| Plan Review Stops For Permit 21100999 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
P |
Date |
2022-03-04 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-04 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-04 |
Time |
11:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2022-02-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-02-14 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-02-14 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2022-02-14 09:51:06 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-11-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-22 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-22 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2021-11-22 16:02:22 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2022-03-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-28 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-28 |
Time |
15:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2022-03-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-23 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-23 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2022-03-23 10:02:52 | CONDO REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | | | | 1) A FLAME SPREAD TEST REPORT FOR THE LAMINATE FLOOR IT | | | SELF IS NOT REQUIRED. PLEASE PROVIDE THE FLAME SPREAD | | | TEST REPORT FOR THE LAMINATE FLOORING AND THE | | | UNDERLAYMENT AS A SYSTEM - OR - A FLAME SPREAD TEST | | | REPORT FOR THE UNDERLAYMENT IT SELF. | | | | | | FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS | | | ATTACHED TO THE FLOORING) | | | | | | 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO | | | VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING | | | TO PROJECTDOX ( [email protected] ) | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-03-04 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-04 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-04 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2022-03-04 11:34:37 | CONDO REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | | | | DRAWING A-102 UNDER SCOPE OF WORK - FLOORING LAMINATE | | | ON MASTER BEDROOM TO BE REPLACED - YOU HAVE SUPPLIED | | | UNDERLAYMENT TEST REPORTS FOR TILE FLOORING - WHICH | | | WILL NOT WORK FOR THE FLAME SPREAD REQUIREMENT | | | | | | "C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS | | | ATTACHED TO THE FLOORING)" | | | | | | THE FLAME SPREAD TEST REPORT WILL NEED TO BE FOR THE | | | COMPLETE SYSTEM (LAMINATE FLOORING AND UNDERLAYMENT) OR | | | THE UNDERLAYMENT ALONE. | | | | | | 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: | | | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. | | | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING | | | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY | | | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP | | | CEILING DESCRIPTION) | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP | | | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING | | | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED | | | DROP CEILING DESCRIPTION) | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS | | | ATTACHED TO THE FLOORING) | | | | | | 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO | | | VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING | | | TO PROJECTDOX ( [email protected] ) | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-02-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-02-14 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-02-14 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2022-02-14 09:50:26 | CONDO REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | 2ND REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: | | | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. | | | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING | | | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY | | | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP | | | CEILING DESCRIPTION) | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP | | | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING | | | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED | | | DROP CEILING DESCRIPTION) | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS | | | ATTACHED TO THE FLOORING) | | | | | | 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO | | | VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING | | | TO PROJECTDOX ( [email protected] ) | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-11-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-22 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-22 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2021-11-22 16:03:11 | CONDO REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: | | | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. | | | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING | | | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY | | | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP | | | CEILING DESCRIPTION) | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP | | | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING | | | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED | | | DROP CEILING DESCRIPTION) | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS | | | ATTACHED TO THE FLOORING) | | | | | | 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO | | | VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING | | | TO PROJECTDOX ( [email protected] ) | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-02-14 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-02-14 |
Time |
19:01 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-02-14 |
Time |
18:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-11-17 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-11-17 |
Time |
22:49 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-11-17 |
Time |
22:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-02-02 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-02-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-02-02 |
Time |
10:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2021-10-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-10-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-10-26 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2021-10-26 15:42:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE INDICATIONS THAT PART THE MASTER BATHROOM | | | WALL IS A FIRE RATED TENANT SEPARATION WALL. | | | | | | ENSURE FIRE RATED TENANT SEPARATION WALLS ARE REPAIRED | | | TO THE EXISTING FIRE RATED SEPARATION. | | | | | | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT. | | | | | | | | | | | | 2) THERE ARE INDICATIONS OF FLOOR REPLACEMENT IN THE | | | MASTER BEDROMM HOWEVER, THERE ARE NO SPECIFICATIONS | | | SHEETS FOR THE UNDERLAYMENT AND FINISHED FLOOR, THAT | | | INDICATE MEETING THE REQUIREMENTS PER NFPA' | | | | | | THERE IS A CORRECT INDICATION ON SHEET A-102, FOR THE | | | WALL & CEILING FINSISHES; HOWEVER, PRODUCT SPEC SHEETS | | | ARE NEEDED FOR THE OFFICIAL RECORD OF BOTH PRODUCTS. | | | | | | PLEASE REVIEW AND PROVIDE SPEC SHEETS. | | | | | | | | | | | | 3) THE APPLICATION INDICATES APT. 2406 ; HOWEVER, THE | | | PLAN SHEETS INDICATE APT 206. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-03-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-23 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-18 |
Time |
08:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-03-04 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-04 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-02-25 |
Time |
08:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-02-14 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-02-14 |
Time |
19:01 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-02-01 |
Time |
15:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-11-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-22 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-10-21 |
Time |
15:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-02-08 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-02-08 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2021-11-02 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-11-02 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-11-02 |
Time |
12:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-03-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-23 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-23 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-02-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-02-14 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-02-14 |
Time |
09:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-11-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-22 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-22 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2021-11-22 16:08:11 | SIGNATURE REVIEW | | | | | | ALL OF THE DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED IN | | | ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES | | | NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN | | | DROP OFF THE ORIGINAL SIGNED AND SEALED | | | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING | | | DIVISION AT THE CITY HALL. | | | | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | |
|
|