| 2021-11-01 15:45:05 | 11/01/21 1ST POOL PLUMBING REVIEW**DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD |
| | CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW? THE PUMP'S |
| | MAXIMUM FLOW FROM ITS PUMP CURVE IS NO LONGER ALLOWED |
| | TO BE USED IN DETERMINING THE MAXIMUM SYSTEM FLOW RATE |
| | PER ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE |
| | 2013 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER |
| | MINUTE (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW |
| | RATE DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF |
| | THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE |
| | TDH CALCULATIONS MUST INCLUDE ALL THE SYSTEM |
| | COMPONENTS, INCLUDING SUCTION AND RETURN PIPING, |
| | FITTINGS, VALVES, CHLORINATOR HEATER, AND FILTER. ALL |
| | SYSTEM COMPONENTS EXCEPT THE PUMP. |
| | |
| | 2. WOULD YOU PLEASE SUBMIT THE POOL PUMP CURVE AND |
| | IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC |
| | TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS |
| | NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH |
| | CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2015 SECS. |
| | 4.4.9, 4.4.9.1. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |