Plan Review Details - Permit 21101050
Plan Review Stops For Permit 21101050
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-02-09 Cont ID  
Sent By cpuell Date 2022-02-09 Time 09:55 Rev Time 0.00
Received By cpuell Date 2022-02-09 Time 09:55 Sent To  
Notes
2022-02-09 09:55:54SUITE 100 UPDATED INTO ALL DATABASES.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-01-30 Cont ID  
Sent By cpuell Date 2022-01-30 Time 08:14 Rev Time 0.00
Received By cpuell Date 2022-01-30 Time 08:14 Sent To  
Notes
2022-01-30 08:15:16PLAN INDICATE THAT THE WORK IS BEING DONE ON SUITE 100,
 SUITE 100 IS NOT A RECOGNIZED SUITE NUMBER, PLEASE
 PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR.
 PLEASE EMAIL TO [email protected] FOR FURTHER QUESTIONS
 YOU CAN ALSO CALL 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2022-02-03 Cont ID  
Sent By rmcphers Date 2022-02-03 Time 12:36 Rev Time 0.00
Received By rmcphers Date 2022-02-03 Time 12:36 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2022-01-11 Cont ID  
Sent By lmarchan Date 2022-01-11 Time 09:21 Rev Time 0.00
Received By lmarchan Date 2022-01-11 Time 09:21 Sent To  
Notes
2022-01-11 09:21:16PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-12-07 Cont ID  
Sent By rmcphers Date 2021-12-07 Time 13:25 Rev Time 0.00
Received By rmcphers Date 2021-12-07 Time 13:25 Sent To  
Notes
2021-12-07 13:25:39PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-11-16 Cont ID  
Sent By rmcphers Date 2021-11-16 Time 16:12 Rev Time 0.00
Received By rmcphers Date 2021-11-16 Time 14:29 Sent To  
Notes
2021-11-16 16:13:43PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-12-07 Cont ID  
Sent By rmcphers Date 2021-12-07 Time 13:25 Rev Time 0.00
Received By rmcphers Date 2021-12-07 Time 13:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-16 Cont ID  
Sent By rmcphers Date 2021-11-16 Time 16:12 Rev Time 0.00
Received By rmcphers Date 2021-11-16 Time 14:30 Sent To  
Notes
2021-11-16 16:12:29OFFICE ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW EXISTING FLOOR PLAN (DEMO PLAN).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-01-04 Cont ID  
Sent By fgiaquin Date 2022-01-04 Time 22:37 Rev Time 0.00
Received By fgiaquin Date 2022-01-04 Time 21:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-11-03 Cont ID  
Sent By jleahy Date 2021-11-03 Time 16:23 Rev Time 0.00
Received By jleahy Date 2021-11-03 Time 14:23 Sent To  
Notes
2021-11-03 16:23:25ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E5.1 45KVA TRANSFORMER:
  
 1) PRIMARY PROTECTION NOT GREATER THAN 125% OF PRIMARY
 CURRENT RATING 215.3(A), T450.3(B)(1), 240.4
  
 2) PRIMARY CONDUCTORS NOT LESS THAN 125% OF THE PRIMARY
 CURRENT RATING 110.14(C)(1)(A)(2), 215.2(A)(1)(A),
 310.15(B)(16)
  
 PAGE E3.1
  
 1) OUTLETS IN COMMON AREAS TO BE TAMPER RESISTANT TYPE
  
 PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A NOTE
 WILL SUFFICE. NEC 406.12;

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-04-01 Cont ID  
Sent By jleahy Date 2022-04-01 Time 10:47 Rev Time 0.00
Received By jleahy Date 2022-04-01 Time 10:47 Sent To  
Notes
2022-04-01 10:47:37VOICE AND DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-10-27 Cont ID  
Sent By   Date 2021-10-27 Time   Rev Time 0.00
Received By bdolan Date 2021-10-27 Time 09:21 Sent To  
Notes
2021-10-27 09:31:401) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-01-30 Cont ID  
Sent By cpuell Date 2022-01-30 Time 08:15 Rev Time 0.00
Received By cpuell Date 2022-01-26 Time 08:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-20 Cont ID  
Sent By shill Date 2022-01-20 Time 09:33 Rev Time 0.00
Received By shill Date 2022-01-06 Time 16:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-04 Cont ID  
Sent By fgiaquin Date 2022-01-04 Time 22:37 Rev Time 0.00
Received By fgiaquin Date 2021-12-02 Time 11:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-16 Cont ID  
Sent By rmcphers Date 2021-11-16 Time 16:14 Rev Time 0.00
Received By rmcphers Date 2021-10-26 Time 07:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-12-03 Cont ID  
Sent By medwards Date 2021-12-03 Time 06:51 Rev Time 0.00
Received By medwards Date 2021-12-03 Time 06:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-10-28 Cont ID  
Sent By medwards Date 2021-10-28 Time 09:34 Rev Time 0.00
Received By medwards Date 2021-10-28 Time 09:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-11-02 Cont ID  
Sent By lcrespo Date 2021-11-02 Time 10:47 Rev Time 0.00
Received By lcrespo Date 2021-11-02 Time 10:12 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status P Date 2022-02-03 Cont ID  
Sent By rgathrig Date 2022-02-03 Time 09:55 Rev Time 0.00
Received By rgathrig Date 2022-02-03 Time 09:55 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2022-01-31 Cont ID  
Sent By rgathrig Date 2022-01-25 Time 13:32 Rev Time 0.00
Received By rgathrig Date 2022-01-25 Time 13:32 Sent To  
Notes
2022-01-31 13:34:29GOOD AFTERNOON DARA NUNEZ
  
 THE COI PROVIDED DOES NOT COMPLY WITH THE LANGUAGE
 STATED IN 553.791(4)(B)
  
 ??.?A CERTIFICATE OF INSURANCE DEMONSTRATING THAT
 PROFESSIONAL LIABILITY INSURANCE COVERAGE IS IN PLACE
 FOR THE PRIVATE PROVIDER?S FIRM, THE PRIVATE PROVIDER,
 AND ANY DULY AUTHORIZED REPRESENTATIVE IN THE AMOUNTS
 REQUIRED BY THIS SECTION.?
  
 WE SEE CERTIFICATES SUBMITTED BY OTHER FIRMS HAVING
 THIS STATEMENT IN THE ?DESCRIPTION OF OPERATION? BOX.
 THE DOLLAR AMOUNT ON THE CERTIFICATE MORE THAN EXCEEDS
 THE REQUIREMENTS
  
 RICHARD GATHRIGHT
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2022-01-19 Time   Rev Time 0.00
Received By   Date 2022-01-19 Time   Sent To  
Notes
2022-01-20 09:33:40PER EMAIL SENT TO DARA NUNEZ ON 1/19/22
  
 IN THE PERMIT APPLICATION SUBMITTAL THERE WAS ONLY A
 NOTICE TO BUILDING OFFICIAL FOR INSPECTION ONLY. THE
 PRIVATE PROVIDER IS ROOP KHIRSUKHANI AND THE FIRM IS
 MTCI PROVIDE PROVIDER SERVICES. PLEASE SUBMIT THE
 PRIVATE PROVIDER?S , OR ANY DULY AUTHORIZED
 REPRESENTATIVE?S PROFESSIONAL LICENSE OR CERTIFICATION
 NUMBERS, QUALIFICATION STATEMENTS OR RESUMES, AND, A
 CERTIFICATE OF INSURANCE DEMONSTRATING THAT
 PROFESSIONAL LIABILITY INSURANCE COVERAGE IS IN PLACE
 FOR THE PRIVATE PROVIDER?S FIRM, THE PRIVATE PROVIDER,
 AND ANY DULY AUTHORIZED REPRESENTATIVE IN THE AMOUNTS
 REQUIRED BY 553.791 (17).
  
 AFTER THAT INFORMATION IS RECEIVED, THE CITY PERMITTING
 RECORD WILL BE UPDATED TO REFLECT THAT INSPECTIONS WILL
 BE PERFORMED BY A PRIVATE PROVIDER
  
 [email protected], [email protected], [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-07 Cont ID  
Sent By rmcphers Date 2021-12-07 Time 13:26 Rev Time 0.00
Received By rmcphers Date 2021-12-07 Time 13:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-11-16 Cont ID  
Sent By rmcphers Date 2021-11-16 Time 16:14 Rev Time 0.00
Received By rmcphers Date 2021-11-16 Time 16:14 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy