ON THE PERMIT APPLICATION.
  
 2) PLEASE PROVIDE DRAWINGS OF THE COMPLETE SYSTEMS
 INCLUDING THE DUCT SIZES OF EACH DUCT, THE CONDENSATE
 PIPING, SIZE AND TERMINATION LOCATION ALONG WITH THE
 CONDENSING UNITS LOCATION AND TIE DOWN METHOD. FBC
 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-11-03 Cont ID  
Sent By medwards Date 2021-11-03 Time 13:58 Rev Time 0.00
Received By medwards Date 2021-11-03 Time 13:58 Sent To  
Notes
2021-11-03 13:59:25PLEASE SEE 1ST CYCLE REVIEW NOTES BELOW.
  
 1) THE PERMIT APPLICATION IS FOR AC CHANGE OUT OF 3
 LENNOX SYSTEMS W/ DUCTWORK REPLACEMENT BUT THE DRAWING
 PROVIDED SHOWS ONLY 1 SYSTEM. PLEASE PROVIDE DRAWINGS
 FOR EACH SYSTEM AS INDICATED ON THE PERMIT APPLICATION.
  
 2) PLEASE PROVIDE DRAWINGS OF THE COMPLETE SYSTEMS
 INCLUDING THE DUCT SIZES OF EACH DUCT, THE CONDENSATE
 PIPING, SIZE AND TERMINATION LOCATION ALONG WITH THE
 CONDENSING UNITS LOCATION AND TIE DOWN METHOD. FBC
 107.2.1
  
 3) THE DESIGNER OF THE DRAWINGS MUST INCLUDE A
 TITLEBLOCK WHICH HAS THEIR PRINTED NAME AND SIGNATURE.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-28 Cont ID  
Sent By medwards Date 2021-10-28 Time 10:34 Rev Time 0.00
Received By medwards Date 2021-10-28 Time 10:33 Sent To  
Notes
2021-10-28 10:40:571) THE PERMIT APPLICATION IS FOR AC CHANGE OUT OF 3
 LENNOX SYSTEMS W/ DUCTWORK REPLACEMENT BUT THE DRAWING
 PROVIDED SHOWS ONLY 1 SYSTEM. PLEASE PROVIDE DRAWINGS
 FOR EACH SYSTEM AS INDICATED ON THE PERMIT APPLICATION.
  
 2) PLEASE PROVIDE DRAWINGS OF THE COMPLETE SYSTEMS
 INCLUDING THE DUCT SIZES OF EACH DUCT, THE CONDENSATE
 PIPING, SIZE AND TERMINATION LOCATION ALONG WITH THE
 CONDENSING UNITS LOCATION AND TIE DOWN METHOD. FBC
 107.2.1
  
 3) THE DESIGNER OF THE DRAWINGS MUST INCLUDE A
 TITLEBLOCK WHICH HAS THEIR PRINTED NAME AND SIGNATURE.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-10-28 Cont ID  
Sent By medwards Date 2021-10-28 Time 10:41 Rev Time 0.00
Received By medwards Date 2021-10-28 Time 10:41 Sent To  
Notes
***NONE***